SLD of Zainakot Grid Substation Submittal-Model

Uploaded by

Momin Bhat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
176 views1 page

SLD of Zainakot Grid Substation Submittal-Model

Uploaded by

Momin Bhat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

220KV BAY NO. I 220KV BAY NO. 2 220KV BAY NO. 3 220KV BAY NO. 4 220KV BAY NO.

220KV BAY NO. 3 220KV BAY NO. 4 220KV BAY NO. 5 220KV BAY NO. 6 220KV BAY NO. 7 220KV BAY NO. 8 220KV BAY NO. 9 220KV BAY NO. 10 220KV BAY NO. 11 220KV BAY NO. 12
WAGOORA - III TRANSFORMER - I WAGOORA - II WAGOORA - I TRANSFORMER - II WAGOORA - IV TRANSFORMER - III AMARGARH - I AMARGARH - II BUS COUPLER ALUSTENG - I ALUSTENG - II

216 kV 216 kV 216 kV 216 kV 216 kV 216 kV 216 kV 216 kV

220kV/ 3/3x110/ 3V 220kV/ 3/3x110/ 3V 220kV/ 3/3x110/ 3V 220kV/ 3/3x110/ 3V 220kV/ 3/3x110/ 3V 220kV/ 3/3x110/ 3V 220kV/ 3/3x110/ 3V 220kV/ 3/3x110/ 3V

WT WT WT WT WT WT WT

900 - 450 / 1-1 A 900 - 450 / 1-1 A 900 - 450 / 1-1 A 900 - 450 / 1-1 A 1600-800-400/1-1-1 A 1600-800-400/1-1-1 A 1600-800-400/1-1-1 A 1600-800-400/1-1-1 A
201 - 89L-E 203 - 89L-E 204 - 89L-E 206 - 89L-E 208 - 89L-E 209 - 89L-E 211 - 89L-E 212 - 89L-E
201 - 89L 203 - 89L 204 - 89L 206 - 89L 208 - 89L 209 - 89L 211 - 89L 212 - 89L
210 - 52

201 - 89C 201 - 52 203 - 89C 203 - 52 204 - 89C 204 - 52 206 - 89C 206 - 52 208 - 89C 208 - 52 209 - 89C 209 - 52 211 - 89C 211 - 52 212 - 89C 212 - 52
210 - 89B 210 - 89A
220kV/ 3/3x110/ 3V

201 - 89A 201 - 89B 203 - 89A 203 - 89B 204 - 89A 204 - 89B 206 - 89A 206 - 89B 208 - 89A 208 - 89B 209 - 89A 209 - 89B 211 - 89A 211 - 89B 212 - 89A 212 - 89B
220 KV, 40 KA for 1 Sec
Twin ACSR Moose
220 KV RESERVE BUS

220kV/ 3/3x110/ 3V

220 KV, 40 KA for 1 Sec


Twin ACSR Moose
220 KV MAIN BUS
202 - 89B 202 - 89A 205 - 89B 205 - 89A 207 - 89B 207 - 89A

202 - 89C 205 - 89C 207 - 89C

202 - 89L 205 - 89L 207 - 89L

900 - 450 / 1-1 A 900 - 450 / 1-1 A 900 - 450 / 1-1 A

216 kV 216 kV 216 kV


AUTO TRANSFORMER BANK II AUTO TRANSFORMER BANK I AUTO TRANSFORMER BANK III
3X(40/50)MVA, ONAN/ONAF 3X (40/50) MVA, ONAN/ONAF 3X(40/50) MVA, ONAN/ONAF
220/132/33 kV, YnaOd1, Z= 11.79% 220/132/11 kV, Yna0d1, Z= 11.79% 220/132/11 kV, YnaOd1, Z= 11.71%
NCT NCT NCT
750/1A 750/1A 750/1A
120 kV 120 kV 120 kV

1500-750-375/1-1-1A 1500-750-375/1-1-1A 1500-750-375/1-1-1

101 - 89L 106 - 89L 109 - 89L

101 - 89C 101 - 52 106 - 52 109 - 89C 109 - 52


106 - 89C 132kV/ 3/3x110/ 3V

101 - 89B 101 - 89A 106 - 89B 106 - 89A 109 - 89B 109 - 89A
132 KV, 31.5 KA for 1 Sec
Twin ACSR Moose
132 KV MAIN BUS

132kV/ 3/3x110/ 3V

132 KV, 31.5 KA for 1 Sec


1500 - 750 - 375 / 1-1-1 A Twin ACSR Moose
132 KV RESERVE BUS 102 - 89B 103 - 89B 104 - 89B 105 - 89B 107 - 89B 108 - 89B 110 - 89B 1500 - 750 - 375 / 1-1-1 A
102 - 89A 103 - 89A 104 - 89A 105 - 89A 107 - 89A 108 - 89A 110 - 89A

111 - 89A 111 - 89B


102 - 89C 102 - 52 103 - 89C 103 - 52 104 - 89C 104 - 52 105 - 89C 105 - 52 107 - 89C 107 - 52 108 - 89C 108 - 52 110 - 89C 110 - 52

102 - 89L 103 - 89L 104 - 89L 105 - 89L 107 - 89L 108 - 89L 110 - 89L 111 - 52
102 - 89L-E 103 - 89L-E 104 - 89L-E 105 - 89L-E 107 - 89L-E 108 - 89L-E
1500 - 750 - 375 / 1-1-1 A 1500 - 750 - 375 / 1-1-1 A 1500 - 750 - 375 / 1-1-1 A 1500 - 750 - 375 / 1-1-1 A 1500 - 750 - 375 / 1-1-1 A 1500 - 750 - 375 / 1-1-1 A 1500 - 750 - 375 / 1-1-1 A

