Manual Fire Detection Panel Salwico Workboat
Manual Fire Detection Panel Salwico Workboat
April 2010
Document no. 5100336-02A01
Part no: 5100336
© 2009-2010, Consilium AB
Quick Guide Quick Guide for Control Panel M 4.3
5100336-02A01 1
Quick Guide for Control Panel M 4.3 Quick Guide
2 5100336-02A01
Global Service and Support
Own companies
Sales- and service representatives
Consilium is constantly increasing and improving its global sales and service
organisation in order to provide our customers with the most competent
service and support. Today Consilium has established own companies in
16 countries plus sales and service representatives in more than 50 countries.
You will find updated contact information on our web-site www.consilium.se.
www.consilium.se
Salwico Cargo
Conventional Fire Detection
System
User Guide
Consilium Marine & Safety AB
Fire & Gas Marine Division
Phone: +46 31 710 77 00
Fax: +46 31 710 78 00
E-mail: Service: [email protected]
Spares: [email protected]
January 2012
Document no. 5100332-02B02
Part no. Part no: 5100332
1 Introduction ...................................................................................... 1
1.1 About This Manual .......................................................................... 1
1.2 Approvals .......................................................................................... 2
5 Operations ........................................................................................ 23
5.1 Access Levels .................................................................................... 23
5.2 Login ................................................................................................. 24
5.3 Fire Alarm ........................................................................................ 24
5.3.1 Information Displayed when “Fire” is Flashing ............................ 24
5.3.2 Mute a Fire Alarm .......................................................................... 25
5.3.3 Reset a Fire Alarm ......................................................................... 25
5.3.4 Several Alarms ............................................................................... 25
5.3.5 Type of Fire Alarms from Conventional Zones ............................. 25
6 Testing ............................................................................................... 33
6.1 About Testing .................................................................................... 33
6.2 Test Mode Overview ......................................................................... 33
6.3 Testing a Fire-detecting Zone .......................................................... 33
6.4 Recommended Test Equipment ........................................................ 34
6.5 Reset Test Mode ................................................................................ 34
6.6 Test the Control Panel Display ........................................................ 34
7 Appendix ........................................................................................... 35
7.1 Fault Code List ................................................................................. 35
7.2 Definitions of Terms ......................................................................... 40
Index ................................................................................................. 47
User Guide 1 Introduction
1 Introduction
NOTE!
This guide is valid for Control panel software versions beginning with version
1.0.0.
The chapter Fire Detection System gives general information about the system.
The chapter Control Panels describes the function of the Control panel and the
Repeater in the Fire detection system.
The chapter Operations describes how to operate the Fire detection system.
The chapter Testing provides brief instructions on how to connect and test the
system (detailed information is found in the Service & Maintenance manual).
The Fault Code List in the Appendix lists the different fault codes.
5100332-02B02 1
1 Introduction User Guide
1.2 Approvals
2 5100332-02B02
User Guide 2 Symbols Used in the Manual
DANGER!
Risk of serious or fatal injury to the user, and/or severe damage to the product, if
the instructions are not followed.
WARNING!
Risk of personal injury and/or damage to the product if the instructions are not
followed.
CAUTION!
Risk of minor or moderate personal injury. Risk of equipment damage, loss of data,
extra work, or unexpected results, if the instructions are not followed.
NOTE!
Note symbols alert you to important facts and conditions.
Hint
Tip symbols direct you to specific instructions, such as where to find additional
information and tell you how to perform a certain operation in an easier way.
5100332-02B02 3
2 Symbols Used in the Manual User Guide
4 5100332-02B02
User Guide 3 Fire Detection System
5100332-02B02 5
3 Fire Detection System User Guide
6 5100332-02B02
User Guide 4 Control Panels
4 Control Panels
As shown in the figure above, the control panel is divided into three sections:
A = System Indicators
B = Operational Controls
C = Numerical Keypad
5100332-02B02 7
4 Control Panels User Guide
1. Power
Steady green light Power supply to the control panel is OK.
2. System fault
Main process fault. A serious system fault in the
Flashing yellow light
system.
3. Test
Steady yellow light At least one zone is manually set in test mode.
4. Warning
Steady yellow light At least one warning indication exists.
5. Zone
Steady yellow light At least one zone or a fire detector is disabled.
At least one zone or a fire detector is in fault condition.
Flashing yellow light
(Priority over disablement indication.)
6. Alarm device
At least one alarm device output (e.g., a bell) is
Steady yellow light
disabled.
Flashing yellow light At least one alarm device output is in fault condition.
9. USB
USB connection for flash memories to load or save a configuration file.
8 5100332-02B02
User Guide 4 Control Panels
1. Main indicators
Fire alarm
The Fire alarm button indicates existance of a fire alarm and gives direct access
to the Fire alarm list.
Indications:
Flashing red light An un-muted fire alarm in the system.
Steady red light All fire alarms are muted.
Pre-Alarm
Note! Only for analogue addressable systems.
The Pre-Alarm button indicates existance of a pre-alarm and gives direct access
to the Pre-Alarm list.
Indications:
Flashing orange light An un-muted pre-alarm in the system.
Steady orange light All pre-alarms are muted.
Fault
The Fault button indicates existance of a fault and gives direct access to the
Fault alarm list.
Indications:
Flashing yellow light An un-muted fault in the system.
Steady yellow light All faults are muted.
Disablements
The Disablements button indicates existance of a disablement and activates the
Disablements menu.
Indications:
Steady yellow light At least one disabled function in the system.
Shortcuts
The Shortcut button activates the customer specific shortcut list.
5100332-02B02 9
4 Control Panels User Guide
Indications:
Steady orange light The alternatives in the shortcut list and the
corresponding indicators (Shortcut 1, Shortcut 2 and
Shortcut 3) are programmed via the definition
program.
2. Status
This button gives direct access to the System status summary list with Alarms
(Fire and Pre-Alarms), Maintenance (Faults and Warnings) and Disablements
(Active and Periodic).
Shortcuts are:
1. Upload the system log to USB Memory stick.
2. Go to the maintenance menu.
3. Menu
This button gives direct access to the main menu and all system functions.
4. Navigation and Command Keys
The arrow keys are used to navigate menus, select different menu alternatives,
and show details for list items.
Go to the previous item in the list or
menu.
ESC
The Escape button is used to go to the top menu screen.
OK
This button is used to select a menu alternative or to accept a function. The OK button
is also in some cases used to show details for a selected list entry.
5. Display
The display has a backlited 4.3" graphical screen, 480×272, 16-bit colour
screen.
6. Alarm buttons
Multiple alarms
Press this button to scroll through the different alarms. The list always returns to the
first fire alarm after 30 seconds of inactivity.
Reset
10 5100332-02B02
User Guide 4 Control Panels
Mute
This red button is used to mute (acknowledge) and silence alarms.
1. Numerical keypad
Keys 0 - 9
The numerical keypad is used to enter numerical values. Keys 1–9 are also used as
shortcuts when navigating in the menus.
Erase
This button is used to erase characters from the text display.
Enter
This button is used to select a menu alternative or to accept a function. The Enter
button is also used to show details for a selected list entry.
Day mode
Increase the brightness/contrast level for the indicators and display on the panel.
Night mode
Decrease the brightness/contrast level for the indicators and display on the panel.
5100332-02B02 11
4 Control Panels User Guide
In the lower part of the display the different options available for each individual
menu are shown.
The numerical keypad is used to enter information, e.g., zone and detector number.
NOTE!
All menus are shown in the system, as described below. But depending on the
actual system configuration some menu alternatives can have limited function.
