ABB SAM600 - I - O - Version - 2.2
ABB SAM600 - I - O - Version - 2.2
Contents
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no
responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
© Copyright 2017 ABB. All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or
registered trademarks of their respective holders.
2 ABB
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2 Issued: May 2019
Revision: C
ABB 3
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
IED supports IEC 61850-8-1 Ed1 or IEC 61850-8-1 Ed 2 Flexible Product Naming allows the customer to use an
communication for station bus and process bus. GOOSE IED vendor independent IEC 61850 model of the IED.
messaging is used between IED and control, and This customer model will be used as the IEC 61850 data
protection IEDs for providing status information of the model, but all other aspects of the IED will remain
primary apparatus, as well as subscribing to protection unchanged (e.g., names in the tools). This offers
trip and open/ close operations from the control IEDs. significant flexibility to adapt the IED to the customers'
For monitoring purposes, MMS communication through system and standard solution.
the station bus is also supported.
SAM600-IO LHMI service kit which can be connected to
Built-in redundant communication features such as PRP the IED is available as accessory for maintenance and
and HSR, and up to six communication ports allow to service operations.
embed the IED in a broad range of communication
architectures. Support for IEC/IEEE 61850-9-3 time The IED ships with an empty configuration at delivery.
synchronization enables the integration of the device With PCM600 Tool, required logic for interfacing primary
into state-of-the-art IEC 61850 station and process bus switchgear objects, adjusting function parameters, and
architectures. mapping binary I/O to signals are steps which need to
be performed by the customer.
Control operations of the primary switchgear is
performed from remote (SCADA/Station) via bay control The SAM600-IO basic delivery includes one binary input
IEDs through IEC 61850-8-1 Ed1 or Ed2. Cyber security module and one binary output module, which is
measures are implemented to secure safe autonomous sufficient for interfacing a single circuit breaker. The
operation of the control functions even if simultaneous SAM600-IO is available in two housing variants, ½ 19”,
cyber attacks occur. One IED can be used for interfacing as well as 1/1 19” form factor. Three instances of circuit
the primary switchgear of a single bay, or it can be used breaker and eighteen instances of switchgear objects
(in a 1/1 19” form factor) to interface multiple bays. are included in the basic delivery. For larger applications
covering, an optional circuit breaker package is available
Disturbance recording is available to allow independent which expands the number of controllable switching
post-fault analysis after primary disturbances in case of objects to nine circuit breakers and all operating at a
a failure in the protection system. 3ms cycle time.
Logic is prepared with a graphical tool. The advanced Figure 1 shows a typical usage of SAM600-IO in a double
logic capability allows special applications such as busbar arrangement, covering the I/O signals from all
automatic opening of disconnectors in multi-breaker primary switchgear objects. SAM600-IO is typically
arrangements, closing of breaker rings, load transfer chained in an HSR loop with SAM600 merging units on
logics and so on. The graphical configuration tool an IEC 61850 process bus, receiving and publishing IEC
ensures simple and fast testing and commissioning. 61850 GOOSE information to protection and control
IEDs, such as Relion 670 series.
Forcing of binary inputs and outputs is a convenient way
to test wiring in substations as well as testing
4 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
IEC17000159-1-en.vsdx
IEC17000159 V1 EN-US
ABB 5
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
6 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
SAM600-IO
Control
Logic
AND, GATE, INV, Basic configurable logic blocks (see Table 2) 40–160
LLD, OR,
PULSETIMER,
RSMEMORY,
SRMEMORY,
TIMERSET, XOR
ABB 7
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
AND 160
GATE 40
INV 80
LLD 40
OR 160
PULSETIMER 40
RSMEMORY 60
SRMEMORY 60
TIMERSET 40
XOR 40
SAM600–IO
Monitoring
8 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
SAM600– IO
Station communication
ABB 9
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
by utilities, in order to have different functions The trip matrix logic (TMAGAPC) function is used to
operating on pre-set values. Hardware switches are route trip signals and other logical output signals to
however sources for maintenance issues, lower system different output contacts on the IED.
reliability and an extended purchase portfolio. The
The trip matrix logic function has 3 output signals and
selector switch function eliminates all these problems.
these outputs can be connected to physical tripping
Selector mini switch VSGAPC outputs according to the specific application needs for
The Selector mini switch (VSGAPC) function block is a
SEMOD158756-5 v10
settable pulse or steady output.
multipurpose function used for a variety of applications,
Group alarm logic function ALMCALH
as a general purpose switch. GUID-16E60E27-F7A8-416D-8648-8174AAC49BB5 v4
The group alarm logic function (ALMCALH) is used to
VSGAPC can be controlled from binary inputs or via IEC route several alarm signals to a common indication, LED
61850. and/or contact, in the IED.
