T50 SERIES PID Controller


User's Manual

OLING
G & CO odels
HEATIN le for All m
ab
Select

T50 series
T52 T53 T54 T57 T59
www.temcoline.com

Thank you for purchasing the T50 series from TemcoLine.


The T50 series is a precision industrial controller that uses an advanced 2
degree-of-freedom (DOF) algorithm.
The T50 series consists of 5 models, which are T52, T53, T54, T57, and
T59.This manual explains the installation, the functions, the operation,
and the handling of the products.
Please read the manual thoroughly before using the products. If any
difficulties arise while using our products, please call our customer service
at +82-1588-5439.

Pay attention to the followings!


- Use the products under the conditions specified in this manual.
- Please heed the cautions and warnings listed in this manual.
- The contents of the manual may be changed without notice.
- The product is designed to be used installed on a control panel.
- This manual is copyrighted, and may not be copied in part or in whole
without permission.
- The manufacturer takes no responsibility for direct or indirect damages
caused by careless operation or operation under unpredictable or risky
environments.

Safety requirements!
Safety requirements are intended to prevent accidents and dangers
through the proper use of the products, so please heed them at all times.
The safety requirements are divided into "cautions" and "warnings", which
indicate the following.

WARNING
Serious injury or death may be caused if instructions are not observed.

CAUTION
Failure to observe these instructions may cause damage to the instrument
or some injury to the user.

2
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

WARNING
1. Use a separate safety device when this product is used to control a
device that could harm lives or expensive property in the event of a
malfunction or a breakdown. (This may cause fires, deaths, or damage
to property.)
2. Do not use this controller at place where there are flammable or
explosive gas. (It may cause a fire or explosion.)
3. Before turning the power on, please check that wiring is correct to
the number of terminal. (It may cause a fire.)
4. Turn off the power during wiring and maintenance to avoid an electric
shock.
5. Do not touch the terminals when it is power on. (It may give an electric
shock.)
6. This controller must be mounted on the panel to avoid an electric
shock.
7. Do not attempt to disassemble, modify and repair.

3
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

CAUTION
1. Please conduct an inspection when water has entered the product.
(It may cause short circuits, fires, and malfunction.)
2. This controller should be used indoors.(It may shorten the controller's
life or give an electric shock.)
3. Observe the rated voltage and specification.(It may cause a fire or
shorten the controller's life.)
4. Be careful that any of foreign materials do not inflow into the
controller. (It may cause a fire or malfunction of the controller.)
5. Do not give direct vibration or shock to the controller. (It may cause
of malfunction of the controller.)
6. Do not use chemical detergent or solvent, but use a dry towel in
cleaning the controller. (It may cause an electric shock or a fire.)
7. Please check the polarity of power before wiring and connecting the
sensor.(It may cause an electric shock or explosion.)
8. Power supply should be insulated and limited voltage/current or Class 2,
SELV power supply device.
9. Altitude max. 2,000m
10. Pollution degree 2
11. Installation overvoltage category II
12. Relay output wires are at least 75 °C of heat resistance and, use Copper
wires from 18 AWG to 24 AWG.
13. Tighten the screw of the terminal is torque from 0.74 to 0.90 N·m

4
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

편리한Features
Useful 기능 !
※ Function
※순간이동 기능!
of menu return

rn
tu
re
nu
me
n of
F u n ctio

If 임의의 (위치)
you press the up key
설정 pressing
while 메뉴에서 the set key
inSET키를 누른menu,
any setting 상태
에서
you UP키를
can move누르면
to the
해당되는 상위(그룹)메뉴로
corresponding upper menu순간 점프하여 빠르게
원하는
and 메뉴로
move 이동할
to the 수 있습니다.
desired menu immediately.

※ Use the menu return function to speed up


※ 순간이동 기능을 사용하십시오!
the setting up to 10 times faster.
설정속도가 최대 10배 까지 빨라집니다.
5
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

Contents
1 . Ordering Information 7
2. Input ranges & Output constitutions 9
3. Dimensions & Panel cutouts 13
4. Terminal Arrangements & Wirings 17
5. Ratings & Specifications 19
6. Features & Function 20
7. Check points before Using 21
8. Initial installation & Min. operation procedures 22
9. Entering into "set menu" and Setting method 23
10. Flow Chart (Parameter structure) 25
11. Easy function & Safety function 26
12. Functions of each setting group 31
1) Control group setting 31
2) Set value(SV) group setting 33
3) Auto tuning(AT) group setting 33
4) P.I.D group setting 34
5) Heater ammeter & HBA group setting 36
6) Alarm(ALARM1,2,3) group setting 37

7) Retransmission group setting 40


8) Communication group setting 41
9) Output group setting 44
10) Input group setting 46
11) Error indication during operation 48
6
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

1. Ordering Information

T 5 -
(4) Power supply voltage
(3) Optional function
(2) Control mode
(1) Size

(1) Size
Code Model Size Remarks
2 T52-SERIES 48(W) x 96(H) x 77(D) Option: 0, 1, 2
3 T53-SERIES 96(W) x 48(H) x 77(D) Option: 0, 1, 2
4 T54-SERIES 48(W) x 48(H) x 77(D) Option: 0, 1, 2, 3, 4, 5, 6, 7
7 T57-SERIES 72(W) x 72(H) x 77(D) Option: 0, 1, 2
9 T59-SERIES 96(W) x 96(H) x 77(D) Option: 0, 1

(2) Control mode


Code Description Remarks
S SINGLE Heating or Cooling control
C COMBINE Normal type (Single) + Heating / cooling type (Dual) integration
Dedicated product for monitoring and controlling the
L LIMIT CONTROLLER temperature for safety

(4) Power supply voltage


Code Description Remarks
0 100 ~ 240V AC General-purpose usage
1 24V AC or DC Alternating or Direct current usage

