Sensitivity Check For UHF PD Detection On Power Transformers
Sensitivity Check For UHF PD Detection On Power Transformers
0-7S03-8447-4/04/$20.00@2004IEEE. 5s
Authorized licensed use limited to: Hitachi Energy. Downloaded on May 31,2024 at 05:40:10 UTC from IEEE Xplore. Restrictions apply.
SENSITIVITY CHECK In the next step a simulation of the coupled frequency
spectrum from the spark gap to UHF-sensor 2 was performed.
An artificial pulse was injected in UHF-sensor 1. Changing
Description of the sensitivity check the voltage level to 14.2 V resulted in a comparable frequency
spectrum in the frequency range between 200 MHz up to 700
A procedure as described for the sensitivity check for GIS is
MHz, see the gray line in figure 4b. Thus the relation of 1.5
as follows [3]: V/pC can be used in further experiments to check the
1) In a laboratory setup use a PD-source with known sensitivity of the UHF-sensor 2 regarding a PD-source close to
magnitude (PC) and locate it close to sensor I .
UHF-sensor 1. If more than two sensors are present, this
Measure the frequency spectrum of the coupled
procedure is repeated for all sensors.
signal to sensor 2.
2) Use an artificial pulse generator to inject pulses at
sensor 1 and change the amplitude until a frequency
spectrum is detected at sensor 2, which is comparable
to the frequency spechum detected at sensor 2
originating from the PD source (see step 1).
59
Authorized licensed use limited to: Hitachi Energy. Downloaded on May 31,2024 at 05:40:10 UTC from IEEE Xplore. Restrictions apply.
Figure 6 shows the detected frequency spectra at the three The sensitivity matrix shown in table 1 can he checked by
UHF-sensors W2, W3 and W4 (blue graphs) located on the cross-correlating the results: the value measured at sensor W2
LV-side, when 45V pulses are injected in UHF-sensor WI, from injected pulses in sensor WI should approximate the
located on the high-voltage side. The background noise at same value measured at sensor WI when pulses are injected in
UHF-sensor is also displayed for comparison reasons (purple sensor W2. This offers an additional verification of the
graphs). From the figures the following observations can be sensitivity check. As can be seen in the table 1, there is only
made: IO-20% deviation between the obtained results and this
I) the injected pulses can be detected at all three confirms the sensitivity check.
UHF-sensors located on the LV-side;
2) the amplitude of the spectrum is highest at UHF-
sensor W3. This can be explained by the fact that WfJW2
coupler WI and W3 are opposite from each other
and a direct coupling path is present;
3) Two frequency ranges with good signal-to-noise
ratio can be concluded from 750-850 MHz and
from 1100-1750 MHz
-1000 4
0 500 1003 1500 2000 290 30W
lMHzl
W12W3
Figure 5 - Location of the UHF couplers on a 150 MVA power ~ .. .......... " , .. ......... ,
transformer:
a) on the low-voltage side
b) on the high-voltage side
,
0 500 lOW 1500 , 2000 2500 3003
IMHzl
Figure 6 - Examples of frequency spectra from injected pulses
in UHF sensor W1 detected at W2, W3 and W4. The purple line
The AREA of the measured frequency spectra are shown in is the background noise spectrum; the blue line is the signal
table 1. spectrum.
60
Authorized licensed use limited to: Hitachi Energy. Downloaded on May 31,2024 at 05:40:10 UTC from IEEE Xplore. Restrictions apply.
Table 1: Key-value AREA in (dB] as being processed Table 2 shows the processed key-value AREA for the
from frequency spectra measured from the sensitivity measured frequency spectra at all four UHF-sensors during
155 kV voltage application. A clear increase at couplers is
detected and is higher than the results fiom the sensitivity
check as shown in tahle 1. This means that the PD activity is
higher than 30 pC, which was unfortunately not confirmed by
a measurement because the noise level was above 150 pC.
reo
:m7 0 1 ’ . . . . . .
i m . I.,
:
.........................
. . . . : .;. ,;
: . . .;. . . . . . . . . . . . . . .j
. .
. . . . properties of the UHF-signals in the transformer to estimate
the location of the PD-source and to estimate more precisely
the magnitude of the discharge level.
0
0 CO 120 180 210 POD 360
.LI.
61
Authorized licensed use limited to: Hitachi Energy. Downloaded on May 31,2024 at 05:40:10 UTC from IEEE Xplore. Restrictions apply.