Generic communication function for Double Point Group warning logic function WRNCALH
GUID-F7D9A012-3AD4-4D86-BE97-DF2A99BE5383 v4
ABB 11
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
before the power interruption. RESET input has Boolean to integer conversion with logical node
priority. representation, 16 bit (BTIGAPC) is used to transform a
set of 16 boolean (logical) signals into an integer. The
• SRMEMORY function block is a flip-flop that can set or block input will freeze the output at the last value.
reset an output from two inputs respectively. Each
block has two outputs where one is inverted. The Integer to Boolean 16 conversion IB16 SEMOD158373-5 v6
memory setting controls if, after a power interruption, Integer to boolean 16 conversion function (IB16) is used
the flip-flop resets or returns to the state it had to transform an integer into a set of 16 boolean (logical)
before the power interruption. The SET input has signals.
priority.
Integer to Boolean 16 conversion with logic node
• TIMERSET function has pick-up and drop-out delayed representation ITBGAPC SEMOD158421-5 v9
outputs related to the input signal. The timer has a Integer to boolean conversion with logic node
settable time delay. representation function (ITBGAPC) is used to transform
an integer which is transmitted over IEC 61850 and
• XOR is used to generate combinatory expressions received by the function to 16 boolean (logic) output
with boolean variables. XOR has two inputs and two signals.
outputs. One of the outputs is inverted. The output
signal OUT is 1 if the input signals are different and 0 Comparator for integer inputs INTCOMP
GUID-A93564FA-0017-4939-A9C1-095DA0FD9832 v1
if they are the same. The function gives the possibility to monitor the level of
integer values in the system relative to each other or to
a fixed value. It is a basic arithmetic function that can be
Fixed signal function block FXDSIGN M15322-3 v15
used for monitoring, supervision, interlocking and other
The Fixed signals function (FXDSIGN) has nine pre-set logics.
(fixed) signals that can be used in the configuration of
an IED, either for forcing the unused inputs in other Comparator for real inputs REALCOMP GUID-E17A88D7-D095-4F36-9CD5-64EBFD2A1DEA v1
function blocks to a certain level/value, or for creating The function gives the possibility to monitor the level of
certain logic. Boolean, integer, floating point, string real value signals in the system relative to each other or
types of signals are available. to a fixed value. It is a basic arithmetic function that can
be used for monitoring, supervision, interlocking and
One FXDSIGN function block is included in all IEDs. other logics.
12 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
The event recording information is an integrated part of Insulation supervision for liquid medium (SSIML) is used
the disturbance record (Comtrade file). for monitoring the oil insulated device condition. For
example, transformers, shunt reactors, and so on. Binary
ABB 13
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
devices are used as input signals to the function. In An access point is an Ethernet communication interface
addition, the function generates alarms based on the for single or redundant station communication. Each
received information. access point is allocated with one physical Ethernet
port, two physical Ethernet ports are allocated if
Circuit breaker condition monitoring SSCBR
GUID-E1FD74C3-B9B6-4E11-AA1B-7E7F822FB4DD v13
redundant communication is activated for the access
The circuit breaker condition monitoring function point.
(SSCBR) is used to monitor different parameters of the
breaker condition. The breaker requires maintenance
Device 1 Device 1
when the number of operations reaches a predefined
value. For a proper functioning of the circuit breaker, it AP1 AP2 AP3 AP1 AP2 AP3
is essential to monitor the circuit breaker operation, SFP_301 SFP_302 SFP_303 SFP_301 SFP_302 SFP_303
IED as a boundary clock between several networks will source device in a subnetwork to the destination device
keep 1us accuracy on three levels or when using an HSR, in a different subnetwork. A route consists of a
15 IEDs can be connected in a ring without losing a destination address and the address of the gateway to
single microsecond in accuracy. be used when sending data to the destination device,
see Figure 3.