7
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

(3) Optional function


Model Code Description Remarks
T52-SERIES RELAY output 1(MAIN/Alarm 3), Alarm output 2,
Basic Basic function +
T53-SERIES SCR(4~20mA), SSR(Voltage pulse) 1,
function (Option code)
RET(4~20mA Retransmission output)
0 D.I (SV1, 2, 3) External digital input Ex.) T52, T53-C00
Communication RS-485(MODBUS-ASCII, RTU)
1 Ex.) T52, T53-C10
Heater ammeter & HBA(CT) Heater break alarm
T54-SERIES RELAY output 2 (ALARM & MAIN OUTPUT), Basic function + Option code
0 SCR(4~20mA), SSR(Voltage pulse) 1 (0 : No option)
1 RET(4~20mA Retransmission), Alarm output 2 Ex.) T54-C10
2 HBA(CT) Heater current & Break Alarm, Alarm output 2 Ex.) T54-C20
3 D.I(SV2, 3) External input, Alarm output 2 Ex.) T54-C30
RET(4~20mA Retransmission),
4 Ex.) T54-C40
Communication (RS-485)
HBA(CT) Heater current & Break Alarm,
5 Ex.) T54-C50
Communication (RS-485)
D.I(SV2, 3) External input,
6 Ex.) T54-C60
Communication (RS-485)
7 Communication (RS-485), Alarm output 2 Ex.) T54-C70
T57-SERIES RELAY output 1, Alarm output 2, Basic function + Option code
0 SCR(4~20mA), SSR(Voltage pulse) 1 (0 : No option)
Communication RS-485(MODBUS-ASCII, RTU),
1 RET(4~20mA Retransmission), Ex.) T57-C10
HBA(CT) Heater current & Break Alarm
D.I(SV2, 3), RET(4~20mA Retransmission),
2 Ex.) T57-C20
HBA(CT) Heater current & Break Alarm
T59-SERIES RELAY output 1, Alarm output 2,
Basic function + Option code
0 SCR(4~20mA), SSR(Voltage pulse) 1,
(0 : No option)
RET(4~20mA Retransmission)
Communication RS-485(MODBUS-ASCII, RTU),
1 Ex.) T59-C10
HBA(CT) Heater current & Break Alarm

1) Example of model building

Ex.) T 5 4- C 10
(1) Size : 48(W) x 48(H) x 77(D) "4"
(2) Control mode : COMBINE "C"
T54-C10
(3) Function per option : RET, Alarm output2 "1"
(4) Supply voltage : 100~240V AC "0"

8
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

2. Input ranges and Output constitutions


1) Input ranges ※ The T50 series has multiple inputs, which may be set and changed by the user.
Input type Input Code Temperature range Accuracy Remarks

1 -200 ~ 1370
K
2 -199.9 ~ 999.9

15 -200 ~ 1000
J
3 -199.9 ~ 999.9

16 -200 ~ 1000
E
4 -199.9 ~ 999.9

T 5 -199.9 ~ 400.0

R 6 0 ~ 1700
Thermocouple B 7 400 ~ 1800
(T.C) * F.S is max. value
S 8 0 ~ 1700
to min. value of
±0.3% of FS
17 -200 ~ 900 each range.
L + 1 Digit
-199.9 ~ 900.0 * Digit is minimum
9
of display.
10 -200 ~ 1300
N
14 -199.9 ~ 999.9

U 11 -199.9 ~ 400.0

C (W5) 12 0 ~ 2300

D (W3) 13 0 ~ 2400

JPt100Ω 20 -199.9 ~ 500.0


(JIS, KS) 22 -200 ~ 500
RTD
Pt100Ω 21 -199.9 ~ 640.0

(DIN, IEC) 23 -200 ~ 640

0~100mV DC 33 0 ~ 100mV DC ※ When using 1~5V input


Voltage (30), the interior jumper
(V DC/mV DC)
-10~20mV DC 32 -10 ~ 20mV DC
switch must be relocated.
1~5V DC 30 1~5V DC

When using current


Current 4~20mA DC 30 input, use the resistor
250Ω on input terminal.

※ How to change the interior switch when using 1~5V input


MULT-IN MODE IN 1~5V ONLY MODE

① Remove plate or take ② Move and insert the jumper ③ Relocated jumper as above
out the main cover. that pulled by tweezers. and attach plate or mounted
9 cover.

D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

2) Output configuration
(1) Alarm output configuration
T50 SERIES can use up to three different alarm outputs for 21 different types.
In addition, the unique output configuration of the system allows the user to
designate the output port freely, and the alarm 1 ~ 3 outputs can be exchanged
or used together.
Press and hold for
more than 3 seconds
T54-C0x, C4x, C5x, C6x
short (The default alarm option model)

shortly 5 times
① Outoput relay(3)
A2TY OFF

Alarm setting group

Alarm 1 type
경보1 종류 설정 setting
(No.
(번호1~21)
1 ~ 21)

② Outoput relay(3)
Alarm
경보2 종류 2 type
설정 setting ALARM 2 T54-C1x, C2x, C3x, C7x
(번호 1~20)
(No. 1 ~ 20) (Additional Alarm Option Models)

Alarm 3 type
경보3 종류 설정setting
(번호1~20)
(No. 1 ~ 20)

Alarm 3 Dead band


경보3 데드밴드 설정 setting
(히스테리시스
(Hysteresis [℃])
[℃]) ③ Outoput SSR(1) ALARM3 enabled when Alarm 1 and Alarm 2
or SCR(2) output SSR(1) or SCR(2) dedicated outputs
Alam1 delay 설정
time setting is set
경보1 지연시간
(off/1~240 sec)
(OFF / 1 ~240초)

Alam2 delay 설정
경보2 지연시간 time setting
(off/1~240 sec)
(OFF / 1 ~240초)
ALARM3
Alam3 delay 설정
경보3 지연시간 time setting enabled when
(off/1~240 sec)
(OFF / 1 ~240초) output SSR(1)
or SCR(2) is
Alarm 3 Setting value
경보3 설정값 set
(알람설정
(Alarm [℃]) [℃])
setting

Alarm 1 output설정
경보1 출력포트 port setting A1Pn~A3Pn(AL1~3)
A1Pn~A3Pn(AL1~3)

(AL1,
(AL1,AL2,
AL2, AL3)

Alarm 2 output설정
경보2 출력포트 port setting ALARM3
(AL1,AL2,
(AL1, AL2, AL3)
AL3)
enabled when
output SSR(1)
경보3 출력포트
Alarm 3 output설정port setting or SCR(2) is
(AL1, AL2, AL3) set
(AL1, AL2, AL3)

10
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

※ Detailed description related to setting of control and alarm output port


① Basically, the T50 series output supports a total of three event outputs, each of
which consists of 21 types.
② Basically, alarm 1 is set to AL1 port, alarm 2 is set to AL2 port, and alarm 3 is set
to AL3 port. However, if necessary, the output port can be used in combination or
a single output port can be used It provides a powerful function that can logical
sum or OR the alarms 1 to 3.
☞ When alarms 1 to 3 are set to one port, it is necessary to set only one of the
process high and process low, or if the process high and the process low are mixed
and the port is specified as one port, process high.
③ When the cooling output is set to RELAY (3) by selecting the heating / cooling
dual control mode, the AL2 (OUT2) port is used as the cooling control output.
④ In case of model without alarm option of T54 (48x48mm), the main control output
(①, ②, ③) port can be automatically changed to various output contact according
to the setting and can be used as maximum 2 relay contact output.

