Segment Protector

FieldConnex® Fieldbus
R2-SP-IC*
< 4 ... 12 outputs Ex ic (FISCO or Entity) or non-incendive (Div 2)
< Advanced fault isolation at the spur
< Segment Protector in Zone 2/Div. 2
< Instruments in Zone 2/Div. 2 or Zone 1/Div. 1
< For FOUNDATION Fieldbus H1 and PROFIBUS PA
< Advanced Diagnostics at the spur
< Power, Com, Diagnostics, and Error LEDs
< T-connector for easy installation and maintenance
< Test points for easy troubleshooting

Segment protector, junction box for fieldbus with short-circuit and fault protection, field junction box,
electronic component for control cabinet installation

Function
The R2 Segment Protector with integrated diagnostics, a device coupler for DIN rail installation, connects 4 ... 12 instruments to the segment with
intrinsic safety (Ex ic, Zone 2/Div. 2). Device connections in Zone 1/Div. 1 require additional methods of ignition protection. Short-circuit, jabber,
and bounce protection isolates most fault condition types from the segment. The short-circuit limit is adjustable for maximum load with Ex ic for
gas groups IIB and IIC.
The T-connector at the trunk allows for exchange of a Segment Protector with no effect on the remaining segment. The terminator is mounted at
the 'T' and removed for network extensions ensuring proper termination.
Short circuit protection ensures proper operation of the segment in case of unwanted faults at the spur. Intrinsic safety at the spur enables work on
devices with hot work permit. The integrated fieldbus terminator features a high-availability design.

Connection
+-S

T Trunk,
Ex nA
non-arcing
S-+

+-S

Spur I I Spur

PS
S-+

+-S

Spur I I Spur
Release date: 2024-09-20 Date of issue: 2024-09-20 Filename: t158642_eng.pdf

Spur 1 ... n
Ex ic

SP SP SP

Zone 2/Div. 2

Technical Data
General specifications
Design / Mounting Cabinet installation
Installation in hazardous area Zone 2 / Div. 2
Fieldbus connection
Main cable (Trunk)
Rated voltage 9 ... 31 V DC
10.5 V DC minimum input voltage acc. to FF-846
Rated current max. 4.5 A

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 1
Segment Protector R2-SP-IC*
Technical Data
Outputs
Number of outputs see table "Technical data depending on model"
Number of devices per output 1
Rated voltage max. 31 V
Rated current max. 32 mA switch 1, position 1
max. 43 mA switch 1, position 2
Short-circuit current 46 mA switch 1, position 1
57 mA switch 1, position 2
Self current consumption see table "Technical data depending on model"
Voltage drop main cable/outputs max. 1.2 V
Voltage drop trunk In/Out 0V
Terminating resistor external type M-FT 100 Ω +/- 10 %
Surge protection Trunk overvoltage protection if voltage exceeds typ. 39 V, max. 41 V
Indicators/operating means
Switch configuration of short-circuit current/rated current
LED PWR green: Fieldbus voltage > 10 V and fieldbus terminator is deactivated
LED COM/ERR yellow: flashing: fieldbus communication status and physical layer diagnostic status
LED SPURS red: 2 Hz flashing in short-circuit condition
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013
Standard conformity
Electromagnetic compatibility NE 21:2011
Degree of protection IEC 60529
Fieldbus standard IEC 61158-2
Climatic conditions IEC 60721
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Ambient conditions
Ambient temperature -50 ... 70 °C (-58 ... 158 °F)
Storage temperature -50 ... 85 °C (-58 ... 185 °F)
Relative humidity < 95 % non-condensing
Shock resistance 15 g 11 ms
Vibration resistance 1 g , 10 ... 150 Hz
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection type screw terminal , pluggable or spring terminal , pluggable
Core cross section see table 2
Release date: 2024-09-20 Date of issue: 2024-09-20 Filename: t158642_eng.pdf

