UPS Datasheet
E200RU
1:1 1-3kVA
FEATURES
RACK / TOWER PLUG & PLAY HOT SWAPPABLE USB CONFIGURABLE
CONVERTIBLE INSTALLATION BATTERY CONNECTIVITY OUTLETS
HIGHLIGHTS
• High frequency, double conversion online technology • Lightning and surge protection
• Fully digitised DSP control • Short circuit and overload protection
• Wide input voltage range • Automatic fan speed control with load variation
• Cold start and programmable auto re-start functions • Emergency Power Off facility
• Advanced battery management • Smart RS232 and USB comms with monitoring software
• Selectable ECO mode for high efficiency operation • Optional relay or SNMP communications card
• Automatic battery charge in UPS off mode
DS-E200RU-03-0523
The Dale E200RU UPS range is the the new range of high FLEXIBLE CONFIGURATION
density double conversion On line UPS suitable for powering
The UPS is highly flexible and easy to configure. Programmable
a wide range of devices such as servers, storage systems,
functions can be set via software or manually via the front
VoIP telephony equipment, network and medical systems as
display panel. E200RU can be configured in the following
well as industrial applications.
operating modes:
At only 2U, the E200RU range is ideal for 19” rack cabinet
• On Line: maximum load protection and output voltage
installations.It has a practical, modern design and includes
waveform quality;
several performance advantages over traditional ON LINE UPS.
• ECO Mode: to increase efficiency (up to to 98%); allows you
The newly-designed inverter is one of the best energy
to select LINE INTERACTIVE technology;
conversion systems on the market, with a unity output power
factor and 92% operating efficiency in ON LINE Mode. • The output sockets can be programmed to disconnect less
critical loads during blackouts (Configurable outlet function).
For business continuity applications requiring long battery
runtimes, battery autonomy can be extended up to several
hours using up to 4 matching battery expansion packs. HIGH BATTERY RELIABILITY
• Automatic and manual battery test;
SIMPLIFIED INSTALLATION • Extendible runtime using matching battery cabinets.
(maximum 4 cabinets)
• E200RU+ can be installed as a tower or in 19” rack cabinets,
by simply pulling out and rotating the display panel;
INSTALLATION VERSATILITY
• Low noise (<50 dBA): the E200RU can be installed in any
environment thanks to its high frequency switching inverter E200RU can be used in a tower or rack format, by simply
and load-dependent digitally controlled fan; turning the display and adding the supplied handles or
optional runners.
• Operation guaranteed up to 40 °C (the components are
designed for high temperatures and are thus subject to less
stress at normal temperatures);
LOW NOISE LEVEL
Thanks to the use of high frequency components and load-
based fan speed control, the noise produced by the UPS is less
than 50 dB.
HIGH QUALITY OUTPUT VOLTAGE
• Even with non-linear loads (IT loads with a crest factor of up
to 3:1);
• High short circuit current on bypass;
• Filtered, stabilised and reliable voltage (ON LINE double
conversion technology (VFI compliant with EN62040-3) with
filters for the suppression of atmospheric disturbances;
• Power factor correction: UPS input power factor close to 1
and sinusoidal current uptake.
SOFTWARE INSTALLATION ACCESSORIES
UPS MONITORING SUITE UNIVERSAL RAIL KIT - For Rack Mount Applications
EMBS10/11/AR - Rack Mount EMBS for 1kVA UPS
COMMUNICATION ACCESSORIES EMBS10/11/PP - Wall Mount EMBS for 1kVA UPS
E-SNMP/1-MINI - SNMP card for network monitoring of UPS EMBS16/11/AR - Rack Mount EMBS for 3kVA UPS
E-RELAY/1-MINI - Volt-free card for status monitoring of UPS EMBS16/11/PP - Wall Mount EMBS for 3kVA UPS
MODEL E201RU E203RU
OVERVIEW
Active power (kVA) 1kVA 3kVA
Active power (kW) 1kW 3kW
Topology True Online Rack / Tower UPS
INPUT
Number of phases 1P + N + E
Connection Type IEC-C14 x 1 IEC-C20 x 1
Nominal voltage 200 / 208 / 220 / 230 / 240 Vac
Voltage Range 160 - 300 Vac
Frequency Range 40Hz - 70Hz (Auto-Detect)
Power Factor >0.99
OUTPUT
Number of Phases 1P + N + E
Connection Type IEC-C13 x 8 IEC-C13 x 8; IEC-C19 x 1
Power factor 1.0pf
Nominal voltage (V) 200 / 208 / 220 / 230 / 240Vac ± 1%
Frequency Range 50 - 60 Hz ± 0.1Hz
THD (Linear Load) <3%
THD (Non-Linear Load) <6%
Efficiency up to 90% up to 92%
Overload Capacity 105-110% for 10 Minutes, 111-130% for 1 Minute, >130% for 3 Seconds
Crest Factor 3:1
Short Circuit Protection Yes
Waveform Pure Sinewave
Transfer Time 0mS
BATTERIES
Battery Type 10 Year VRLA
DC Voltage 36VDC 72VDC
Battery Quantity 3 x 12V / 7Ah 6 x 12V / 7Ah