11
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

(2) Setting of heating and cooling control PID control mode


Example) Model T54-C10
T50 SERIES Output
selection
Heating or cooling Output
T54
number control (output 1) terminal
Press and hold for
more than 3 seconds 0 RELAY ON/OFF control ①, ②, ③
1 SSR P.I.D control ⑥, ⑦ D.I
short
2 SCR (4~20mA) P.I.D control ⑥, ⑦
3 RELAY P.I.D control ①, ②, ③

※ Press and hold key for more than


3 seconds in any menus to return to Normal
operation mode. After the auto tuning is
completed, the entry of the input and
output setting menu is automatically blocked.
Please refer to the instruction manual if
PV
reset and release are required.

SV
Use or , key to adjust the setting number corresponding to the output type, and then save it

using key.
Example) Model T54-C10
PV

Selecting Output Operation (REV, DIR, DUAL) Output Heating or cooling Output
selection
REV : Heating control number control (output 2) terminal
SV
DIR : Cooling control
1 SSR P.I.D control ⑪, ⑫
Dual : Heating and cooling control
2 SCR (4~20mA) P.I.D control ⑪, ⑫
Only displayed during dual (heating and cooling) control
3 RELAY P.I.D control ⑭, ⑮

Cycle time in heating (output 1) SSR or relay


※ It is not used in the SCR (4 to 20 mA) mode,
Cooling Gain
so it will not be displayed. output Gco > 1.0
GCO Operation
Cycle time in Cooling (output 2) SSR or relay Gco = 1.0
※ It is not used in the SCR (4 to 20 mA) mode,
so it will not be displayed.
Gco < 1.0
The cooling gain setting range can be set from 0.1 to 10.0

Heating side
※ Caution! proportional band
Cooling side
proportional band
In Heating & cooling mode, control output uses alarm 2
output, so must be change to alarm 1 or alarm 3 when
using alarms. 0 PV

(3) Dead band setting


It is used only for heating / cooling control and sets the dead zone area of
heating and cooling.
※ Explanation of operation according to dead band value
The default value is set to 0.0% and does not need to be
PID group menu
set except in special cases.

Select group (default) - value(Overlap band) + value(Dead band)


output output

output output output output


Dead band setting
of heating of cooling of heating of cooling
(-100 ~ 100%)
0 PV 0 PV
Set value(target) Set value(target)

12
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

3. Dimensions and Panel cutouts


1) T52 (48x96 mm) Dimensions
45±0.5
48.0 10.0 77.0

Min. 20

92±0.5
96.0

96.0

Min. 30

91.0
T52 / T53 (96x48)
Panel cutouts

(Unit: mm)

2) T53 (96x48 mm) Dimensions


96.0 10.0 77.0
48.0

48.0

43.6

3) T54 (48x48 mm) Dimensions T54 (48x48) Panel cutouts


+0.5
48.0 8.8 77.0 45 -0
+0.5

Min.17
45 -0
48.0

48.0

44.9

Min.17

(Unit: mm)

13
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

4) T57 (72x72 mm) Dimensions


T57 (72x72) Panel cutouts
72.0 9.0 77.0
68±0.5

Min.20

68±0.5
72.0
72.0

67.0
Min.30

(Unit: mm)

5) T59 (96x96 mm) Dimensions


96.0 10.0 77.0 T59 (96x96)
Panel cutouts

92 ± 0.5
96.0
96.0

91.0

92 ± 0.5
Min.30

Min.20

(Unit: mm)

※ HBA option (Heater break alarm)


Current transformer (CT) : using 800:1 CT of TS-9W or CTL-6-S

Panel cutouts

CTL-6-S (U-RD) (Unit: mm)


TS-9W(Temcoline)
14
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

6) Installation
(1) T54-SERIES
① Process the mounting hole referring to the panel machining dimensions of
the previous page on the panel.
② Insert this device from the front of the panel.
③ After inserting the two brackets into the holes of the left and right brackets
of the device, Slide it until it fits tightly to the panel and secure it.

Panel Panel

Bracket hole

(2) T52/ T53/ T57/ T59-SERIES


① Bore a hole in the panel, referring to the panel cutouts on the previous page.
② Insert this device into the front of the panel.
③ Insert 2 brackets, one each on the bracket holes on the top and the bottom
of the device.
④ Secure using screws on the two locations at top and bottom.

Hole of fixing screw Hole of fixing screw

Bracket hole Bracket hole Turn the screw


2-3 times after
contact with panel.

[ figure 1 ] Top side [ figure 2 ] Bottom side [ figure 3 ] Fixing completion

15
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

7) Terminal wiring method


(1) SCREW
① When wiring the terminal, tighten the screw with a tightening torque of
0.74 to 0.90 N.m.

SCREW

(2) Cautions for terminal wiring


① Signal lines and power lines should be separately wired to avoid the effects
of noise
② Use a crimp terminal to wire the terminals.
③ Tighten the terminal screws with a tightening torque of 0.74 to 0.90 N.m.
④ Please use the following form of crimp terminal M3.5.

Less then 7.2 mm

Less then 7.2 mm

Crimp terminal

16
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

4. Terminal Arrangements and Wirings


1) T52 (48x96 mm), T53 (96x48 mm)

T52 OPTION1
OPTION
OPTION2

T53 (T52-S10)
(T53-S10)
(T52-C10)
(T53-C10)

D.I 1

D.I 2

2) T54 (48x48 mm)

T54 OPTION1
OPTION
OPTION2
(T54-C1X) (T54-C2X)
D.I
D.I
D.I

OPTION3 OPTION4 OPTION5 OPTION6 OPTION7


(T54-C3X) (T54-C4X) (T54-C5X) (T54-C6X) (T54-C7X)

D.I D.I D.I D.I D.I D.I D.I D.I D.I D.I

17
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

3) T57 (72x72 mm) OPTION

T57 OPTION 1
(T57-C1X)
OPTION 2
(T57-C2X)
D.I 1

D.I
D.I11
D.I 2
D.I
D.I22

4) T59 (96x96 mm) ※ Terminal explanation (T59-S10 basis)

T59 Terminal : OUT1 only for output


selection no. 0, 3 (Relay output) mode.
Terminal : OUT1 only for output.
selection no. 1, 2 (SSR, SCR output) mode.
Terminal : RET(Retransmission 4~20mA)
or for power of sensor SPS. (DC 15V)
Terminal : Power supply terminal.
Terminal : Alarm1 output terminal.
Terminal : Alarm2 output terminal.
D.I 1 Terminal : It is an external input (DI)
terminal. various functions can be set with
D.I 2 external switches according to DIS 1-5 (1: OFF,
2: SV 1-3, 3: run / stop 4: 4: auto / manual
5: alarm reset).
Terminal : The input sensor type is
changed according to the input setting number
with the univeral input terminal.
Terminal : RS-485 communication
terminals completely isolated, Modbus-ASCII,
Modbus-RTU, PC-Link, TL-Link basic.
OPTION 1 (T59-C1X) Terminal : C.T(800:1) input terminals
for Heater break alarm.
18
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

5. Ratings and Specifications


Model T50 SERIES
Rating 100~240V AC 50~60Hz (voltage operating range: 85~265V AC)
Power Supply
※ Option: Rating 24V AC or DC (operating voltage range 20~28V DC)

Power Consumption 5VA(MAX) at AC100~240V 4W at DC 24V


TC: K, J, T, E, R, B, S, L, N, U, C(W5), D(W3)
Platinum RTD: KPt100(KS), JPt100(JIS), Pt100(DIN)
Input Type
Current input(A): 4~20mA DC
Voltage input(V): 1~5V DC, -10~20mV DC, 0~100mV DC

Dispaly Accuracy ±0.3% of FS +1 Digit

Current input(250Ω), Voltage input(including TC) 1MΩ min.