Housing material Polycarbonate


Degree of protection IP20
Mass see table "Technical data depending on model"
Dimensions see table "Technical data depending on model"
Mounting DIN rail mounting
Data for application in connection with hazardous areas
EU-type examination certificate TÜV 12 ATEX 098651 X
Marking 1 II 3G Ex nA [ic] IIC T4 Gc
1 II (3)D [Ex ic Dc] IIIC
Supply
Maximum safe voltage Um 35 V
Outputs
Voltage Uo 32 V
Current Io 46 mA switch 1, position 1
65 mA switch 1, position 2
Inductance Lo 0.125 mH switch 1, position 1
0.25 mH switch 1, position 2

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 2
Segment Protector R2-SP-IC*
Technical Data
Capacitance Co 60 nF
Directive conformity
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approval E106378
Control drawing 116-0406
Approved for Class I, Division 2, Groups A, B, C, D
IECEx approval IECEx TUN 12.0015X
Approved for Ex nA [ic] IIC T4 Gc
[Ex ic Dc] IIIC
General information
Supplementary information Statement of Conformity, Declaration of Conformity, Attestation of Conformity and
instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.

Assembly
Release date: 2024-09-20 Date of issue: 2024-09-20 Filename: t158642_eng.pdf

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected] 3
Segment Protector R2-SP-IC*

Additional Information

Dimensions and Assembly

1 2 3 4 5 6 7 8

POSITION
7 8
S
_ + S
_ + S
_9 + S
10
_ + S
11
_ + S
12
_ +
1 2

+
_ S
PWR

77 (3")
COM +
_ S
+
_ S +
_ S +
_ S +
_ S +
_ S +
_ S
Trunk
1 2 3 4 5 6 PEPPERL+FUCHS
Segment Protector ®

A 37 (1.5")

42 (1.7")

60 (2.4")

All dimensions in millimeters (mm) and inches (") and without tolerance indication.

Description:
1 Connection spur 1
2 LED ERR spur 1 (red, short circuit)
3 LED COM/ERR (communication/diagnostics)
4 LED PWR (power)
5 Separation wall ACC-R2-SW.3
6 Switch, short circuit current selection
7 Terminator M-FT, removable
8 T-connector T-CON.3

Housing height "A" see table "Technical data depending on model".

Installation
see manual
Release date: 2024-09-20 Date of issue: 2024-09-20 Filename: t158642_eng.pdf

Electrical Connection

Table 1: Technical data depending on model


R2-SP-IC4* R2-SP-IC6* R2-SP-IC8* R2-SP-IC10* R2-SP-IC12*
Number of outputs 4 6 8 10 12
Housing height (A) 93 mm (3.7") 121 mm (4.7") 148 mm (5.8") 177 mm (7") 205 mm (8")
Mass 130 g 180 g 230 g 280 g 330 g
Quiescent current max. 15 mA max. 17 mA max. 17 mA max. 19 mA max. 19 mA
Power loss at 31 V input 470 mW** 530 mW** 530 mW** 590 mW** 590 mW**

** + 10 mW per spur at 20 mA load

Table 2: Wire cross section

Wire cross section Trunk terminals Spur terminals


Screw terminal flexible wire 0.2-2.5 mm2 0.2-2.5 mm2
rigid wire 0.2-2.5 mm2 0.2-2.5 mm2

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

4
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]
Segment Protector R2-SP-IC*
Spring terminal flexible wire 0.5-2.5 mm2 0.2-2.5 mm2
rigid wire 0.5-2.5 mm2 0.2-2.5 mm2

Type Code

Type of housing
R2 DIN mounting rail housing for cabinet installation
Function
SP Segment Protector
Explosion protection method
IC Ex ic, non-incendive field wiring rated spur outputs
Number of outputs (equipped with screw terminals)
04 4 spurs
06 6 spurs
08 8 spurs
10 10 spurs
12 12 spurs
Alternative terminal options
1 Spring terminals (instead of screw terminals)

R2 - SP - IC .
A - B - C D E

Delivery
Scope of Delivery

Type code Description


1 x M-FT Fieldbus Terminator
1 x T-CON.3 T-Connector
1 x TP-CON.3 per output Fieldbus plug sockets with test points
Release date: 2024-09-20 Date of issue: 2024-09-20 Filename: t158642_eng.pdf

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

5
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com [email protected] [email protected] [email protected]

You might also like