الحسابات الهيدروليكية
الحسابات الهيدروليكية
الحسابات الهيدروليكية
for
Prepared By:
Acec Consultant
8/7/2024
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr al monagem factory
Hell Page 2
General Data
Project Title: al monagem factory Project File Name: al monajem..fiw
Designed By: Acec Consultant Date: 8/7/2024
Code Reference: NFPA 13,14/SBC 801 Approving Agency:
Client Name: Phone:
Address: City, State Zip Code:
Company Name: Representative:
Company Address: City And State:
Phone:
Building Name: Building Owner:
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:
Project Data
Description Of Hazard: Ordinary 1 Sprinkler System Type: Wet
Design Area Of Water Application: 1500 ft² Maximum Area Per Sprinkler: 130 ft²
Default Sprinkler K-Factor: 8.00 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 100.00 gpm Outside Hose Stream Allowance: 250.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm
Sprinkler Specifications
Make: Model:
Size: Temperature Rating: 155 F
Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 1500.00 ft²
Minimum Desired Density: 0.150 gpm/ft²
Application Average Density: 0.297 gpm/ft²
Application Average Area Per Sprinkler: 125.00 ft²
Sprinkler Flow: 445.27 gpm
Average Sprinkler Flow: 37.11 gpm
100
90
82
80
70
Pressure psi
60
50
40
30
20
10
0
1 2 3 4 5 6 7 8 9 10