12 5100332-02B02
User Guide 4 Control Panels
3 Disablements (3)
1 New disablement1 (3.1)
1 Zones (3.1.1)
Choose Zone and Zone Type
1 Permanent disablement
2 Timer disablement
3 Clock disablement
4 Periodic disablement
2 Detectors & Manual Call Points (3.1.2)
Note! Only for analogue addressable systems
Choose Zone, Detector Type and Detector
1 Permanent disablement
2 Timer disablement
3 Clock disablement
4 Periodic disablement
3 External Controls (3.1.3)
1 External Controls (3.1.3.1)
1 All groups (Doors, Fire, etc.) (3.1.3.1.1)
2 Doors (3.1.3.1.2)
3 Fire (3.1.3.1.3)
4 Fault (3.1.3.1.4)
5 Ventilation (3.1.3.1.5)
6 Indication (3.1.3.1.6)
2 Alarm Transfer (3.1.3.2)
4 Alarm Device (Bells etc.) (3.1.4)
5 Alarm Delay (3.1.5)
1 Permanent disablement
2 Timer disablement
3 Clock disablement
4 Periodic disablement
6 Test Mode (3.1.6)
2 Disablement list* (3.2)
1 Reset (reconnect) (3.2.1)
3 Periodic Disable list* (3.3)
4 Old Disablements (3.4)
5 Remove all disablements (3.5)
5100332-02B02 13
4 Control Panels User Guide
4 Login (4)
5 Settings (5)
1 Set Dimmer (5.1)
2 Set Time (5.2)
3 Set Date (5.3)
4 Test display (5.4)
5 Alarm Delay Times2 (5.5)
1 Alarm Delay Time 1 (mute)
2 Alarm Delay Time 2 (reset)
6 Keyboard Beep (5.6)
7 Cause Effect in Test Mode (5.7)
3 Modules* (6.3)
0 Disable Modules
2 Module Inputs
0 Disable
2 Set Input
3 Clear Input
3 Module Outputs
0 Disable
2 Set Output
3 Clear Output
4 Loops
Select Loop Units (only when addressable loop)
14 5100332-02B02
User Guide 4 Control Panels
7 History (7)
1 Fire History List* (7.1)
2 Fault History List* (7.2)
3 Disable History List* (7.3)
4 Common History List* (7.4)
8 Maintenance (8)
Note! Only for analogue addressable systems
1 Lightly Contaminated Detectors (8.1)
2 Heavily Contaminated Detectors (8.2)
5100332-02B02 15
4 Control Panels User Guide
Home
The top-level menu displays system and the name of the installation (if defined).
Fault Alarms
1 Fault Alarms
The menu from which fault- and warning messages are listed and handled.
1.1 Fault List
Shows all present fault indications.
1.2 Warning List
Shows all present warning messages, for instance a dirty detector.
1.3 Reset All Faults
The system will attempt to reset all present fault alarms in the Fault List (1.1).
Fire Alarms
2 Fire Alarms
Fire alarms and pre-alarms are displayed and managed from this menu. Muted
alarm devices may be reactivated here.
2.1 Fire List
Shows all present Fire Alarms.
2.2 Pre-Alarm List
Shows all present Pre-Alarms.
2.3 Resound (restart bells)
If the alarm devices have been silenced by pressing Mute button , this
function will restart them (if the fire alarm has not been reset).
2.4 Reset All Fire Alarms
The system will attempt to reset all Fire Alarms in the Fire List (2.1)
Disablements
3 Disablements
Disablemented parts of the Fire detection system are added, removed, or listed
from this menu. (For instructions, see Disablements, page 27.)
3.1 New Disablements (access level 2B)
Adds new disablements.
3.1.1 Zones
Disable entire zones for a specified time period or permanent.
3.1.2 Detectors & Manual Call Points
Note! Only for analogue addressable systems.
Disable individual detectors or manual call points for a specified time period or
permanent.
3.1.3 External Control
Deactivate External Controls or an Alarm Transfer.
3.1.3.1 External Controls
Disables outputs (all or individual categories) to external controls. This means
that an alarm condition will not cause activation of the selected category.
16 5100332-02B02
User Guide 4 Control Panels
5100332-02B02 17
4 Control Panels User Guide
Login
4 Login
Log in from this menu by entering a personal access code. For further details see
section Login, page 24.
Settings
5 Settings
Use this menu to adjust system parameters, such as the dimmer level, date, time
and alarm delay time.
It is also possible to make a lamp test for the control panel under “Test display”
(5.4).
5.1 Set Dimmer
Use this menu to adjust the contrast level (1–9) for the display and indications on
the control panel.
5.2 Set Time
Use this menu to set the system time.
It is possible to synchronize the system clock with the ship's central time.
5.3 Set Date
Use this menu to set the system date.
5.4 Test display
Use this menu to activate a lamp test that verifies correct function of the display
and all indications on the control panel.
5.5 Alarm Delay Times (access level 3)
Use this menu to adjust the programmable alarm delay time (max 2 minutes).
5.6 Keyboard Beep
Use this menu to turn the keyboard beep ON or OFF.
5.7 Cause Effect in Test Mode
Use this menu to turn the Cause Effect programming ON or OFF during test
mode. If set to ON, the outputs are activated as normal during test mode.
Service Menu
Service Menu (access level 2 for basic functions, but access level 4 is needed to
6
perform advanced service options)
Use this menu to list and view information about the system and its components.
It is also possible to make disablements of the listed units. The Service menu is
described in more detail in the separate Service and Maintenance manual.
6.1 System Details
This menu lists the installed system's information, such as name and reference
number (if defined). It also lists when the system was last configured and by
which program.
6.2 Centrals
Use this menu to list information about the installed centrals and the modules in
each central.
18 5100332-02B02
User Guide 4 Control Panels
6.3 Modules
Use this menu to list information about the installed system modules. It is
possible to display all details about the modules, such as installed detector loops,
installed program versions, input/output status. It is also possible to print
information.
6.4 Zones
This menu shows a list of all zones configured in the system. It is possible to list
all loop units in a zone if the zone consists of addressable loop units, disable
zones or loop units, and set a single fire detector in alarm condition.
6.5 Loops
This menu shows a list of all physical loops installed in an analogue addressable
system. A loop can consist of conventional or addressable fire alarm detectors
and other loop units. It is also possible to disable entire loops. Use Scan Loop to
scan the loop for new loop units.
6.6 Reload configuration
Reload the configuration when a new updated configuration file or
supplementary text file has been downloaded to the system.
6.6.1 Load entire configuration
Use this command to reload the configuration. The system will restart.
6.6.2 Load Supplementary Texts only
Use this command to reload all supplementary texts from the configuration file
without a system restart.
6.7 Load configuration from USB Memory
Download a new configuration file from a suitable USB Memory stick.
6.8 Save configuration to USB Memory
Copy the existing configuration file to a suitable USB Memory stick.
6.9 Save changes to configuration
CAUTION!
It is highly recommended to backup the Configuration File before
continuing.
Use this command to save all changes made from the control panel to the system
configuration.
NOTE!
The changes are not permanently saved in the configuration file until this
command is performed.
6.10 Synchronize system configuration
CAUTION!
It is highly recommended to backup the Configuration File before
continuing.
Use this command to synchronise the Configuration Files in the system.
6.11 Reboot system (excluding myself)
This operation will reboot all Control Modules in the system.
NOTE!
The Control Module used for this procedure will not reboot.
6.12 Reboot myself
The operation will reboot this Control Module only.