WT WT WT WT WT WT

132kV/ 3/3x110/ 3V 132kV/ 3/3x110/ 3V 132kV/ 3/3x110/ 3V 132kV/ 3/3x110/ 3V 132kV/ 3/3x110/ 3V 132kV/ 3/3x110/ 3V

120 kV 120 kV 120 kV 120 kV 120 kV 120 kV 120 kV

75 MVA, ONAN/ONAB P. TRANSFORMER


3 X(20/ 25) MVA, ONAN/ONAF
NCT 132/33 kV, YNyn0, Z= 11.79%
132KV BAY NO. 1 132KV BAY NO. 2 132KV BAY NO. 3 132KV BAY NO. 4 132KV BAY NO. 5 132KV BAY NO. 6 132KV BAY NO. 7 132KV BAY NO. 8 132KV BAY NO. 9 450/1A
TRANSFORMER - I BEMINA - I BEMINA - II WANGANPORA - I WANGANPORA - II TRANSFORMER - II LJHP - I LJHP - II TRANSFORMER - III 30 kV 132KV BAY NO. 11
1500 - 750 - 375 / 1-1-1 A
BUS COUPLER

305 - 89L

305 - 89C 305 - 52

33 kV/ 3/3x110/ 3V
305 - 89B 305 - 89A

33 KV MAIN BUS 33 KV, 25 KA for 1 Sec


AAAC Torontalla

33 kV/ 3/3x110/ 3V

LEGEND
33 KV RESERVE BUS
311- 89A 311 - 89B 309 - 89A 309 - 89B 310 - 89A 310 - 89B 304 - 89A 304 - 89B 132/33KV BAY NO. 10 305 - 89A 305 - 89B 307 - 89A 307 - 89B 308 - 89A 308 - 89B 220 KV
600 - 300 - 150 / 1-1-1 A 600 - 300 - 150 / 1-1-1 A TRANSFORMER - IV
303 - 89A 303 - 89B
311-52 309-52 310-52 304 - 89C 304-52 305 - 89C 305-52 307 - 89C 307-52 308 - 89C 308-52 132 KV
309 - 89L 310 - 89L 303-52 304 - 89L 305 - 89L 307 - 89L 308 - 89L
309 - 89L-E 310 - 89L-E 304 - 89L-E 305 - 89L-E 307 - 89L-E 308 - 89L-E 33 KV

311 - 89L 20 / 1 A 600 - 300 - 150 / 1-1-1 A 600 - 300 - 150 / 1-1-1 A 600 - 300 - 150 / 1-1-1 A 600 - 300 - 150 / 1-1-1 A
20 / 1 A SINGLE PHASE TRANSFORMER
311 - 89L-E

30 kV 30 kV 30 kV 30 kV WAVE TRAP

POTENTIAL TRANSFORMER
20 MVAR CAPACITOR 33KV BAY NO. 1 33KV BAY NO. 2 33KV BAY NO. 3 33KV BAY NO. 4 33KV BAY NO. 5 33KV BAY NO. 6 33KV BAY NO. 7 33KV BAY NO. 8
BANK AUXILIARY - II AUXILIARY - I BUS COUPLER SPARE FEEDER TRANSFORMER - 1 BADGAM FEEDER MAGAM FEEDER HMT FEEDER
TERTIARY/SPARE TRANSFORMER BUS ARRANGEMENT CURRENT TRANSFORMER

220 kV Transformer Bay 220 kV Transformer Bay 220 kV Transformer Bay LIGHTNING ARRESTOR
132 kV Transformer Bay

ISOLATORS 1. 220KV - 1600A


220 kV Spare Bus
132 kV Spare Bus
2. 132KV - 2500A

3. 33KV - 2500A

11 kV Tertiary Bus SF6 CIRCUIT BREAKERS

CAPACITOR VOLTAGE
TRANSFORMER (CVT)

Name of
Jammu and Kashmir Power Development Department
Department
132 kV Spare Bus
33 kV Spare Bus

132 kV Transformer Bay 132 kV Transformer Bay 132 kV Transformer Bay

33 kV Transformer Bay

CT SPECIFICATIONS Drawing Title SLD of 450 MVA, 220/132/33 kV Grid Substation Zainakot

Knee Point Excitation


No. of Voltage
Ratios Accuracy Class ALF / ISF Burden Current
CT Cores VK mA PERCENTAGE IMPEDANCE
220 KV 4 No. PS Cores, Bank - I Tap 5 - 11.71 Tap 17 - 11.82 Drawing No. SLD/ZK/JKPDD/02
5 900 - 450/1-1 Tap I - 12.03
WAGOORA 1 Metering Core <10, <5 60VA 900 / 450 30 at VK/2 Emco Normal
SINGLE PHASE
CURRENT 4 No. PS Cores, 3X50MVA, Bank - II Tap 5 - 11.79
Tap I - 13.33 Tap 17 - 13.42
TRANSFORMER AMARGARH 5 1600 - 800 - 400 / 1-1-1
0.2 Metering Core <5 20VA
1600 / 800 <25/50 at VK
220 / 132 kV Crompton & Greaves Normal Drawn By Ckd By App By Date Drg Size Scale Rev
3 No. PS Cores, POWER Bank - III Tap 5 - 11.79
132 KV 5 1500 - 750 - 375 / 1-1-1 1500 / 750 30 at VK/2 Tap I - 13.33 Tap 17 - 13.42
1 Metering Core 10 , <5 30VA TRANSFORMERS Crompton & Greaves Normal
6.07.2015 00
33 KV 2 600 - 300 - 150 / 1-1-1 1 / 5P 10 <10 15/30VA