8. Ethernet
Access points
14 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
10. Hardware description The optical Ethernet module (OEM) provides two
additional optical Ethernet ports. The port connectors
Hardware modules IP14529-1 v1
are:
Numeric processing module NUM
M12643-3 v4
The numeric processing module (NUM) is a CPU module
that handles all protection functions and logic.
ABB 15
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
• SFP Optical LC
• Galvanic RJ45
A
D
IEC17000156-1-en.vsdx
IEC17000156 V1 EN-US
M2152-3 v8
B
C
E
IEC17000157-1-en.vsdx
IEC17000157 V1 EN-US
A
D
B C
IEC17000128-1-en.vsdx
IEC17000128 V1 EN-US
IEC08000165‐3‐en.vsdx
M15243-12 v10
IEC08000165 V3 EN-US
Figure 5. Case with rear cover and 19” rack mounting kit
16 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Case size A B C D E F G H I
(mm)/
(inches)
6U, 1/2 x 19” 265.9/ 223.7/ 247.5/ 255.0/ 205.8/ 190.5/ 466.5/ 232.5/ 482.6/
10.47 8.81 9.74 10.04 8.10 7.50 18.36 9.15 19
6U, 1/1 x 19” 265.9/ 448.0/ 247.5/ 255.0/ 430.1/ 190.5/ 466.5/ 232.5/ 482.6/
10.47 17.65 9.74 10.04 16.86 7.50 18.36 9.15 19
The G and H dimensions are defined by the 19” rack mounting kit.
ABB 17
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
18 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets
the specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to
perform its intended functions according to the specified requirements
GUID-1E949E38-E04D-4374-A086-912C25E9F93C v2
Presumptions for Technical Data For operate and reset time testing, the default setting
values of the function are used if not explicitly stated
otherwise.
ABB 19
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Power consumption -
each mA board £2W
each mA input £ 0.1 W
Auxiliary DC voltage
M12286-1 v9 IP15843-1 v3
Binary inputs 16 -
Power consumption
24/30 V, 50 mA max. 0.05 W/input -
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
20 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Maximum 176 binary input channels The stated operate time for functions
may be activated simultaneously with include the operating time for the
influencing factors within nominal binary inputs and outputs.
range.
M50609-2 v9
Table 7. BIM - Binary input module with enhanced pulse counting capabilities
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
ABB 21
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Maximum 176 binary input channels The stated operate time for functions
may be activated simultaneously with include the operating time for the
influencing factors within nominal binary inputs and outputs.
range.
M12573-1 v11
Binary inputs 8 -
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
* Note: For compliance with surge immunity a debounce filter time setting of 5 ms is required.
22 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Maximum 176 binary input channels The stated operate time for functions
may be activated simultaneously with include the operating time for the
influencing factors within nominal binary inputs and outputs.
range.
M12318-1 v10
Table 9. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Binary outputs 10 2
0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
ABB 23
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Maximum 72 outputs may be activated The stated operate time for functions
simultaneously with influencing factors include the operating time for the
within nominal range. After 6 ms an binary inputs and outputs.
additional 24 outputs may be
activated. The activation time for the M12584-1 v10
Table 10. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
24 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Maximum 72 outputs may be activated The stated operate time for functions
simultaneously with influencing factors include the operating time for the
within nominal range. After 6 ms an binary inputs and outputs.
additional 24 outputs may be
activated. The activation time for the SEMOD175395-2 v9
Table 11. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Number of outputs 6 6
Test voltage across open contact, 1 min No galvanic separation No galvanic separation
Continuous 5A 5A
1.0 s 10 A 10 A
0.2 s 30 A 30 A
1.0 s 10 A 10 A
220 V/0.2 A
250 V/0.15 A
ABB 25
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Table 12. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Number of outputs 6