Input Impedance (RTD line resistance: ≤ 10Ω, when 3-line resistance are
the same)
Input Sampling Period 50~250ms (variable according to SG-PID algorithm)
1c 250V AC, 3A(resistance load) electric lifespan ≥ 100,000 min.
Relay
(time proportional PID output or ON/OFF output)
Control Voltage DC15V 25mA (Built-in short protection circuit)
Output (S.S.R) Voltage pulse (time proportional PID output)
Current
(S.C.R) 4~20mA DC, load impedance ≤ 600Ω(continuous PID output)
Super 2 degree-of-freedom PID (SG-PID algorithm),
Control Method
S-Fuzzy, Auto-Tuning
Multi SV Input(D.I) ON: ≤ 1KΩ, OFF: ≥ 100KΩ(external control SV1, 2, 3)

4~20mA DC, load impedance ≤ 600Ω resolution 1/4,600


Retransmission
PV(process value), SV(set value), MV(manipulated variable [%]),
Output
SPS(sensor module power supply)
Alarm ALARM 1, 2 1a 250V AC 3A (Resistive load)
HBA common
Output (C.T) HBA: 0.1 ~ 38.0 A AC (Resolution 0.1A)
2 wires RS485 totally independent isolation structure
Communication Max. speed: 19,200bps/ Max. connect no. 99 devices (32
Output devices recommended) Support protocol: PC-Link, TL-
Link, Modbus-ASCII, Modbus-RTU
Ambient Temperature -10~50℃/ relative humidity 25~85% RH
and Humidity (but with neither condensation nor freezing)

Approved T54
Certification (except T54-C10, C20, C30, C70)
Standards
Conformed

Weight T52, T53, T57: 230g T54: 140g T59: 320g


(Bracket, Accessories included) ※ + 30g, if options are added

19
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

6. Features and Function (ex. T54-SERIES )

① Process value (PV)


display (Red color)

② Auto tuning (AT) lamp

③ Set value (SV)


display (Green color)

⑩ Set value Up key

⑨ Set value Down key

⑧ Shift key
⑦ Storage & Function key
④ Control output lamp
⑤ SV2 display lamp
⑥ Alarm output lamp
⑪ Cooling output lamp (for dual
control)
※ Description
NAME FUNCTION

① Process value Display the process value. (red color)


② Auto tuning lamp Flash every 0.5 second during auto tuning.
③ Set value display Display the set value, codes, and modes.

④ Control output lamp Lights when the control output is ON.

⑤ SV2 display lamp Lights when the SV2 is displayed.

⑥ Alarm output lamp Lights during the alarm is ON.

⑦ Function key Use to move the menus, to store, and to operate.

⑧ Shift key Use to shift the digits.

⑨ Set value down key Use to decrease set value and to move the menu.

⑩ Set value up key Use to increase set value and to move the menu.

⑪ Cooling output lamp Displays cooling output during heating/ cooling control.

20
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

7. Check points before Using


1) Default values at the point of manufacture
The default input and output values of the product at the point of manufacture
are as follows.

Input : K-Type (Code No. 1) Output : SSR (Code No. 1)

※ In the case of the basic model of T54-S00 only, when SSR(1) or SCR(2) is chosen
as the output mode, Alarm 1 output will be in main relay.(Refer to page 8 for
details.)

2) 7 Segment display indications

3) Initial display on power supply (T54 SERIES basis)


Option indication
Model Name
0 : Basic type (No option)
1 : RET, ALARM1, 2
2 : HBA(CT), ALARM1, 2
3 : DI, ALARM1, 2
4 : RET, RS-485
5 : HBA(CT), RS-485
6 : DI(SV1, 2), RS-485
7 : RS-485, ALARM1, 2

Output type indication


0 : RELAY ON/OFF control
1 : SSR (VOLT-PULSE) PID control
2 : SCR (4~20mA) PID control
3 : RELAY PID control
Input type indication
01 : K-Type (-200~1370 ℃)
02 : K-Type (-199.9~999.9 ℃)
Firmware version display
33 : mV DC (0~100mV)

21
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

8. Initial installation and Minimum operation procedures


The following are the instructions for initial installation and minimum operation
procedures. Please read the contents of this manual, including the general
functions outlined here, as thoroughly as possible before operating the device.

1) Check the external wiring diagram and specifications.


(power supply and terminal arrangement)

2) Check input and output specifications!


The default setting for the T50 series at the point of manufacturer are as follows.

Input : K-Type (setting code : -200 ~ 1370℃)


Output : SSR mode (setting code 1)

If you wish to change the input or the output type, please select the option
you desire on the input group and the output group menus.

※ The input type settings must be configured first before changes to other
set values are made.

When the input type is changed, all other parameters (set values) are reverted
to their factory default.

3) Select the desired set value (SV).

4) Please set auto-tuning or P, I, D values to suit the operating environment.


Auto-tuning is recommended except under special circumstances.

※ To ensure safety and prevent wrong operation, once auto-tuning


has been completed, "level-2"(setting menu display limit) will be set
automatically. At the same time, setting menu output group(8.out)
and input group(9.in) are not displayed. If needed reset, please
change to "level-3"(setting menu display limit) and operate.
Please refer to the "3) setting menu display limit" at page 27.

22
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

9. Entering into "set menu" and Setting method


1) Input & Output type setting
Temcoline products are universalized input and output.
Please set up input and output type firstly and use when
install our unit.

more than 3 sec.

When it is LEVEL 3, input/output set is


available.(Refer to p25) Setting menu
Press display limit(LEVEL) function)
once shortly LEVEL 1~3

Press once shortly

① Input type setting : Select the desired input sensor type.


