Analysis of EHV CT Failure Due To Improper Grounding of C Terminal
Analysis of EHV CT Failure Due To Improper Grounding of C Terminal
Analysis of EHV CT Failure Due To Improper Grounding of C Terminal
K. K. Jembukailas,
Larsen & Toubro Limited, Chennai
Introduction
K. K. Jembukailas,
Larsen & Toubro Limited, Chennai
Leakage
K. K. Jembukailas,
Larsen & Toubro Limited, Chennai
CT Analysis
Purpose
Procedure
Fig 6. Capacitance between concentric conducting
As case study, the equivalent circuit of Dead Tank CT is spheres
analysed using PSCAD with inclusion of the capacitance
values (actual values from manufacturer due to Considering two concentric conducting spheres of radii
insulation grading. Based on the values, the effect of "a" and "b", such that b>a and V=0 at r=b, V=Vo at r=a,
un-grounding "C" terminal is illustrated Vis à-vis effect the concentric capacitance between two spheres is
of grounding the same. given as C = Q/V
The same analysis can be done, on Live Tank designed Where V=Vo = Potential difference between two
CT also, where the Insulation Grading is done on spheres
Secondary Winding Conductor in this case, the
Q-Total charge on surface of sphere of radius r
insulation thickness reduces as one travels towards
bottom of the tank. The voltage distribution is uniform E-Electric field intensity, D-Electric flux density
when the "C" terminal is properly grounded. & non 𝛿 𝑉𝑜
uniform distribution of voltage as the "C" dielectric, D E=∆𝑉 = 𝛿𝑟
𝑉 = 1 1 𝑎𝑟 𝑉/𝑚
( − )𝑟 2
𝑏 𝑎
is always normal to the surface. terminal grounding
𝑉𝑜 𝑉𝑜
gets disturbed. 𝐷 = 𝜀𝐸 = −𝜀 1 1 𝑎𝑟 = −𝜀 1 1 C/m2
( − )𝑟 2 ( − )𝑟 2
𝑏 𝑎 𝑏 𝑎
Effect of Concentric Capacitance
As per boundary conditions between conductor and
The equivalent circuit of Current Transformer is shown dielectric, D is always normal to the surface.
in fig. 5. In Dead tank design CT, the primary conductor 𝑉𝑜
which is brought to the bottom tank, is to be insulated 𝜌𝑠 = |𝐷| = 𝜀 1 1 𝑎𝑟 C/m2
( − )𝑟 2
𝑏 𝑎
for the full rated voltage (VL/73) As the insulation is
𝑉𝑜
graded, floating/concentric capacitance is formed Q=𝜀 1 1 𝑥 4𝜋𝑟 2
( − )𝑟 2
across each layer resulting in voltage drop across these 𝑏 𝑎
capacitances. =𝜀
4𝜋𝑉𝑜
𝑎𝑟 C
1 1
( − )𝑟 2
𝑏 𝑎
𝑄 4𝜋𝜀
C= = 1 1 F
𝑉 ( − )
𝑏 𝑎
K. K. Jembukailas,
Larsen & Toubro Limited, Chennai
nearest insulating material or dielectric medium it "Tan? tests under normal conditions as given by the
causes a flash-over/breakdown [4]. manufacturer is 1100pF and current Sowing through
this capacitance is 83.7mA. So, the 1100pF capacitance
Grounding of “C” Terminal
is divided into different series capacitances depending
To know the effect/behaviour of dead tank CT with "C" on the number of graded insulation layers. Here the
terminal grounding, we have considered the floating insulation layers assumed 12. no’s for grading. The
capacitance equivalent circuit as shown in fig. 7 voltage drops leakage current, etc of the Capacitive
equivalent circuit when "C" terminal is grounded are
shown in fig. 8.
K. K. Jembukailas,
Larsen & Toubro Limited, Chennai
The equivalent circuit and resultant waveforms due to through the body which will slowly contaminate the
improper grounding of "C" terminal using PSCAD is across of and insulation When this condition continues
shown in fig 10 & fig 11 over a period of time, insulation deteriorates and
finally leads to insulation failure there by explosion of
CT
Observations
K. K. Jembukailas,
Larsen & Toubro Limited, Chennai
Table. Il Evaluated parameters with "C" terminal However, in order to ensure the proper connection of
grounding through high resistance. 'C' terminal, performance of periodical DGA (Dissolved
Gas Analysis) is also recommended
Voltag Capacitanc Voltage Leaka EC
e Drop e (pF) Drop ge (kVp) Conclusion
across across curre
each each layer nt As it is experienced as well as evident from above
divider (kVp) (mAp) analysis, the effect of un-grounding/improper
(kVp) grounding of "C" terminal can cause damages not only
49.74 C1=25853 EC1=14.4 50.4 305.6 to the Current Transformer but also to the surrounding
C2=23391 EC2=16 equipment & may result in fatal injuries to the
C3=22160 EC3=16.8 personnel working with the equipment. Hence, it is
C4=19698 EC4=18.95 recommended that the "C" terminal of CT should
C5=17235 EC5=21.67 always be properly grounded.
C6=14773 EC6=25.27
49.74 C7=16077 EC7=23.2
C8=13397 EC8=27.86 References
C9=12593 EC9=29.7
C10=11522 EC10=32.4 1. 735-kv Cascade Style Current Transformer,
49.74 C11=8250 EC111=45.2 Donald I. Johnston, Senior Member IEEE, and
C12=5500 EC121=67.9 Howard Lucas Senior member IEEE, IEEE
Transactions On power apparatus and systems
vol. pas-86, no. 10 October 1967.
Result
2. "Current transformer Assembly, United States
From Table I & II we can observe that, the voltage at Patent Den Tsuboji, Yokohama.
"C" terminal is zero under solidly grounded condition, 3. "System for monitoring the insulation Quality
while it shoots up close to the system voltage under of step graded insulated HCurrent
improper or un-grounding if this condition persist for Transformer, United States Patent, Thomas
long period, depending upon the healthiness of Meyer Pinellas Park.
surrounding insulation, CT may get damaged. 4. "An overview of technical challenges in “The
design of current transformers,” Nisha Das and
Trouble Shooting
Marian K Kazmierczuk Wright, State University.
This problem can be easily identified by conducting the
Tanδ test on the CT periodically which is used to
evaluate the insulation healthiness of the system.