6.13 Download Firmware to modules
Use this command to overwrite the firmware in the chosen Module
5100332-02B02 19
4 Control Panels User Guide
History
7 History
Use this menu to view previous events in the Fire detection system.
7.1 Fire History List
Shows a chronological list of the last 200 fire alarms.
7.2 Fault History List
Shows a chronological list of the last 200 fault alarms.
7.3 Disable History List
Shows a chronological list of the last 200 disablements.
7.4 Common History List
Shows a common chronological list of the last 1000 pre-alarms, fire alarms, fault
alarms, disablements, warnings, and I/Os.
Maintenance
8 Maintenance
Note! Only for analogue addressable systems.
Use this menu for monitoring detectors that may need maintenance.
8.1 Lightly Contaminated Detectors
Shows a list of lightly contaminated detectors for the entire system.
8.2 Heavily Contaminated Detectors
Shows a list of heavily contaminated detectors for the entire system.
• Fire alarms
• Faults
• Disablements
20 5100332-02B02
User Guide 4 Control Panels
Repeater panel
• Power
Green steady light indicates that the power supply to the repeater panel is OK.
• Local Mute
Silence the local buzzer alarm.
• Night mode
Decrease the brightness/contrast level for the indicators and display on the panel.
• Day mode
Increase the brightness/contrast level for the indicators and display on the panel.
• Lamp test
When you press the buttons for Day and Night mode at the same time, all the repeater
panel indicators and the display are lit – if not, they are not working correctly.
5100332-02B02 21
4 Control Panels User Guide
22 5100332-02B02
User Guide 5 Operations
5 Operations
The user has to log in to the system before any vital operations can be performed.
Without access to an authorization code the user can only view fire and fault
alarms and mute the local buzzer.
Access level 2B is the default level. The system automatically returns to access
level 2B after 30 minutes of inactivity.
3 Power User access level Personnel trained and authorized to Same permissions as level 2B, plus
Enter access code for level 3 via make changes to the configured these additional permissions:
menu/login. system. • Possibility to make changes to
the configured system
4 Service access level Only authorized service personnel All functions available, including
Enter access code for level 4 via trained by an authorized service advanced service options.
menu/login. organization.
A Control Panel M 4.3 could be programmed to view events in the system with
restricted rights to operate functions. For example a fire alarm is shown, but mute
and reset are not allowed.
5100332-02B02 23
5 Operations User Guide
5.2 Login
Each user is assigned to a specific access level.
The predefined users are assigned the following default access codes:
Level 2B 2222
Level 3 3333
• Number of alarm(s)
• First, last and current list entry
• Zone in alarm
• Supplementary text (if defined in system configuration)
• Time of alarm
• Date of alarm
24 5100332-02B02
User Guide 5 Operations
5100332-02B02 25
5 Operations User Guide
26 5100332-02B02
User Guide 5 Operations
See Fault Code List, page 35 for a list of all fault messages.
5.6 Disablements
5.6.1 About Disablements
It is possible to disable different devices attached to the system, such as zones,
alarm devices and external control devices.
DANGER!
When a fire detector or zone is disabled, the Fire detection system will not be able
to detect any occurring fire in that area. It is therefore important that disablements
are minimized in terms of quantity of disabled units and duration of time.
Permanent disablement
The device is permanently disabled until it is manually enabled.
NOTE!
5100332-02B02 27
5 Operations User Guide
Timer disablement
Disablement is instantaneous and lasts for the time period entered (hh:mm).
Maximum disablement time is 23 hours 59 minutes. Maximum disablement time
can be limited depending on rules and regulations.
Clock disablement
Enter a reconnection time. Disablement is instantaneous and the reconnection will
take place next time the entered time occurs. The maximum disablement time is 23
hours 59 minutes.
Take time under consideration on ships going through different time zones (if the
system time is not synchronized with the ship's central time).
Periodic disablement
A disablement for a certain time period during certain days of the week. Example:
Disable zone 1 each Tuesday and Friday between 7.00 - 17.00.
Take time under consideration if the system is travelling through different time
zones (if the system time is not synchronized with a central time).
The new disablement is also added in the disablements list under: Menu » 3
Disablements » 2 Disablement list
28 5100332-02B02
User Guide 5 Operations
NOTE!
Only permanent disablements can be reactivated.
5100332-02B02 29
5 Operations User Guide
5.7 Reconnecting
5.7.1 Reconnecting Disabled Items
All disablements in the system are presented in the disablement list. Any
enablement is made from this list.
30 5100332-02B02
User Guide 5 Operations
The Service menu is used for configuring the system in the commissioning phase,
as well as for troubleshooting and making small updates when the system is in
operation. The menu has functions for loading and saving information from/to a
suitable USB Memory.
The Service menu screen displays a list of the 8 service menu alternatives, as
shown in the figure below.
Please refer to the Service and Maintenance manual for detailed information about
the Service menu.
5100332-02B02 31
5 Operations User Guide
32 5100332-02B02
User Guide 6 Testing
6 Testing
The system has a special test mode function which makes the testing easier.
• External alarm devices and controls are by default not activated in case of a fire.
Hint
This functionality can be turned off.
NOTE!
The system handles fire alarms from zones not in test mode in the usual way.
The tested zone will automatically return to normal operation after two hours.
It is now safe to test each detector and manual call point in this fire zone during the
next two hours.
All alarms are listed under: Menu » 7 History » 1 Fire History List.
NOTE!
Use appropriate test equipment. See section Recommended Test Equipment, page
34.
5100332-02B02 33
6 Testing User Guide
For detailed information, please refer to the data sheets for the products.
1 The zones in test mode are listed in the Disablement List, found under:
Menu » 3 Disablements » 2 Disablement List.
2 Choose the zone in the Disablement List and then press .
• The display
• All indications on the control panel
1 To test the control panel display, use: Menu » 5 Settings » 4 Test display.
34 5100332-02B02
User Guide 7 Appendix
7 Appendix
The smoke detector is exposed to strong Protect the detector from the airflow
airflow or consider repositioning the detector.
Replace the detector.
Refer to the Installation manual or
The detector has a dirty (polluted) sensor
130 DIRTY SENSOR Service & Maintenance manual:
element
5100332-02B02 35
7 Appendix User Guide
36 5100332-02B02
User Guide 7 Appendix
5100332-02B02 37
7 Appendix User Guide
38 5100332-02B02
User Guide 7 Appendix
5100332-02B02 39
7 Appendix User Guide
40 5100332-02B02
User Guide 7 Appendix
The main bus outside a Central cabinet used for communication between Modules and
Backbone Bus External
stretched central parts. It consists of two redundant RS485 channels, two 24 VDC
(BBE)
power lines and the Basic Backup (BBU) signal and Synchronisation Signal (SYNC).
The main bus inside a Central Cabinet used for communication between Modules. It
Backbone Bus Internal (BBI) consists of two redundant RS-485 channels, two 24 VDC power lines and the Basic
Backup (BBU) signal and Synchronisation Signal (SYNC).
A Backbone Bus may be split in several Segments. Power feeding can be separate for
Backbone Segment each segment by using one Charger M per segment. Communication can be isolated
between segments by using Isolator Modules.
A signal in the Backbone Bus that is used for transmitting the Central's alarm status.
Basic Backup Signal (BBU) The signal is only used when a module in Managed mode loses communication with
its Controller Module.
The Cause/Effect program defines how the inputs and outputs of the system should
Cause/Effect
react.
An umbrella name for all the Modules and Devices that can be connected together, e.g.