(setting code 1~33 / refer to P7, Input ranges)

INPUT(T.C) CODE TEMP. RANGE INPUT(RTD) CODE TEMP. RANGE


1 -200 ~ 1370
K 20 -199.9 ~ 500.0
2 -199.9 ~ 999.9 J P t 1 0 0Ω
15 -200 ~ 1000 (JIS, KS)
J 22 -200 ~ 500
3 -199.9 ~ 999.9
16 -200 ~ 1000 -199.9 ~ 640.0
E 21
4 -199.9 ~ 999.9 P t 1 0 0Ω
(DIN, IEC)
T 5 -199.9 ~ 400.0 23 -200 ~ 640
R 6 0 ~ 1700
B 7 400 ~ 1800 INPUT(V DC/mV DC) CODE
Press
S 8 0 ~ 1700
once shortly 0~100 mV DC 33
17 -200 ~ 900
L
9 -199.9 ~ 900.0 -10~20 mV DC 32
10 -200 ~ 1300
N 1~5V DC
14 -199.9 ~ 999.9
U 11 -199.9 ~ 400.0 30
4~20mA DC
C (W5) 12 0 ~ 2300 (Use 250Ω r e s i s t o r )
D (W3) 13 0 ~ 2400
Press
once shortly

② Output type setting : Select the desired output type.


SETTING
CONTROL OUTPUT
CODE
0 RELAY ON/OFF CONTROL
1 SSR P.I.D CONTROL
2 SCR (4~20mA) P.I.D CONTROL
3 RELAY P.I.D CONTROL

※ If the P value is set to OFF even when the P.I.D control output 1, 2, or 3
is selected, it operates in the ON / OFF mode.
23
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

2) Set value(SV) setting [ in condition of Mvn = OFF (basic) ]


① Enter to setting mode by key
② Set a desired value by key
③ Store a value by key

3) Quick auto tuning


AT operation start : + 0.5 second
AT stop by perforce : + 0.5 second

AT command lamp (flash every 0.5 sec.)

Auto-tuning is required before operating for the first time. Set the target value(SV) in the
range mainly used and run auto-tuning. When auto-tuning begins, the "auto-tuning command
lamp" will flash every 0.5 second and will turn off upon completion of the auto-tuning
process. Please refrain from operating the keys while auto-tuning is in progress.

※ Function of menu return

※순간이동 기능!

간이
동기
능! 편리한 기능!
※ Useful Features

Use the menu return


※ 순간이동 기능을
function to speed up
사용하면 설정속도가
the setting up to
임의의
If you press(위치)
the up key 최대 10배까지 빨라
10 times faster.
설정 메뉴에서
while pressing the set key
SET키를 누른상태
in any setting menu,
집니다.
에서 UP키를 누르면
you can move to the
해당되는 상위 (그룹)
corresponding upper menu
메뉴로 순간 점프하여 빠르게
and move 메뉴로
원하는 to the desired
이동할menu immediately.
수 있습니다.

24
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

10. Flow Chart (Parameter structure)


OPERATION MODE
SET + 0.5 초
+ 0.5 sec. AUTO TUNING...
SET + 3 초 SET SET
+ 3 sec.

SET 33sec.
초 SET
SET

SET
33 sec.

SET

3 sec. SETTING MODE

※ Function of
menu return

+
If the device is left idle
If you press the for approximately 50
up key while seconds after entering
pressing the set
key in any setting menu, a setting menu other
you can move to the than the operation mode,
corresponding upper menu
and move to the desired menu it will return automatically
immediately. to the operation mode.

※ The full menu diagram above shows all control and setting menus on the T50 series, but during actual
operations the menus that are the most relevant to the situation according to the options and the operation
mode, providing a simpler user interface while retaining functionality.

25
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

11. Easy function and Safety function


1) Easy Menu
"Easy Menu" is displays the most frequently used functions of the T50 series
and hides the others.
<Setting method>

operation mode operation mode

+ 3 sec.
3 sec.
3 sec.

3 sec.
[EASY = ON] User setting menu

(SV. NO = 1) (SV. NO = 2) (SV. NO = 3)


2) Control output[%] (Mvn) check and
manual operation mode
"Mvn [%] check function" display the control
output[%], which can be viewed by pressing
the key while operating in normal
operation mode and is shown as a
percentage of control output (0~100(%))
in the SV display. In this normal operation
mode, by pressing the key each, showing
the SV and Mvn values alternately.
Any required, value of SV can be adjusted
by , or key and stored by
pressing key.
<Setting method> <In condition of Mvn=ON>
operation mode <Mvn Manual Operation>
operation mode "Mvn [%] Manual Operation" can be used for
testing the control output and for the manual
control system, Press and hold the and
keys simultaneously for 2 seconds in the control
+ 3 sec. output (Mvn) display to enter. At this time, you
can manipulate value the desired amount of
output with the and key.
3 sec.

PV PV

SV SV

[Mvn = ON] + 2 sec.


Mvn display screen Blinking!
(Present Mvn Out = 85%) (Display on the manual operation mode)
In manual operation mode, press key for
※ After manual operating must be return to the normal about 1.5 seconds to return to normal operation
operation mode. (automatic control) mode.
26
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

3) Setting menu display limit (LEVEL) function


The setting menu display limit function limits the range displayed according
to the level set in the control and the setting menus in the T50 series. This can
be used, for example, to prevent user's miscontrol after all settings have been
configured.

<operation mode> 3 sec.

+ 3 sec.

[ LEVEL = 0 ]
This may only change
the target SV.
[ LEVEL = Lock ]
Locking all setting
and control menus.

LEVEL 1~3
[ LEVEL display range by setting ]

DISP(LEVEL) = 3 [menu group 0~9] ALL


DISP(LEVEL) = 2 [menu group 0~7]
DISP(LEVEL) = 1 [menu group 0~1]

※ Once auto-tuning has been completed, setting menu display limit


will be set automatically at "level-2" to ensure safety and prevent
user miscontrol. If the input and the output parameters need to
be changed after auto-tuning, set to "level-3" before doing so.
27
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

4) How to use other special functions


The T50 series has convenient and powerful functions. You can
select whether or not to use the following special function setting menu.

+ 3 seconds (Special function setting menu)


Press the key a short time to advance to the next function menu.

① LEVEL Setting Menu Lock Function (See Page 25)

② EASY Menu setting function (See Page 24)

③ Mv(Manipulated variable) Display setting function (see Page 24)


MV [%] Displays the control output.

④ Setting of Auto Tuning type


There are two modes, FAST and NORMAL, but they are all in the default
"FAST mode" except for special cases.

⑤ LBA(Control Loop Break Alarm) Set control loop break alarm(LBA)


If A 1ty (first alarm output type setting) is set to 21, If you do not use the
HBA feature or the model does not have the HBA feature, the LBA feature
is automatically enabled. The LBA value is automatically set during auto
tuning (enabling the menu only when using LBA).
※ What is the control loop alarm(LBA) ?
LBA is a function that outputs an alarm when the input (sensor) does not change even if the control
output is output for a certain time or longer, considering that there is an error in the control loop.
That is, it can be used as a substitute for the heater break alam(HBA) function, and is output when
a defect or malfunction of the control device occurs.