Backup Time @ Half Load 17 Minutes 11 Minutes
Backup Time @ Full Load 7 Minutes 5 Minutes
Charge Current 1A
Recharge time 90% Capacity after 5 hours
EXTERNAL BATTERY PACKS
Battery Pack Model EER201U EER203U
Maximum Number of External Packs 4 Packs
ENVIRONMENT
Temperature 0 °C - +40 °C
Relative Humidity 0-90%
Altitude <1500m
Storage Temperature -25 °C - +55 °C
Noise Level <50dB
Heat Loss 0.14kW 0.26kW
MODEL E201RU E203RU
DISPLAY
LCD Measurements Voltage / Frequency / Battery level / Backup Time / Output Load Watts & VA / Temperature
LED Indicators Alarm / Bypass Mode / Battery Mode / Inverter Mode
Alarm (Audible / Visual) Audible or Visual; Line Failure / Battery Low / Overload / System Fault
COMMUNICATIONS
Standard Standard RS232 / USB
SNMP Card E-SNMP/1-MINI (Optional)
Alarm Card E-RELAY/1-MINI (Optional)
WEIGHTS & DIMENSIONS
Weight (kG) 13.2kg 28.6kg
Dimensions (H x W x D) 86.5 x 440 x 430mm 86.5 x 440 x 600mm
Rack Space Required 2U
STANDARD ACCESSORIES
Manuals User Manual
Software Only with SNMP Card
Input Cables 3 Pin UK Plug
Output Cables IEC-C13 x 3
Data Cables RS232 & USB
OTHER
Standard Warranty Period 3 Years for Electronics / 1 Year for Batteries
Recommended EMBS EMBS10/11/AR or EMBS10/11/PP EMBS16/11/AR or EMBS16/11/PP
CONNECTIONS
EER200U Series Battery Pack 1-3kVA
MODEL EER201U EER203U
Compatible UPS Model E201RU E203RU
BATTERY
Battery Type 12V Valve Regulated Lead Acid (VRLA) maintenance free
Battery Life 10 Year design life at 20°C
Battery Capacity 7Ah
Maximum number of packs 4
Number of battery strings per pack 2
Nominal voltage 36V 72V
Battery Charger
AC Supply limits 208-256V
Protection Circuit breaker
DC charge voltage 41.25V 82.5V
DC charge current 2A
recharge time 8 hours to 90% capacity
charger output protection Fuse
Environment
Operating temperature 0 °C - +40 °C
Relative humidity 0-90% (non-condensing)
Altitude 1500m maximum
Storage temperature 0 °C - +40 °C
WEIGHTS & DIMENSIONS
Weight (kG) 30kg 44.6kg
Dimensions (H x W x D) 86.5 x 440 x 430mm 86.5 x 440 x 710mm
Pack(QTY) Autonomy Full Load (Minutes) Autonomy Half Load (Minutes)
UPS 1 2 3 4 1 2 3 4
E201RU 28 51 76 102 63 115 171 230
E203RU 18 33 50 67 41 75 112 151
EERS203U Series Battery Pack 3kVA
MODEL EERS203U
Compatible UPS Model E203RU / E203RSU
BATTERY
Battery Type 12V Valve Regulated Lead Acid (VRLA) maintenance free
Battery Life 10 Year design life at 20°C
Battery Capacity 7Ah
Maximum number of packs 4
Number of battery strings per pack 1
Nominal voltage 72V
Battery Charger
Protection Circuit breaker
DC charge voltage 82.5V
DC charge current 2A supplied by own mains feed
recharge time 8 hours to 90% capacity
charger output protection Fuse
Environment
Operating temperature 0 °C - +40 °C
Relative humidity 0-90% (non-condensing)
Altitude 1500m maximum
Storage temperature 0 °C - +40 °C
WEIGHTS & DIMENSIONS
Weight (kG) 30kg
Dimensions (H x W x D) 86.5 (2U) x 440 x 460mm
Pack(QTY) Autonomy Full Load (Minutes) Autonomy Half Load (Minutes)
UPS 1 2 3 4 1 2 3 4
E203RU 11 18 26 33 25 41 58 75
E203RSU 5 11 18 26 11 25 41 58
EERS203U-4U Series Battery Pack 3kVA
MODEL EERS203U
Compatible UPS Model E203RU / E203RSU
BATTERY
Battery Type 12V Valve Regulated Lead Acid (VRLA) maintenance free
Battery Life 10 Year design life at 20°C
Battery Capacity 7Ah
Maximum number of packs 3
Number of battery strings per pack 3
Nominal voltage 72V
Battery Charger
Protection Circuit breaker
DC charge voltage 82.5V
DC charge current Supplied by UPS
recharge time 8 hours to 90% capacity
Environment
Operating temperature 0 °C - +40 °C
Relative humidity 0-90% (non-condensing)
Altitude 1500m maximum
Storage temperature 0 °C - +40 °C
WEIGHTS & DIMENSIONS
Weight (kG) 68kg
Dimensions (H x W x D) 177 (4U) x 443 x 490mm
Pack(QTY) Autonomy Full Load (Minutes) Autonomy Half Load (Minutes)
UPS 1 2 3 1 2 3
E203RU 26 49 75 58 118 171
E203RSU 18 41 67 41 94 151
Looking for something more bespoke?
With our own purpose-built, manufacturing facility, we’re a one-stop
shop for our customers providing design consultancy, manufacture
and ongoing maintenance for our products.
What we do
• An end-to-end service - design, manufacture, install, commissioning
and servicing
• Experts in customised UPS solutions
• In-house mechanical and electrical design capability
• Solutions for any environment, application and location
• Industry-specific solutions including WIMES specified and PADS
Approved UPS
• In-house project management team to manage the development
and delivery of your product for exactly when you need it.
Get in touch with our team today to discuss your requirements.
[email protected]
0330 999 3000