CCP Platform
“the Control M 4.3 Module is a member of the CCP Platform”.
A Central is a complete system that can operate autonomously; monitor its detectors
and inputs, activate its outputs and display its faults and alarms. If connected to other
Central centrals, it exchanges information with the other centrals via the System Bus, thus
allowing all centrals to act as one System.
Each central can only have one Backbone Bus.
Central Cabinet Enclosure to contain a complete or part of a central.
Central Cabinet including basic functionality of Fire Detection System such as:
Compact Central Control Panel, Power supply, Battery backup, Basic I/Os and at least one analogue
addressable loop. The Cabinet supplies limited expansion possibilities.
The Control M 4.3, the Control M 2.2 and the Control M X can all act as Controller
Control Module
Modules, i.e. be in Controller Mode.
The Control M 4.3 and Control M 2.2 can act as a Control Panel, i.e. they have an
Control Panel
HMI and the rights to manipulate and supervise the System.
Control Modules can run in Controller Mode, i.e. being Master or Hot Standby Master
within a central. Control Modules can also be in managed mode, that is being a module
Controller Mode
that is managed by the master. All other modules are always running in managed
mode.
A Control Module that is in Controller Mode (master or hot standby) in a Central or
Controller Module
System.
DCS Distributed Central System (see also Stretched Central).
Detector A device capable of detecting fire or gas alarms.
Disablement of devices such as a Zones or Detectors. Alarms from disabled devices
Disablement
will be inhibited.
Emergency Shut Down System, embedded system taking care of safety procedures in
ESD System
case of emergency, for example shut down of fire doors, ventilation etc.
An additional (RS485) bus used inside a central for intra-central communication. The
Extension Bus is typically used for connecting Repeater Modules (that does not require
Extension Bus
redundant communication and power) and should not be confused with the Backbone
Bus.
Communication to external entities is called external communication, using for
External Communication
example MODBUS, NMEA or TCMS protocols.
External Control Outputs used to control external equipment, for example fire doors.
Fault Condition The state of the system when a fault is detected.
5100332-02B02 41
7 Appendix User Guide
A module with inputs and/or outputs. I/O modules always run in Managed Mode, that
I/O Module
is they must be managed by a Controller Module.
I/O Pin or I/O Signal An I/O Pin or an I/O Signal is a logical signal, compare to terminal.
Inter-central Communication Communication between centrals is called inter-central communication.
A communication channel used to interface the systems with external devices.
Interface Channel
Interface channels can be configured to communicate on different protocols.
Communication within a central is called intra-central communication. This
Intra-central Communication
communication is between modules.
A common name for the cable, loop devices and other equipment connected to a loop
Loop
module.
Fire Detectors, Gas Detectors, Manual Call Points and other devices that can be
Loop Device
connected to the Loop.
Loop Module A Module supplying power and is in charge of communication to the loop devices.
The opposite of Controller Mode. All modules that are managed by a Controller
Managed Mode
Module are in Managed Mode.
MCS Multi Central System. A System consisting of more then one Central.
MFZ Main Fire Zone.
Modules in the System can take on different roles. Connected to the Backbone Bus
they can be in:
• Central Controller Mode (Master or Hot Standby)
• Central Managed Mode
Mode of operation
Modules connected to the System Bus can be in:
• System Controller Mode (Master or Hot Standby)
• System Managed Mode
A module that is a part of the Platform, that is can be used to build Centrals. Modules
Module within the platform generally supply a Backbone Bus interface. Controller Modules
also have a System Bus Interface.
42 5100332-02B02
User Guide 7 Appendix
Module Address Module Addresses are set via DIP switches on the Modules.
Mute Acknowledge and silence the local buzzer and in some cases the alarm devices.
PA Public Addressing.
Power Output Output providing power supply, normally used to power external devices.
A condition preceding the Alarm Condition to give early warning for potentially
Pre-Alarm Condition
dangerous situations like a smouldering fire.
Programmable Output Output which signal behaviour is configurable via the Configuration Program.
PSU Power Supply Unit.
Refers to the quality or state of being redundant, that is exceeding what is necessary or
Redundancy normal. In the System the term is used to describe backup functionality like in Hot
Standby Controller Modules.
Electrically operated switch output, normally providing C/NO/NC contacts for
Relay
connection of signal receiver.
The main attribute for Repeater Panels is that they can show information but not affect
Repeater Panel
the Central (or System) they belong to. The Repeater M 4.3 is a Repeater Panel.
Modules enter 'safe state' when they detect system faults. Modules in Safe State put
Safe State their I/O in a predefined state and stop all communication in order to avoid disturbing
system integrity.
SCS Single Central System.
Salwico Safety Management interactive graphics, a PC-based software package
SMig system
providing graphical presentation and control of the System.
A central that is physically distributed to two or more physical locations. One location
Stretched central (DCS) may or may not supply power to another location (segmented) and two locations may
or may not have isolated communication lines.
A signal in the Backbone Bus that is used for transmitting synchronization signal used
Synchronization Signal
by system Modules to synchronize there behaviour.
System A System consists of one or more Centrals.
The communication bus used for connecting multi-central systems. The System Bus is
used for inter-central communication but can also be used for external communication.
System Bus
If inter-central communication redundancy is required, the system bus will consist of a
primary and a secondary System Bus.
Terminal A Terminal is a physical point of connection, compare I/O pin.
Detectors put in the Test Condition (or Test Mode) are inhibited from generating the
Test Condition Alarm Condition but the alarms are displayed on the Control Panels to prove that the
tested Detectors are operational.
Universal Serial Bus, a communications bus that may be used to connect flash
USB
memories, keyboards, mice or other devices.
The state of the system when a warning is detected. Warnings are not as serious as
Warning Condition faults and only of informative nature, for example that a Gas Detector is in need of
calibration.
Zone A group of detectors located in a geographical area.