⑥ Run /stop function setting


In the normal operation mode, operation or stop control is possible by
pressing the key for more than 1.5 seconds. In other words, this is
a menu that activates this function.
SV
■ Stop mode
Activate the run / stop key
- Display : stop on the SV
- Output : Control off , Alarm off
- Auto tuning : stop (P.I.D unchanged)

⑦ Heater operation time (accumulated) function


It is a function that can prevent accidents so that the life of the heater
can be predicted in advance and prepared in advance. It is accumulated
up to 9999 days 23 hours 59 minutes.(about 27 years or more)
DAY

Normal operation mode

HOUR MINUTE

※ It is possible to initialize heater operation time but if necessary, contact customer support team.

28
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

⑧ Setting the input compensation function for each section (4 sections)


This compensation function can be used when there is a mechanical
problem such as a heater block, a chamber, etc., and when the present
value(PV) does not match the external measured value due to the
position of the temperature sensor.

※When is turned on in the special function setting menu,


group menu is created in the general setting group menu.

Actual temperature

+7℃ deviation has occurred

After compensation
temperature

+5℃ deviation has occurred

-2℃ deviation has occurred

[ Input compensation for each section ]

Ex.) The actual temperature of the control object used at


0 ~ 1000 ℃ was measured. Measurements at 250 ° C are
+ 5 ° C, -2 ° C at 500 ° C, and + 7 ° C at 750 ° C,
In this case, the compensation settings are as follows.
FR-L=0℃, BSP1=250℃, BSP2=500℃, BSP3=750℃, FR-H=1000℃
BS0=0℃, BS1=-5℃, BS2=+2℃, BS3=-7℃, BS4=0℃

⑨ Alarm latch function setting (OFF-AL1-AL2-AL3-ALL)


This function maintains the alarm status until it is manually released
from the outside after an alarm occurs. To disable this feature, press
the Shift ( ) button on the front of the product.
Alternatively, you can disable the function by connecting an external
switch to the DI (SV2) terminal.
When this function is set, the maximum or minimum value of input (PV) is
recorded, until you disable this feature, you can check the maximum or
minimum value to identify the problem.
Alarm(Latch) Reset
(Push s/w recommended.)
<< Information check menu >>
[Set value menu] [Peak value display menu]

Check peak value when


an alam occurs
Peak hold value

Present value(PV) and


Set value(SV)

Release alarm
(press for more than 1.5 seconds)

29
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

⑩ Disiable function of reset on front ( )


Set whether to use latch function ON or OFF when using alarm function.

front reset ON/OFF

⑪ Setting the indicator mode


This function is for use only for monitoring without using the control
function. When this function is set, all control related functions are
not displayed and all parameters and user interface are automatically
optimized as monitoring dedicated devices.

※ In the indicator mode, only 4. HBA setting group / 5. ALM setting group / 6. TRS setting
group / 7. COM setting group / 9. IN setting group and special function setting menu can
be set.

T54-C2x, C5x (HBA option model)

Current detector(CT 800: 1)


TC8L or CTL-6-S

※ In the HBA setup menu, the ammeter function and the overcurrent (HOC) alarm and the
HBA alarm are used as the current lower limit alarm function.

ⓐ SV: set temperature of alam ⓑ SV: Heater or other current

※ SV window can be used as a general ammeter. Depending on the alarm and settings.

30
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

12. Functions of each setting group


1) Control group setting
Control zone, fast function, and ramp function may be selected, and the fast
function works only in PID control mode. In addition, as shown in Table 1, the
3 set values (SV1, SV2, SV3) preset by the two external contact inputs may be
selected and controlled.
display description setting range condition initial value

Enter to control group - - -

Activate function of zone PID OFF / ON Always OFF

Activate high speed PID mode OFF / ON PID control OFF

Initial rising temp. setting


OFF / EUS (0 ~ 100 %) Always OFF
(Ramp function)

Initial drop temp. setting


(Ramp function) OFF / EUS (0 ~ 100 %) Always OFF

Time (Hour/Minute) Always


MIN / HOUR HOUR
unit selection (Ramp function)
OFF / SV1,2,3 / RUN /
Activate external digital input STOP / AUTO-MANUAL / D I option OFF
ON/OFF switch ALARM RESET

※ Function selection menu of external digital input

① OFF ② SV1,2,3 ③ Run ④ Stop ⑤ Auto/ Manual ⑥ Alarm(Latch)


selection Reset

selection selection selection selection selection

※ EU : An engineering unit in compliance with the input range


Ex.) Input selection no. : 01 (K-TYPE)

EU 0 % = -200 INPUT -200 0 1370 [℃ ]

EU 100 % = 1370 EU 0 100 [%]

INPUT -200 0 1370 [℃ ]


EUS 0 % = 0 (0) (200) (1570)
EUS 100 % = 1570
EUS 0 100 [%]

31
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

(1) Control zone (ZONE): In an environment with large temperature fluctuations,


the optimal PID value may vary according to the temperature range. This function
allows 3 separate temperature ranges to be set in order to control the PID value
in each of them.
(2) FAST MODE : The T50 series uses Temcoline's unique SG-PID variable sampling
control. Therefore, it is recommended to turn it off normally. If a very fast control
system, such as pressure control or motion control, is required, you can fine-tune
the control by using Fast mode ON.
(3) Ramp function : This controls the incline toward the initial set values (SV1, SV2,
SV3). To use this function, set the time at the initial temperature increase and
decrease settings, or define the desired initial temperature increase or decrease
per hour or minute. Once this has been set, a steady incline from the starting
temperature to the set values will be maintained.

[℃]

(SV)100 For example,when the


desired SV is set as 100℃,
80
the initial temperature
60 increase as (UP.RT) 20℃,
and the time unit (RTMU)
40
as in minutes, the incline
(Present Temp.)20 to the SV will be at 20℃
per minute.
1 2 3 4 [Hour/Min.(t)]
[시간/분(t)]

(4) Digital input selection(dis): External Target set value on External contact input (SV-n)
contact input.It is a function to select DIS SV selection mode by
whether to use. selection external contact signal
① OFF: Stops the external digital input OFF NO external contact signal
external signal
function. display selection SV2 SV3