Continuous 8A
1.0 s 10 A
0.2 s 30 A
1.0 s 10 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
26 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
M12441-1 v10
Table 13. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Binary outputs 24
Influencing factors
M16705-1 v16 IP15846-1 v1
ABB 27
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
100-250 V DC ±20%
Interruption
interval
0–50 ms No restart
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Level 3
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Level 4
Surge immunity test 2-4 kV, 1.2/50ms high energy IEC 60255-26, Zone A
1-2 kV, BOM and IRF outputs IEC 60255-26, Zone B
Conducted common mode immunity test 30-3 V, 15-150 Hz IEC 61000-4-16, Level 4
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Level 5
100 A/m, cont.
Pulse magnetic field immunity test 1000 A/m IEC 61000–4–9, Level 5
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Level 5
Change of temperature test Test Nb for 5 cycles at -25°C to +70°C IEC 60068-2-14
Damp heat test, steady state Test Ca for 10 days at +40°C and humidity 93% IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55°C and humidity 93 to 95% (1 cycle IEC 60068-2-30
= 24 hours)
Test According to
Vibration endurance test Class I: Rack, flush and wall mount IEC 60255-21-1
Shock response test Class I: Rack, flush and wall mount IEC 60255-21-2
Shock withstand test Class I: Rack, flush and wall mount IEC 60255-21-2
Bump test Class I: Rack, flush and wall mount IEC 60255-21-2
ABB 29
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
3 ms 8 ms
SMPPTRC 12 -
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v3
3 ms 8 ms
TMAGAPC 12 -
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v2
3 ms 8 ms
ALMCALH - 5
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v2
3 ms 8 ms
WRNCALH - 5
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v2
3 ms 8 ms
INDCALH - 5
GUID-D1179280-1D99-4A66-91AC-B7343DBA9F23 v3
3 ms 8 ms
AND 80 80
30 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
GUID-45DF373F-DC39-4E1B-B45B-6B454E8E0E50 v3
3 ms 8 ms
GATE 20 20
GUID-0EC4192A-EF03-47C0-AEC1-09B68B411A98 v3
3 ms 8 ms
INV 40 40
GUID-B2E6F510-8766-4381-9618-CE02ED71FFB6 v2
3 ms 8 ms
LLD 20 20
GUID-35A795D7-A6BD-4669-A023-43C497DBFB01 v4
3 ms 8 ms
OR 80 80
GUID-E05E5FB1-23E7-4816-84F2-1FBFFDFF2B43 v2
3 ms 8 ms
3 ms 8 ms
RSMEMORY 20 40
GUID-7A0F4327-CA83-4FB0-AB28-7C5F17AE6354 v2
3 ms 8 ms
SRMEMORY 20 40
GUID-C6C98FE0-F559-45EE-B853-464516775417 v3
3 ms 8 ms
ABB 31
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
GUID-0B07F78C-10BD-4070-AFF0-6EE36454AA03 v2
3 ms 8 ms
XOR 20 20
GUID-65A2876A-F779-41C4-ACD7-7662D1E7F1F2 v3
3 ms 8 ms
B16I 9 9
GUID-3820F464-D296-4CAD-8491-F3F997359D79 v2
3 ms 8 ms
BTIGAPC – 16
GUID-B45901F4-B163-4696-8220-7F8CAC84D793 v2
3 ms 8 ms
IB16 - 18
GUID-A339BBA3-8FD0-429D-BB49-809EAC4D53B0 v2
3 ms 8 ms
ITBGAPC - 16
GUID-B258726E-1129-47C9-94F9-BE634A2085FA v4
Table 41. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
3 ms 8 ms
TEIGAPC 18 36
GUID-CEA332FF-838D-42B7-AEFC-C1E87809825E v3
3 ms 8 ms
INTCOMP – 30
32 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v4
3 ms 8 ms
REALCOMP – 30
ABB 33
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Monitoring GUID-5E04B3F9-E1B7-4974-9C0B-DE9CD4A2408F
M16080-1 v6
v5
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording time and maximum number 340 seconds (100 recordings) -
of channels, typical value) at 50 Hz
34 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
GUID-F034B396-6600-49EF-B0A5-8ED96766A6A0 v8
Time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for pressure alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for pressure lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
GUID-83B0F607-D898-403A-94FD-7FE8D45C73FF v8
Time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for oil alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for oil lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Reset time delay for temperature alarm (0.000-60.000) s ±0.2% or ±250ms whichever is greater
Time delay for temperature lockout (0.000-60.000) s ±0.2% or ±250ms whichever is greater
GUID-B6799420-D726-460E-B02F-C7D4F1937432 v9
Independent time delay for spring charging (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
time alarm
Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
alarm
Independent time delay for gas pressure (0.00 – 60.00) s ±0.2% or ±30 ms whichever is greater
lockout
ABB 35
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
M12700-1 v4
Function Value
Resolution 1 ms
Function Value
Buffer capacity Maximum number of indications presented for single disturbance 352
Function Value
Resolution 1 ms
Fundamental Harmonic
Frequency (0.95 - 1.05) X fr 2nd order to 5th order (0.1 - 0.5) X V ± 2 mHz
Total Harmonic (10 to 150) V 2nd order to 5th order (0.1 - 0.5) X V ± 4%
Distortion
(VTHD)
36 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Function Value
Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for
communication using any protocol
Number of channels Up to 6 single or 3 redundant or a combination of single and redundant links for
communication using any protocol
Function Value
ABB 37
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Hardware
IED
M11778-1 v7 SEMOD53385-1 v1
Table 60. Water and dust protection level according to IEC 60529
View IP code
Electrical safety
GUID-1CF5B10A-CF8B-407D-8D87-F4B48B43C2B2 v2 GUID-2825B541-DD31-4DAF-B5B3-97555F81A1C2 v1
Pollution degree 2 (normally only non-conductive pollution occurs except that occasionally a temporary conductivity caused by
condensation is to be expected)
38 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
SEMOD53376-2
SEMOD53371-1
M12583-1 v8
v6
v1
Connection system
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)
GUID-96676D5D-0835-44DA-BC22-058FD18BDF34 v3
ABB 39
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Table 66. SAM600-IO – Typical application time delay for processing signals
BOM, binary 8 ms
output
SOM, static 5 ms
output
Data Value
Function Value
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled ± 1.0 ms typically
measurement values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically
GUID-8AEB81D0-1731-46DF-A206-D2E758823575 v2
Data Value
Supported types of clock Boundary Clock (BC), Ordinary Clock (OC), Transparent Clock (TC)
40 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management.
Please refer to the available functions table for included application functions.
PCM600 must be used to configure the IED.
To obtain the complete ordering code, please combine code from the selection tables, as given in the example below.
Example of a complete code: SAM600–IO*2.2 – F00 - H56P23P24 - AG - CA - CD1D1ARGN1N1XXXXXXX - KKKKXHPP. Using the code of each position #1-9
specified as SAM600-IO*1-2-3 3 3 –4 5-6 6-7 7 7 7 7 7 7 7 7 7 7 7 7 7 7-8 8 8 8 8 8 8 8
Product SAM600–IO*
Product version 2.2
Configuration alternative
Switchgear control unit SAM600–IO F00
Ordering number
Switchgear control unit SAM600–IO 1MRK002850-AA
Position
Product version #1 Notes and rules
Version no. 2.2
Selection for position #1 2.2
Position
Configuration alternative Ordering no #2 Notes and rules
Switchgear control unit SAM600–IO 1MRK004250-FA F00
Selection for position #2
Position
Software options Ordering no #3 Notes and rules
No option X00 All fields in the ordering
form do not need to be
filled in.
Circuit breaker 1MRK004001-VY H56
IEC 62439-3 Parallel redundancy protocol 1MRK004001-PP P23
IEC 62439-3 High-availability seamless redundancy 1MRK004001-PR P24
Selection for position #3
Position
Casing Ordering no #4 Notes and rules
1/2 x 19" rack casing 1MRK000151-VA A
1/1 x 19" rack casing 1MRK000151-VC D
Selection for position #4
ABB 41
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Position
Mounting details with IP40 of protection from the front Ordering no #5 Notes and rules
No mounting kit included X
19" rack mounting kit for 1/2x19" case or 2xRHGS6 or RHGS12 1MRK002420-BB A
19" rack mounting kit for 1/1 19" case 1MRK002420-CA C
Wall mounting kit 1MRK002420-LA G
Selection for position #5
Position
Power supply modules Ordering no #6 Notes and rules
Compression terminals 1MRK002960-GA C
Ringlug terminals 1MRK002960-HA R
Power supply module, 24-60 VDC 1MRK002239-AB A
Power supply module, 90-250 VDC 1MRK002239-BB B
Selection for position #6
When ordering I/O modules, observe the maximum quantities according to the tables below.
Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but
can also be freely placed.
Note: The maximum quantity of I/O modules depends on the type of connection terminals.