5100332-02B02 43
7 Appendix User Guide
44 5100332-02B02
User Guide 8 Quick Guide for Control Panel M 4.3
5100332-02B02 45
8 Quick Guide for Control Panel M 4.3 User Guide
46 5100332-02B02
Index
Index
A Fire alarms, Menu alternatives............................... 12
About testing.......................................................... 33 Fire detection system, Access levels...................... 23
Access levels, Custom specific restrictions ........... 23 Fire detection system, System description............. 5
Access levels, Description of................................. 23 Fire alarm, Information displayed in the Control
Alarm delay............................................................ 29 Panel....................................................................... 24
Alarm delay off indicator, Control Panel M 4.3 .... 8 Fire alarm, Mute..................................................... 25
Alarm device indicator, Control Panel M 4.3 ........ 8 Fire alarm, Reset .................................................... 25
Arrow keys, Control Panel M 4.3 .......................... 10 Fire history list ....................................................... 33
Arrow keys, Repeater M 4.3 .................................. 21 Fire-Fault-Dis. button, Repeater M 4.3.................. 21
C H
Clock disablement.................................................. 28 History, Explanation of menu alternatives............. 20
Control Panel M 4.3, Description of numerical History, Menu alternatives ..................................... 15
keypad .................................................................... 11
Control panel display, Testing................................ 34 L
Control Panel M 4.3, Description of operational Lamp test buttons, Repeater M 4.3 ........................ 21
controls................................................................... 9 Local Mute button, Repeater M 4.3 ....................... 21
Control Panel M 4.3, Description of system Login, Access codes............................................... 24
indicators................................................................ 8
Custom indicators, Control Panel M 4.3................ 8
M
Maintenance, Explanation of menu alternatives.... 20
D Maintenance, Menu alternatives ............................ 15
Day mode button, Control Panel M 4.3 ................. 11 Menu alternatives, Choosing ................................. 12
Day mode button, Repeater M 4.3 ......................... 21 Menu alternatives, Explanation of ......................... 15
Disablement list ..................................................... 34 Menu Alternatives, Menu tree ............................... 12
Disablement list ..................................................... 28 Menu button, Control Panel M 4.3 ........................ 10
Disablement, Acknowledgement ........................... 28 Multiple alarms button, Control Panel M 4.3 ........ 10
Disablements button, Control Panel M 4.3............ 9 Mute button, Fault alarm........................................ 26
Disablements, Explanation of menu alternatives... 16 Mute button, Fire alarm ......................................... 25
Disablements, Menu alternatives ........................... 13 Mute button, Control Panel M 4.3 ......................... 11
Disabling a conventional zone ............................... 28
Disabling alarm devices......................................... 29
Disabling alarm transfer output ............................. 30
N
Disabling external outputs ..................................... 29 Night mode button, Control Panel M 4.3............... 11
Night mode button, Repeater M 4.3....................... 21
E
Enter button, Control Panel M 4.3 ......................... 11
O
Erase button, Control Panel M 4.3......................... 11 OK button, Control Panel M 4.3............................ 10
Escape button, Control Panel M 4.3 ...................... 10
P
F Periodic disablement.............................................. 28
Fault alarm, Information displayed in the Control Permanent disablement .......................................... 27
Panel....................................................................... 26 Power indicator, Control Panel M 4.3.................... 8
Fault alarm, Mute................................................... 26 Power indicator, Repeater M 4.3 ........................... 21
Fault alarm, Reset from the Fault list..................... 26 Pre-Alarm button, Control Panel M 4.3................. 9
Fault alarms, Explanation of menu alternatives..... 16
Fault alarms, Menu alternatives............................. 12 R
Fault alarm, Reset .................................................. 26 Reconnecting disabled items.................................. 30
Fault alarm, Reset all faults ................................... 27 Reconnecting periodic disablements...................... 30
Fault button, Control Panel M 4.3 ......................... 9 Remove all disablements ....................................... 30
Fire alarm button, Control Panel M 4.3 ................. 9 Repeater M 4.3, Description of keys and
Fire alarm, Reset several alarms ............................ 25 indicators................................................................ 21
Fire alarm, From conventional zones..................... 25 Reset button, Fault alarm ....................................... 26
Fire alarms, Explanation of menu alternatives ...... 16 Reset button, Fire alarm......................................... 25
5100332-02B02 47
Index
S
Service, Explanation of menu alternatives............. 18
Service, Menu alternatives..................................... 14
Settings, Explanation of menu alternatives............ 18
Settings, Menu alternatives.................................... 14
Shortcuts button, Control Panel M 4.3................... 9
Status button, Control Panel M 4.3........................ 10
System fault indicator, Control Panel M 4.3.......... 8
T
Test Equipment ...................................................... 0
Test mode overview ............................................... 33
Test indicator, Control Panel M 4.3 ....................... 8
Test the control panel display ................................ 34
Testing a fire-detecting zone .................................. 33
Timer disablement.................................................. 28
U
USB connection, Control Panel M 4.3................... 8
W
Warning indicator, Control Panel M 4.3 ................ 8
Z
Zone indicator, Control Panel M 4.3...................... 8
Zone, Test mode..................................................... 33
48 5100332-02B02
Global Service and Support
Own companies
Sales- and service representatives
Consilium is constantly increasing and improving its global sales and service
organisation in order to provide our customers with the most competent
service and support. Today Consilium has established own companies in
16 countries plus sales and service representatives in more than 50 countries.
You will find updated contact information on our web-site www.consilium.se.
www.consilium.se
Salwico Cargo
Conventional Fire Detection
System
Installation Manual
Consilium Marine & Safety AB
Fire & Gas Marine Division
Phone: +46 31 710 77 00
Fax: +46 31 710 78 00
E-mail: Service: [email protected]
Spares: [email protected]
January 2012
Document no. 5100333-02B02
Part no. Part no: 5100333
1 Introduction ...................................................................................... 1
1.1 About this Manual ........................................................................... 1
1.2 Approvals .......................................................................................... 2
4 Installation ....................................................................................... 7
4.1 Prerequisites for Installation ........................................................... 7
4.2 Mechanical Installation ................................................................... 7
4.2.1 Installation Order ........................................................................... 7
4.2.2 Control Panels ................................................................................ 7
4.2.3 Loop Units ..................................................................................... 7
4.2.4 Mounting of Modules on a DIN rail .............................................. 7
5 Verification ....................................................................................... 13
5.1 Prerequisites for Verification ........................................................... 13
5.2 Loops ................................................................................................. 13
5.2.1 Verification of Loops ..................................................................... 13
5.2.2 Testing of System Parts .................................................................. 14
8 Appendix ........................................................................................... 29
8.1 EN54 Functions ............................................................................... 29
8.2 Address List and Test Report ........................................................... 30
8.3 Central Unit Terminal & Cabling Layout ....................................... 31
8.4 RS485 Termination .......................................................................... 33
8.4.1 General Recommendations for Installation of RS485 ................... 33
8.4.2 Application Examples for Installation of RS485 ........................... 33
Index ................................................................................................. 47
Installation Manual 1 Introduction
1 Introduction
NOTE!
This guide is valid for Control panel software versions beginning with version
1.0.0.
Chapter Verification describes how to test the installed system. After the
installation is completed, the system is verified, which must be performed by a
person with good knowledge of the various functions. This chapter also includes
verification and troubleshooting.
5100333-02B02 1
1 Introduction Installation Manual
1.2 Approvals
2 5100333-02B02
Installation Manual 2 Symbols Used in the Manual
DANGER!
Risk of serious or fatal injury to the user, and/or severe damage to the product, if
the instructions are not followed.
WARNING!
Risk of personal injury and/or damage to the product if the instructions are not
followed.
CAUTION!
Risk of minor or moderate personal injury. Risk of equipment damage, loss of data,
extra work, or unexpected results, if the instructions are not followed.
NOTE!
Note symbols alert you to important facts and conditions.
Hint
Tip symbols direct you to specific instructions, such as where to find additional
information and tell you how to perform a certain operation in an easier way.
5100333-02B02 3
2 Symbols Used in the Manual Installation Manual
4 5100333-02B02
Installation Manual 3 General Description
3 General Description
5100333-02B02 5
3 General Description Installation Manual
NOTE!
System boot-time is kept to a minimum during normal operation, but it can be
extra-long after a new installation, commissioning or major maintenance work
(depending on the configuration of the data definition file).
Hint
For detailed requirements, refer to the data sheets.
6 5100333-02B02
Installation Manual 4 Installation
4 Installation
The different parts of the system, the control and system modules, should first be
mechanically installed. The different loop units are thereafter electrically installed
and set up according to the definition of the loops and drawings.
The cables must be tested separately before the loops are connected to the loop
module. This eliminates any problem with the cable and electrical installation of
the loop units.
The installation is completed with the electrical installation of the the control and
system modules.
The mechanical installation of the different types of loop and zone units are
described in their respective data sheets.
5100333-02B02 7
4 Installation Installation Manual
The cables connecting from the backbone bus to the control panels or stretched
central part must meet the following requirements:
Channel 1 & 2
• Min 2 x 2 x 0.3 mm2, twisted pair shielded
(RS485 + backup signal, one conductor)
NOTE!