② SV1, 2, 3 selection: Up to three store display the SV1 OFF OFF


ON
display the SV2 ON OFF
values can be set as set values(SV).
display the SV3 ON ON
③ RUN: It can be controlled by connecting
a digital signal or by connecting a ※ Please use a non-voltage contact (relays,
switch to the external DI (SV2) input switches) for direct input. If a non-contact
device such as a semiconductor are used,
terminal. (initial value: Run) please operate within the ranges
④ STOP: It can be controlled by connecting ON = under 1KΩ, OFF = over 100KΩ
a digital signal or by connecting a switch to the external DI (SV2) input terminal.
(initial value: Stop)
⑤ AUTO/MANUAL : It can be controlled by connecting a digital signal or by connecting
a switch to the external DI (SV2) input terminal.
※ In order to use Run / Stop function and Auto / Manual function, 'Mvn' and 'St p.M' function must
be activated in special function setting menu, and communication and external input terminal can
be controlled.
⑥ Alarm (Latch) Reset: When the Alarm Latch function is turned on in the special
function setting menu, you can use the reset function by connecting the push
switch to the external DI (SV2) input terminal.
32
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

2) Set value(SV) group setting


With the SV group, the 3 control set values (SV1, SV2, SV3) must be set before
they can be selected and controlled as desired by direct input signal or by the
internal menu.
※ When controlling with external contact signal, external contact input switch (DIS)
of control setting group must be set to "SV-n". When it is OFF, it is selected by
setting value number selection (SV, no).
display description setting range condition initial value
Enter to set value setting
group - - -

Target set value NO 1/2/3 Always 1

Target set value SV1 EU (0.0 ~ 100.0 %) Always EU (0.0%)

Target set value SV2 EU (0.0 ~ 100.0 %) Always EU (0.0%)

Target set value SV3 EU (0.0 ~ 100.0 %) Always EU (0.0%)

3) Auto tuning(AT) group setting


Before the PID temperature controller can be used for the first time, the P, I,
D values must be tuned. The auto-tuning function finds the optimal value by
tuning automatically according to the load factor and other conditions. Please
make sure that the controller is tuned before using it for the first time, by
defining the set values in the most frequently used range and running auto-
tuning. When auto-tuning begins, the "auto-tuning command lamp" will flash
every 0.5 second and will turn off upon completion of the tuning process. Please
refrain from operating the keys while auto-tuning is in progress. The T50 series
is able to perform several kinds of auto-tuning. To make auto-tuning easier, the
Quick-AT function, which allows the command to be executed with a simple
external key combination.
display description setting range condition initial value
Enter to auto tuning
setting group - PID control -

Auto tuning (AT) type


Standard / Low PID control STD
selection

Auto tuning (AT)


start selection OFF / 1 / 2 / 3 / Auto PID control OFF

This product performs optimally when auto-tuning is executed in the STD


mode according to the S-PID algorithm. We recommend that you operate the
product in the STD mode.

33
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

(1) Types of auto-tuning (AT)


The T50 temperature controller has two tuning methods, standard auto-tuning
(STD: based on the set value) and low-SV tuning (LOW: SV - 10%). Under normal
conditions, the standard auto-tuning is recommended.

(2) Start auto-tuning


This menu starts the auto-tuning process. Select the number of the SV that you wish
to tune (SV1 → " 1 ", SV2 → " 2 ", SV3 → " 3 "), and auto-tuning will begin, making
automatic calculations which will be stored under the P, I, D values of the corresponding
SV. When set on AUTO, SV1~3 will be auto-tuned consecutively if in the control
group ZONE is set as off. If ZONE is on, groups 1, 2, and 3 will be created based
on the ranges set in 1RP and 2RP of the PID group, and the results will each be
stored under the PID groups 1, 2, and 3.

4) P.I.D group setting


This is used to view the PID and ARW values produced by auto-tuning in the
auto-tuning groups, and to change the values manually.
(1) In the PID selection group, press the key to set automatically or manually
the anti-reset wind-up ARW value. Pressing again the key will display the
PID selection mode, where you may choose to view the group PID parameters
by selecting 0~3. For example, when " 0 " is selected in the PID mode, no PID
values will be shown. Use the key to select " 1 " and then press the key
to view the PID values for group 1. Selecting " 2 " and " 3 " will display the values
for groups 2 and 3 respectively. (This is intended to prevent accidentally mishandling
the settings.)

(2) Manual reset (MR) is displayed


Maximum range (EU 100%)
when the integral value set at
OFF, and it is used to manually
remove control offsets. Zone 3
2-RP Set point of zone 2 (2RP)
(3) When the control group zone
selection mode is on, 2 zone Zone 2
location settings may be made 1-RP Set point of zone 1 (1RP)
to control 3 zones.
Zone 1
(4) The " n " in the table as below [Time]
indicates that the number may Minimum range (EU 0%)
be from 1 to 3.

This product provides optimal control when ARW is in automatic mode


according to the S-PID algorithm. We recommend that you used the product in
the automatic mode. The ARW function is actually seldom required with S-PID.

34
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

display description setting range condition initial value

Enter to P.I.D setting group - PID control -

Auto /
Anti Reset Wind-up setting PID control AUTO
50.0 ~ 200.0 %

P.I.D group selection 0/1~3 Always 1

OFF / 0.1 ~ 999.9 ℃ PID group


n. Proportional band (P) 20.0 %
(OFF = ON/OFF) selection

n. Integral time (I) OFF / 1 ~ 6000 sec. Always 240 sec.

n. Derivative time (D) OFF / 1 ~ 6000 sec. Always 60 sec.

ntegral time
n. Manual reset (M.R) -5.0 ~ 105.0 % 50.0 %
OFF

Heating and
n. Hysteresis band -100.0 ~ 50.0 % 3.0 %
Cooling type

n. Zone position setting EU (0)< 1.RP< 2.RP


ZONE=ON EU (100.0 %)
< EU (100.0 %)

The meaning of the n symbol in the table indicates that there are a total of three
groups (SV1-3), such as n.P. In other words, you can set the P, I, D parameter
values separately applied according to SV number selection. Up to three P, I, and
D values can be set and individually controlled to achieve optimal control for
each temperature step.

35
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

5) Heater Ammeter and HBA (Heater Burnout Alarm) Setting Group


Temcoline's T50 SERIES supports instrument-level precision AC ammeter. It
supports real-time AC current monitoring and HBA (heater break alarm) function
of 0.1 ~ 38.0 A maximum.In normal operation mode, heater current can be
monitored at the same time as current temperature.

Press and hold for more then


T54-C2x, C5x (HBA OPTION MODEL)
3 seconds.

Short

1 Current transfomer (800:1)


TC8L or CTL-6-S

Shortly 4 times
Burn-out Control output contact
4
CT (800:1)
HBA Setting group
AC 200V
Heater(1KW x 2)

Current setting of heater break alarm


(OFF ~ 40.0A)
① HBA(heater break alarm) current setting procedure is as follows
Normal current value + burn-out current 10A + 5A
HBA Setting value = = = 7.5 [A]
2 2
Hysteresis setting of heater break alarm
② Hdb(Heater break alarm Dead band or hysteresis): This function is to prevent
(0.0 ~ 20.0A)
malfunction when the current change approaches or exceeds the set value.
Heater break alarm start point setting Hdb Setting value = (maximum current - minimum current) x 1.4
(0 ~ 100%/output When setting SCR (#2) However, it is not applicable when the control output SCR (2) is used.

