Jazz ™Plc+Hmi Micro-PLC+HMI Installation Guide: JZ20-T10/JZ20-J-T10 JZ20-T18/JZ20-J-T18 JZ20-J-T20HS
Jazz ™Plc+Hmi Micro-PLC+HMI Installation Guide: JZ20-T10/JZ20-J-T10 JZ20-T18/JZ20-J-T18 JZ20-J-T20HS
Jazz ™Plc+Hmi Micro-PLC+HMI Installation Guide: JZ20-T10/JZ20-J-T10 JZ20-T18/JZ20-J-T18 JZ20-J-T20HS
* Note that for JZ20-J modules those dimensions are 7.5 mm (0.295”).
Unitronics 1
01/16 JZ20-T1X/JZ20-J-T1X/JZ20-J-T20HS
(1.409") (1.496")
DIN-rail mounting 35.8 mm 38 mm Panel mounting
Snap PLC onto the DIN rail Cut-out: 117 x 89mm (WxH)
(4.606”x 3.504”)
Note: Removing the unit requires clearance space. Recommendation: approximately 40mm (1.58”).
For UL listed module, in order to meet the UL508 standard, panel-mount this device on
the flat surface of a Type 1 enclosure.
Wiring
This equipment is designed to operate only in SELV/PELV/Class 2/Limited Power
environments.
All power supplies in the system must include double insulation. Power supply outputs
must be rated as SELV/PELV/Class 2/Limited Power.
Do not connect either the ‘Neutral or ‘Line’ signal of the 110/220VAC to device’s 0V pin.
Do not touch live wires.
All wiring activities should be performed while power is OFF.
Install an external circuit breaker. Guard against short-circuiting in external wiring.
Use appropriate circuit protection devices.
Unused pins should not be connected. Ignoring this directive may damage the device.
Double-check all wiring before turning on the power supply.
2 Unitronics
JZ20-T1X/JZ20-J-T1X/JZ20-J-T20HS 01/16
To avoid damaging the wire, use a maximum torque of 0.5 N·m (5 kgf·cm).
Do not use tin, solder, or any substance on stripped wire that might cause the wire
Caution
strand to break.
Install at maximum distance from high-voltage cables and power equipment.
Wiring Procedure
Use crimp terminals for wiring; use 3.31 mm ² –0.13 mm² wire (12-26 AWG):
1. Strip the wire to a length of 7±0.5mm (0.270–0.300“).
2. Unscrew the terminal to its widest position before inserting a wire.
3. Insert the wire completely into the terminal to ensure a proper connection.
4. Tighten enough to keep the wire from pulling free.
Wiring Guidelines
Use separate wiring ducts for each of the following groups:
o Group 1: Low voltage I/O and supply lines, communication lines.
o Group 2: High voltage Lines, Low voltage noisy lines like motor driver outputs.
Separate these groups by at least 10cm (4"). If this is not possible, cross the ducts at a 90˚angle.
For proper system operation, all 0V points in the system should be connected to the system 0V
supply rail.
Allow for voltage drop and noise interference with input lines used over an extended distance.
Use wire that is properly sized for the load.
Earthing the product
To maximize system performance, avoid electromagnetic interference as follows:
Use a metal cabinet.
Connect the 0V terminal directly to the earth ground of the system.
Use the shortest, less than 1m (3.3 ft.) and thickest, 2.08mm² (14AWG) min, wires possible.
Inputs
1. All the products comprise I0-I5; these digital inputs are arranged in a single group. Via wiring,
the entire group may be set to either pnp or npn.
2. The following information concerns JZ20-T10/JZ20-J-T10 and JZ20-T18/JZ20-J-T18:
I0 and I1 can function as high-speed counters or as normal digital inputs.
3. The following information concerns JZ20-J-T20HS:
I0, I1, and I4 can function as high-speed counters, as part of a shaft-encoder, or as
normal digital inputs.
I2, I3, and I5 can function as either counter reset, as part of a shaft-encoder, or as
normal digital inputs.
If I0, I1, I4 are set as high-speed counters (without reset), I2, I3, I5 can function as normal
digital inputs.
4. The following information concerns JZ20-T18/JZ20-J-T18 and JZ20-J-T20HS in addition to I0-
I5, these comprise the following:
I6 and I7 may be wired as either digital or analog inputs. These may be wired as either:
npn digital inputs
pnp digital inputs
analog (voltage) inputs
In addition, one input may be wired as a pnp input, while the other is wired as an analog input.
Note that if one input is wired as an npn input, the other may not be wired as an analog input.
5. The following information concerns JZ20-T18/JZ20-J-T18 and JZ20-J-T20HS:
AN0 and AN1 are analog (current) inputs.
Unitronics 3
01/16 JZ20-T1X/JZ20-J-T1X/JZ20-J-T20HS
JZ20-T18/JZ20-J-T18
Note: The inputs are arranged in two groups. You can wire one group as npn and the other as pnp,
or wire both groups as npn, or as pnp. In either case, the n/p pins must be connected.
Input wiring (I0-I7), npn (sink) Input wiring (I0-I7), pnp (source)
JZ20-J-T20HS
Note: The inputs are arranged in two groups. You can wire one group as npn and the other as pnp,
or wire both groups as npn, or as pnp. In either case, the n/p pins must be connected.
Input wiring (I0-I7), npn (sink) Input wiring (I0-I7), pnp (source)
4 Unitronics
JZ20-T1X/JZ20-J-T1X/JZ20-J-T20HS 01/16
HSC input wiring, npn (sink) HSC input wiring, pnp (source)
Unitronics 5
01/16 JZ20-T1X/JZ20-J-T1X/JZ20-J-T20HS
JZ20-J-T20HS
Analog inputs
Note: Shields should be connected at the signal source.
Analog Input wiring, current (JZ20-T18/JZ20-J-T18/JZ20-J-T20HS only)
2 or 3-wire,(AN0-AN1) 4-wire,(AN0-AN1)
The information in this document reflects products at the date of printing. Unitronics reserves the right, subject to all applicable laws, at any time, at its sole
discretion, and without notice, to discontinue or change the features, designs, materials and other specifications of its products, and to either permanently or
temporarily withdraw any of the forgoing from the market.
All information in this document is provided "as is" without warranty of any kind, either expressed or implied, including but not limited to any implied warranties of
merchantability, fitness for a particular purpose, or non-infringement. Unitronics assumes no responsibility for errors or omissions in the information presented in
this document. In no event shall Unitronics be liable for any special, incidental, indirect or consequential damages of any kind, or any damages whatsoever arising
out of or in connection with the use or performance of this information.
The tradenames, trademarks, logos and service marks presented in this document, including their design, are the property of Unitronics (1989) (R"G) Ltd. or other
third parties and you are not permitted to use them without the prior written consent of Unitronics or such third party as may own them
DOC05007-C7 01/16
6 Unitronics