The backup signal is only needed for one channel. (The back up signal
is optional.)
• Max allowed cable length is 700 m
• Optional: Power supply (24 VDC) 1 x 2 x 0.75 mm2
Refer to the system connection drawing
NOTE!
Channel 1 and Channel 2 should be routed separately for improved safety if both
channels are used.
Detector loops
Detector loop cables must meet the following minimum requirements. We refer to
current regulations for the rest of the specification.
8 5100333-02B02
Installation Manual 4 Installation
Measure between the + and - pole and earth to detect an earth fault.
5100333-02B02 9
4 Installation Installation Manual
Follow this instruction to set address for the Repeater M 4.3 module in the system
and set the panel functions.
1 Press both arrow keys + to open the Use the arrow keys to scroll
Enter Access Code menu. and select the digits for the
Approximate 4-5 seconds. Access Code.
Confirm with the Local Mute
button (= Next digit or
Enter).
( = Previous.)
2 Proceed to choose address and layout for For all menu alternatives use
the Repeater module: the arrow keys to scroll and
• Enter Central Address select.
Confirm with the Local Mute
• Enter Module Address
button.
• Enter Layout Follow the instructions on the
Reboot the Repeater module (it will take lower part of the screen.
the module about 20 seconds to restart).
Refer to Central Unit Terminal & Cabling Layout, page 31 for more information.
For other electrical installations, such as Printer and Basic Backup Signal (BBU),
refer to the specific project drawings.
10 5100333-02B02
Installation Manual 4 Installation
Control Panel
If the Control Panel is placed outside of the Fire detection cabinet, connection to
the Central Unit is made via the external Backbone Bus channel (BBE), as shown
in the System Block Diagram, page 5. Each cable should be routed seperately
for maximum security.
5100333-02B02 11
4 Installation Installation Manual
12 5100333-02B02
Installation Manual 5 Verification
5 Verification
5.2 Loops
5.2.1 Verification of Loops
NOTE!
Once the loop cable has been tested and is free from faults, the next step is to
connect it to the central.
5100333-02B02 13
5 Verification Installation Manual
5 Make a fire detector test of the complete See Testing of System Parts,
Fire detection system. page 14.
Use appropriate test equipment (smoke
detector test gas, heat detector tester) to test
each detector and loop unit. See section
Recommended Test Equipment, page 15.
Print out the “Fire alarm history list” found
under Menu » 7 History » 1 Fire History
List. This list contains the 500 latest fire
alarms, and is cleared each time the system
is restarted.
6 Use a top to bottom procedure if you have
any problem with the verification of the
loop function.
Start by solving the problems that affect the
whole loop and then continue with the
problems with each address.
The system has a special test mode function which makes the testing easier.
• External alarm devices and controls are by default not activated in case of a fire.
Hint
This functionality can be turned off.
NOTE!
The system handles fire alarms from zones not in test mode in the usual way.
The tested zone will automatically return to normal operation after two hours.
14 5100333-02B02
Installation Manual 5 Verification
2 Select a zone and confirm by pressing the The Disablements, Test, and
button. Zone/Unit indicators light to
confirm that they are in test
mode.
It is now safe to test each detector and manual call point in this fire zone during the
next two hours.
All alarms are listed under: Menu » 7 History » 1 Fire History List.
NOTE!
Use appropriate test equipment. See section Recommended Test Equipment, page
15.
For detailed information, please refer to the data sheets for the products.
1 The zones in test mode are listed in the Disablement List, found under:
Menu » 3 Disablements » 2 Disablement List.
2 Choose the zone in the Disablement List and then press .
• The display
• All indications on the control panel
1 To test the control panel display, use: Menu » 5 Settings » 4 Test display.
5100333-02B02 15
5 Verification Installation Manual
If the earth fault still remains after this step, examine the cables to all other devices
connected to the Fire detection system.
The faults are reset from the Fault list under Menu » 1 Fault Alarms » 1 Fault List.
A service pack contains the software for all modules in a CCP System with the
exception of Control MX / 2.2 / 4.3 and Repeater M 4.3.
NOTE!
NOTE: Service package is included in the file “cm_firmware” and downloaded
automatically in the system when the system is updated by using the
“cm_firmware”
16 5100333-02B02
Installation Manual 5 Verification
Follow the steps below to upgrade service pack and the firmware in a CCP System:
Prerequisites
• A USB Memory Stick and a CCP Service pack release
5100333-02B02 17
5 Verification Installation Manual
NOTE!
The system will only update the modules that have software that differs from what
is in the service package.
3 All modules will be upgraded to the version stored in the local service
pack.
Wait until all modules are upgraded. The system reports for example:
5. 1.1 has 0 modules left to update of total 1. Failed 0 Operation
Succeeded.
18 5100333-02B02
Installation Manual 6 Commissioning Requirements
6 Commissioning Requirements
6.1 Prerequisite
The procedure described below is to be followed by the installation team.
If nothing else is agreed, no commissioning engineer will be sent before the steps
below are confirmed and the appropriate papers are signed and sent to your local
Consilium office or authorized representative.
5100333-02B02 19
6 Commissioning Requirements Installation Manual
NOTE!
Deviations from the above criteria may cause time delays. These time delays will
be invoiced.
6.5 Summary
For each loop, a test report as described in Address List and Test Report, page 30
must be filled in and sent to your local Consilium office or authorized
representative before commissioning of the system starts.
20 5100333-02B02
Installation Manual 7 Fire Detection Installation Guidelines
CAUTION!
Always refer to and act according to current local rules and regulations.
NOTE!
For detailed connection and installation information, refer to the data sheet for each
unit.
5100333-02B02 21
7 Fire Detection Installation Guidelines Installation Manual
• The maximum distance for a smoke detector from a wall or a bulkhead is 5.5 m.
The maximum distance between two detectors is 11 m.
• When placed in engine spaces, smoke detectors shall have 2 m extra cable slack
to enable relocation within the space.
• In cabins and in lockers, mount the detector with its LEDs facing toward the
door.
22 5100333-02B02
Installation Manual 7 Fire Detection Installation Guidelines
• Mount the flame detector to give it clear access to the location of the anticipated
fire. A detector has a typical cone of vision of 100° from the central axis, see
data sheet of flame detector for more information. Place the detector beside, but
not directly above, the protected object to prevent the risk that black smoke may
block the flames. Place the detector at an angle of 45° downwards. This way the
detector will project both downward and forward and catch the least amount of
dirt. For more information about its angle of projection, refer to the flame
detector’s data sheet.
• A general rule is to install the detector on a height that is twice the height of the
highest object in the supervised area, if possible.
• Avoid sources for false alarm (e.g. flares) from entering the detector’s cone of
vision.
5100333-02B02 23
7 Fire Detection Installation Guidelines Installation Manual
7.1.9 Bells
• Installation height is normally 0.2 m from the ceiling and max 2.2 m from the
floor.
• After installation, make sure that the gong is free from the cables, otherwise the
sound output may be reduced.
• Should be mounted with cable entrance facing downwards.
24 5100333-02B02
Installation Manual 7 Fire Detection Installation Guidelines
When installing metal cable tubes – following must be taken into account:
• If there is more than one cable in the same tube, the cross section (counted of
mutual external diameters) may be max 40% of the inner cross section of the
tube.
• If the tube is more than 10 m long, drafting holes has to be done.
• Tubes must be installed on support so that the background may be painted.
• Tube installation must be done by welding or by tube joints. Fastening distances
are located 100 mm from the tube end and afterwards every 1.5 m.