Case sizes BIM IOM BOM/ MIM Maximum in case
SOM
1/1 x 19” rack casing 14 6 4 4 14 *)
1/2 x 19” rack casing 3 3 3 1 3
*) including a combination of maximum four modules of type BOM, SOM and MIM
42 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
P3/X31
P4/X41
P5/X51
P6/X61
P7/X71
P8/X81
P9/X91
P10/X101
P11/X111
P12/X121
P13/X131
P14/X141
P15/X151
P16/X161
(front view/rear position p3. 1 BOM,
view) SOM or IOM is required
but freely placed.
1/2 case █ █ █ These black marks
indicate the maximum
1/1 case █ █ █ █ █ █ █ █ █ █ █ █ █ █
number of modules
per casing type and
the slots that can be
occupied.
Compression 1MRK002960-KA C
terminals
Ringlug 1MRK002960-LA R Only valid for 1/1 x 19"
terminals rack casing .
Only every second slot
can be used; see Table
74
No board in slot X X X X X X X X X X X X X
Binary output 1MRK000614-AB A A A A A A A A A A A A A
module 24
output relays
(BOM)
BIM 16 inputs, 1MRK000508-DD B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1 B1
RL24, 24-30VDC,
50mA
BIM 16 inputs, 1MRK000508-AD C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1 C1
RL48, 48-60VDC,
50mA
BIM 16 inputs, 1MRK000508-BD D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1 D1
RL110,
110-125VDC,
50mA
BIM 16 inputs, 1MRK000508-CD E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1 E1
RL220,
220-250VDC,
50mA
BIM 16 inputs, 1MRK000508-CE E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2 E2
RL220,
220-250VDC,
120mA
BIM 16 inputs, 1MRK000508-HA F F F F F F F F F F F F F F
RL24, 24-30VDC,
50mA, enhanced
pulse counting
BIM 16 inputs, 1MRK000508-EA G G G G G G G G G G G G G G
RL48, 48-60VDC,
50mA, enhanced
pulse counting
BIM 16 inputs, 1MRK000508-FA H H H H H H H H H H H H H H
RL110,
110-125VDC,
50mA, enhanced
pulse counting
BIM 16 inputs, 1MRK000508-GA K K K K K K K K K K K K K K
RL220,
220-250VDC,
50mA, enhanced
pulse counting
IOM 8 inputs, 1MRK000173-GD L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1
10+2 outputs,
RL24, 24-30VDC,
50mA
IOM 8 inputs, 1MRK000173-AE M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1 M1
10+2 outputs,
RL48, 48-60VDC,
50mA
ABB 43
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
44 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Station communication, remote end serial communication and Ordering no #8 Notes and rules
time synchronization
Slot position (front view/rear view)
P30:1/X301
P30:2/X302
P30:3/X303
P30:4/X304
P30:5/X305
P30:6/X306
P30:6:1/X3061
P30:6:2/X3062
Available slots in 1/2 and 1/1 case █ █ █ █ █ █ █ █
No communication board included X X X X
Ethernet SFP, optical LC connector 1MRK005500-AA K K K K K K Ethernet SFP is basic
in P30:1, P30:2, P30:3
Ethernet SFP, RJ45 connector 1MRK005500-BA P P P P P P
and P30:4. P30:6:1 and
P30:6:2 require the
Optical Ethernet
module in P30:6.
Optical Ethernet module 1MRK002266-EA H
Selection for position #9
ABB 45
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
Accessories IP15151-1 v1
Protection cover
M15040-3 v7
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-TA
Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-RA
Combiflex
SEMOD130267-5 v8 IP15161-1 v1
Mounting kit
Side-by-side mounting kit Quantity: 1MRK 002 420-Z
User documentation
Rule: Specify the number of printed manuals requested
Application manual IEC Quantity 1MRK 511 445-UEN
:
Communication protocol manual, IEC 61850 Edition 1 IEC Quantity 1MRK 511 440-UEN
:
Communication protocol manual, IEC 61850 Edition 2 IEC Quantity 1MRK 511 441-UEN
:
46 ABB
© Copyright 2017 ABB. All rights reserved
Switchgear control unit SAM600-IO 1MRK 511 448-BEN C
Version 2.2
For our reference and statistics we would be pleased to be provided with the following application data:
ABB 47
© Copyright 2017 ABB. All rights reserved
48
ABB AB
Grid Automation Products
SE-721 59 Västerås, Sweden
Phone +46 (0) 21 32 50 00
Scan this QR code to visit our website
www.abb.com/protection-control
1MRK 511 448-BEN