• Bending radius must be at least 6 times the external diameter of the tube.
• The upper tube end in open decks must be sealed up, this to prevent water from
coming in.
When installing plastic cable tubes – following must be taken into account:
• Bending radius must be at least six times external diameter of the tube.
• Installation must be done onto the warm side of a thermal insulation and at least
100 mm from a hot surface, preferably below it. Piping is not allowed inside a
thermal insulation.
• The tubes are tied with galvanized wire clips. The first clip is located
approximately 100 mm from the tube end and afterwards every 1 m.
7.2.4 Cabling
When installing the cables – take into account the minimum internal bending
radius, that has nominal value of six times the external diameter of the cable.
• If two separate routes for the cables are required – all supplies and involved
control cables must be passed by separate routes according to the drawings and
cable passing list.
• Do not bundle low voltage cables together with power cables, they have to be
separated from each other.
5100333-02B02 25
7 Fire Detection Installation Guidelines Installation Manual
• When cable bundles are mounted on trays this can be done as follows:
• On the trays along the ship – the power cables on the left side (Port-side)
and the low voltage cables on the right side (Starboard-side) of the tray.
• On the trays across the ship – the power cables to the fore side and the low
voltage cables in the stern side of the tray.
• On the fore or stem bulkhead trays in vertical shaft – the power cables to the
Port-side or the Starboard-side bulkhead trays, the power cables to the fore
side and the low voltage cables to the stern side of the tray.
• In cable junctions and when exiting the cable trays bridges with fastening bolts
have to be used – low voltage cables for alarm, communication, navigational
and measuring equipment have to be installed in their own bundles.
• Each fire detector installed in engine room areas shall have two (2) meters extra
cables, this to make it possible to relocate the detector position when
performing “real” smoke tests with fans etc. running.
• Wet spaces:
• Cables are penetrated from the bellow or from the side with diaphragm
seals.
• Let the cables enter the sealing at a right angle (or as near a right angle as
possible).
• Dry spaces:
• Free entering
No cables are to be installed below 50 mm distance from bottom or fuel oil tank,
except cables ending in these spaces.
26 5100333-02B02
Installation Manual 7 Fire Detection Installation Guidelines
• When installing cables without plastic tube inside the lining, the cables are
fastened to supporting construction of the ceiling with plastic bundle-ties.
7.2.7 Markings
• Cables entering terminal boxes and equals shall be marked with identification
markings.
• The cable identification is to be done with a metal dymo-tape – on open decks
the dymo-tape must be of stainless steel.
• Cable markings are the same as the identification marks in the drawings.
• The cable is passed in switchboards, decks and terminals unpeeled as near the
connection place as possible.
• Mark extra wires (not used) and do not cut them.
• Earthing wire is marked with yellow/green sleeve.
• Cable wire ends of 0.5–2.5 mm2 shall be equipped with compression-type
collar, if the contact screw presses direct wires.
• A cable eye shall be installed at the end of a conductor, connected by means of
a screw or a bolt.
• No more than two conductors shall be connected onto one side of the same
terminal.
5100333-02B02 27
7 Fire Detection Installation Guidelines Installation Manual
28 5100333-02B02
Installation Manual 8 Appendix
8 Appendix
5100333-02B02 29
8 Appendix Installation Manual
30 5100333-02B02
Installation Manual 8 Appendix
Charger M
A Module that supervises and controls the power and battery functions.
For complete information, see the data sheet for each module.
5100333-02B02 31
8 Appendix Installation Manual
32 5100333-02B02
Installation Manual 8 Appendix
5100333-02B02 33
8 Appendix Installation Manual
34 5100333-02B02
Installation Manual 8 Appendix
5100333-02B02 35
8 Appendix Installation Manual
The smoke detector is exposed to strong Protect the detector from the airflow
airflow or consider repositioning the detector.
36 5100333-02B02
Installation Manual 8 Appendix
5100333-02B02 37
8 Appendix Installation Manual
38 5100333-02B02
Installation Manual 8 Appendix
5100333-02B02 39
8 Appendix Installation Manual
40 5100333-02B02
Installation Manual 8 Appendix
5100333-02B02 41
8 Appendix Installation Manual
Device that is activated in case of fire, for example audible and optical alarms like
Alarm Device
bells, sirens and flashlights.
A supervised output for signalling that a fire has occurred. The Alarm Transfer Output
Alarm Transfer Output
is usually used in onshore systems for alerting the Fire Brigade.
The main bus outside a Central cabinet used for communication between Modules and
Backbone Bus External
stretched central parts. It consists of two redundant RS485 channels, two 24 VDC
(BBE)
power lines and the Basic Backup (BBU) signal and Synchronisation Signal (SYNC).
The main bus inside a Central Cabinet used for communication between Modules. It
Backbone Bus Internal (BBI) consists of two redundant RS-485 channels, two 24 VDC power lines and the Basic
Backup (BBU) signal and Synchronisation Signal (SYNC).
A Backbone Bus may be split in several Segments. Power feeding can be separate for
Backbone Segment each segment by using one Charger M per segment. Communication can be isolated
between segments by using Isolator Modules.
A signal in the Backbone Bus that is used for transmitting the Central's alarm status.
Basic Backup Signal (BBU) The signal is only used when a module in Managed mode loses communication with
its Controller Module.
The Cause/Effect program defines how the inputs and outputs of the system should
Cause/Effect
react.
An umbrella name for all the Modules and Devices that can be connected together, e.g.
CCP Platform
“the Control M 4.3 Module is a member of the CCP Platform”.
A Central is a complete system that can operate autonomously; monitor its detectors
and inputs, activate its outputs and display its faults and alarms. If connected to other
Central centrals, it exchanges information with the other centrals via the System Bus, thus
allowing all centrals to act as one System.
Each central can only have one Backbone Bus.
Central Cabinet Enclosure to contain a complete or part of a central.
Central Cabinet including basic functionality of Fire Detection System such as:
Compact Central Control Panel, Power supply, Battery backup, Basic I/Os and at least one analogue
addressable loop. The Cabinet supplies limited expansion possibilities.
The Control M 4.3, the Control M 2.2 and the Control M X can all act as Controller
Control Module
Modules, i.e. be in Controller Mode.
The Control M 4.3 and Control M 2.2 can act as a Control Panel, i.e. they have an
Control Panel
HMI and the rights to manipulate and supervise the System.
Control Modules can run in Controller Mode, i.e. being Master or Hot Standby Master
within a central. Control Modules can also be in managed mode, that is being a module
Controller Mode
that is managed by the master. All other modules are always running in managed
mode.
A Control Module that is in Controller Mode (master or hot standby) in a Central or
Controller Module
System.
DCS Distributed Central System (see also Stretched Central).
Detector A device capable of detecting fire or gas alarms.
Disablement of devices such as a Zones or Detectors. Alarms from disabled devices
Disablement
will be inhibited.
Emergency Shut Down System, embedded system taking care of safety procedures in
ESD System
case of emergency, for example shut down of fire doors, ventilation etc.
An additional (RS485) bus used inside a central for intra-central communication. The
Extension Bus is typically used for connecting Repeater Modules (that does not require
Extension Bus
redundant communication and power) and should not be confused with the Backbone
Bus.
42 5100333-02B02
Installation Manual 8 Appendix
A module with inputs and/or outputs. I/O modules always run in Managed Mode, that
I/O Module
is they must be managed by a Controller Module.
I/O Pin or I/O Signal An I/O Pin or an I/O Signal is a logical signal, compare to terminal.
Inter-central Communication Communication between centrals is called inter-central communication.
A communication channel used to interface the systems with external devices.
Interface Channel
Interface channels can be configured to communicate on different protocols.
Communication within a central is called intra-central communication. This
Intra-central Communication
communication is between modules.
A common name for the cable, loop devices and other equipment connected to a loop
Loop
module.
Fire Detectors, Gas Detectors, Manual Call Points and other devices that can be
Loop Device
connected to the Loop.
Loop Module A Module supplying power and is in charge of communication to the loop devices.
The opposite of Controller Mode. All modules that are managed by a Controller
Managed Mode
Module are in Managed Mode.
MCS Multi Central System. A System consisting of more then one Central.
MFZ Main Fire Zone.
5100333-02B02 43
8 Appendix Installation Manual
Modules in the System can take on different roles. Connected to the Backbone Bus
they can be in:
• Central Controller Mode (Master or Hot Standby)
• Central Managed Mode
Mode of operation
Modules connected to the System Bus can be in:
• System Controller Mode (Master or Hot Standby)
• System Managed Mode
A module that is a part of the Platform, that is can be used to build Centrals. Modules
Module within the platform generally supply a Backbone Bus interface. Controller Modules
also have a System Bus Interface.
Module Address Module Addresses are set via DIP switches on the Modules.
Mute Acknowledge and silence the local buzzer and in some cases the alarm devices.
PA Public Addressing.
Power Output Output providing power supply, normally used to power external devices.
A condition preceding the Alarm Condition to give early warning for potentially
Pre-Alarm Condition
dangerous situations like a smouldering fire.
Programmable Output Output which signal behaviour is configurable via the Configuration Program.
PSU Power Supply Unit.
Refers to the quality or state of being redundant, that is exceeding what is necessary or
Redundancy normal. In the System the term is used to describe backup functionality like in Hot
Standby Controller Modules.
Electrically operated switch output, normally providing C/NO/NC contacts for
Relay
connection of signal receiver.
The main attribute for Repeater Panels is that they can show information but not affect
Repeater Panel
the Central (or System) they belong to. The Repeater M 4.3 is a Repeater Panel.
Modules enter 'safe state' when they detect system faults. Modules in Safe State put
Safe State their I/O in a predefined state and stop all communication in order to avoid disturbing
system integrity.
SCS Single Central System.
Salwico Safety Management interactive graphics, a PC-based software package
SMig system
providing graphical presentation and control of the System.
A central that is physically distributed to two or more physical locations. One location
Stretched central (DCS) may or may not supply power to another location (segmented) and two locations may
or may not have isolated communication lines.
A signal in the Backbone Bus that is used for transmitting synchronization signal used
Synchronization Signal
by system Modules to synchronize there behaviour.
System A System consists of one or more Centrals.
The communication bus used for connecting multi-central systems. The System Bus is
used for inter-central communication but can also be used for external communication.
System Bus
If inter-central communication redundancy is required, the system bus will consist of a
primary and a secondary System Bus.
Terminal A Terminal is a physical point of connection, compare I/O pin.
Detectors put in the Test Condition (or Test Mode) are inhibited from generating the
Test Condition Alarm Condition but the alarms are displayed on the Control Panels to prove that the
tested Detectors are operational.
Universal Serial Bus, a communications bus that may be used to connect flash
USB
memories, keyboards, mice or other devices.
44 5100333-02B02
Installation Manual 8 Appendix
The state of the system when a warning is detected. Warnings are not as serious as
Warning Condition faults and only of informative nature, for example that a Gas Detector is in need of
calibration.
Zone A group of detectors located in a geographical area.
5100333-02B02 45
8 Appendix Installation Manual
46 5100333-02B02
Index
Index
A H
About testing.......................................................... 14 Heat detector, Installation guidelines..................... 22
B I
Backbone Bus External (BBE), Electrical I/O M 70................................................................. 31
installation.............................................................. 8 I/O M 70, Connection to ........................................ 9
Bells, Installation guidelines.................................. 24 I/O M 700............................................................... 31
Bus Isolator M........................................................ 31 Installation guidelines, Cabling and electrical
installation.............................................................. 25
Installation order, Mechanical installation............. 7
C IS Smoke detector for EX areas, Installation
Cable requirements, Electrical installation ............ 8
guidelines ............................................................... 23
Cabling, Installation guidelines ............................. 25
Central status.......................................................... 19
Central unit terminal layout with cabling .............. 31 L
Change Over M Ext ............................................... 31 Loop M X............................................................... 31
Charger M .............................................................. 31 Loop configuration................................................. 19
Cold room Heat detectors, Installation guidelines. 24 Loop status ............................................................. 19
Commissioning requirements ................................ 19 Loop units, Mechanical installation....................... 7
Control M 2.2......................................................... 31 Loops, Verification of ............................................ 13
Control M X........................................................... 31
Control Panel M 4.3............................................... 31
Control Panel M 4.3, Installation order ................. 7
M
Manual call points, Installation guidelines ............ 24
Control panel display, Testing................................ 15
Muting faults, Trouble shooting............................. 16
Control panels, Mechanical installation................. 7
Control panels, Electrical installation .................... 11
Conventional high temperature Heat detectors, P
Installation guidelines ............................................ 23 PSU M AC/DC 5A ................................................ 31
D R
Detector loops, Cable requirements....................... 8 Relay M 8............................................................... 31
Disablement list ..................................................... 15 Repeater M 4.3....................................................... 31
Door holder magnet 130kp, Installation Reset faults, Trouble shooting ............................... 16
guidelines ............................................................... 24 Reset test mode ...................................................... 15
Door holder magnet 65kp, Installation guidelines. 24 RS485 Termination ................................................ 33
Door release switch, Installation guidelines .......... 24 RS485, Application examples for installation ....... 33
E S
Earth fault, Trouble shooting ................................. 16 Smoke detector, Installation guidelines ................. 21
Electrical siren, Installation guidelines .................. 24 System modules, Description................................. 31
Electrical equipment, Location of.......................... 28
T
F Terminal layout, Electrical installation .................. 10
Fault list ................................................................. 16 Test Equipment ...................................................... 0
Fault list ................................................................. 16 Test for earth failure............................................... 9
Fire detection system, System description............. 5 Test mode overview ............................................... 14
Fire detection system, System data........................ 6 Test the control panel display ................................ 15
Fire history list ....................................................... 14 Testing a fire-detecting zone .................................. 14
Fire history list ....................................................... 15
Flame detectors, Installation guidelines................. 22
Z
Zone, Test mode..................................................... 14
G
Guidelines, Loop units installation ........................ 21
5100333-02B02 47
Index
48 5100333-02B02
Global Service and Support
Own companies
Sales- and service representatives
Consilium is constantly increasing and improving its global sales and service
organisation in order to provide our customers with the most competent
service and support. Today Consilium has established own companies in
16 countries plus sales and service representatives in more than 50 countries.
You will find updated contact information on our web-site www.consilium.se.
www.consilium.se
Fire alarm central
Salwico Workboat CI
Part no. 5102013-01A
General description
Salwico Workboat CI is a conventional fire detection system with 8 fire detector sections SOLAS
compliant. Tested and certified by all major classification societies, this system provides an optimal fire
detection solution for smaller vessels.
The system is managed and supervised through Control Panel M 4.3. The Control Panel M 4.3 is
mounted on the front of the fire alarm cabinet.
Data
Related Parts
NOTE:
If external DC power source is used this must be adjusted to 28.5V. A separate DC/DC kit is available in case this requirement
can’t be fulfilled.