Heater Current Monitor ③ HbS(Heater break alarm start point setting): Displayed only when control
(AC 0.1 ~ 38.0A) output (3) is used. Set when using power control element such as TPR.
HbS Setting value = Output current x 0.3 when the set value stays unchanged.
Heater current compensation
(CT tolerance compensation) ※ In case of heater break alarm, A1TY (Alam 1 type set) must be set to 21 to use.
(-10.0 ~ 10.0A)
④ H.[A](Heater current monitor): The AC current flowing in the current heater is
Heater current monitoring
accurately measured and displayed at 0.1 to 38.0 A. When "H.EXT" is turned ON,
HOLD function(ON/OFF)
the SV display window of the normal operation menu is displayed in real time.
Activation for current monitoring ⑤ H.Adj(Heater current compensation): Calibration is possible when using a
at Normal operation mode different ratio of CT than the current detector tolerance or 800: 1.
38 A
H.Adj correction value = x Measurement deviation
Measured value
< Normal operation menu >
For example, assuming a current of 10A is displayed at 9.8A,

38 A
H.Adj correction value = x 0.2 A =0.775 ≒ 0.8 A
9.8 A

⑥ H.HLd(Heater current hold): The output when the control output is used by
SSR (1) or Relay (3) is output in time division. At this time, it is very difficult to
read the instantaneous current value. Therefore, the last measured current
value can be temporarily held and the correct current value can be measured
ⓐ SV: Set value ⓑ SV: Heater current at any time.

When the external current monitoring


function is enabled, the heater current can be
checked from the normal operation menu in
real time, just like the current temperature.

Enables current monitoring for normal operation menu.

Enables control output for normal operation menu.


ⓑ control output (MVn) ⓒ Heater current
ⓐ Target
temperature

36
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

6) Alarm (Alarm1,2,3) group setting


The T50 series has three separate alarm outputs, and in the setting group,
alarms may be chosen among 21 types, and the dead band(Hysteresis) for the
alarm output may be set. Please find alarm code with the desired function in
the 'Alarm output type and Selection code' on the next page and use it to set
the alarm output in the settings mode.
display description setting range condition initial value

Enter to alarm setting group - Always -

Type of alarm 1 OFF / 1~21 Always 3

Type of alarm 2 Always OFF


OFF / 1~20
Type of alarm 3 Always OFF

When using
Hysteresis of alarm 1 1℃
Alarm 1

EUS (0.0~100.0%) When using


Hysteresis of alarm 2 1℃
Alarm 2

Hysteresis of alarm 3 When using 1℃


Alarm 3

When using OFF


Delay time of alam1
Alarm 1

OFF / 1~240 sec. When using OFF


Delay time of alam2
Alarm 2

When using OFF


Delay time of alam3
Alarm 3

When using EU(100.0%)


Value of alarm 1
Alarm 1
PV alarm,
Deviation alarm When using
Value of alarm 2 0℃
Alarm 2
EU (-100.0 ~ 100.0 %)
When using 0℃
Value of alarm 3
Alarm 3

Output port of alarm 1 When using AL 1


Alarm 1

Output port of alarm 2 When using AL2


AL1/ AL2/ AL3 Alarm 2

Output port of alarm 3 When using AL3


Alarm 3

The HBA will be generated through alarm output #1 (when A1TY = 21). This
37 means that HBA may be set only through alarm output #1.
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

(1) Alarm output type and Selection code


CODE NO. ALARM TYPE ALARM OUTPUT OPERATION

01 Absolute value upper-limit When temperature OFF ON


is falling
09 Process low When temperature OFF ON
is rising Hy s t e r e s i s

11 with hold function


OFF ON

19 with hold function (Inverted) Low High


Alarm setting value

02 Absolute value lower-limit When temperature ON OFF


is falling
10 Process low When temperature ON OFF
is rising Hy s t e r e s i s

12 with hold function ON OFF


Temperature
Low High
20 with hold function (Inverted) Alarm setting value

03 Upper-limit deviation <Negative temp. value setting> <Positive temp. value setting>
When tem-
perature is OFF ON OFF ON
05 Process low falling
When tem-
perature is OFF ON OFF ON
rising Hy s t e r e s i s Hy s t e r e s i s
13 with hold function
OFF ON OFF ON
Temperature
Low - High Low High
15 with hold function (Inverted) -Alarm SV SV Alarm
setting value

04 Lower-limit deviation
When tem-
<Negative temp. value setting> <Positive temp. value setting>
perature is ON OFF ON OFF
06 Process low falling
When tem- ON OFF ON OFF
perature is
rising Hy s t e r e s i s Hy s t e r e s i s
14 with hold function ON OFF ON OFF
Temperature
Low - High Low High
16 with hold function (Inverted) SV -Alarm Alarm SV

When temperature
Upper & Lower-limit is falling
ON OFF ON
07 deviation When temperature ON OFF ON
is rising
Hy s t e r e s i s

Upper & Lower-limit ON OFF ON


17 deviation with hold Temperature
Low High
Alarm SV Alarm

Upper & Lower-limit When temperature OFF ON OFF


08 deviation in range
is falling
When temperature OFF ON OFF
is rising Hy s t e r e s i s
Upper & Lower-limit ON
OFF OFF
18 deviation in range Temperature
Low High
with hold Alarm SV Alarm

Heater break alarm (HBA) Refer to HBA ! (ALARM1 only)


21
Control Loop break alarm LBA operation when heater break alarm(HBA) is not used (ALARM1 only)

Heater break alarm (Inverted, HBA) Refer to HBA ! (ALARM1 only)


22
Control Loop break alarm (Inverted) LBA operation when heater break alarm(HBA) is not used (ALARM1 only)

When alarm type reverse-correspondence is selected for alarm type and code, please be aware
■ Example 118 ℃
that whenof Alarm
the output
alarm lamp1 turns
settingon, the contact
118 output will beONoff.

■ Example of Alarm output 1 setting OFF
118 ℃
When Set Value (SV) = 100℃
■ Example of Alarm
Alarmtype
output 1 setting OFF ON 118℃
< example of Alarm output 1 setting > OFF When temperature120 ON℃
Alarm type deviation) = 03
(Upper-limit 120 ℃ OFF ON
Alarm type OFFis falling 120 ON℃
(Upper-limit deviation) = 03
(Upper-limit deviation) = 03 Hysteresis (2OFF
℃) ON 120℃
Hysteresis (Dead band) = 2 ℃ OFF
Hysteresis (2 ℃)When temperature
ON
Hysteresis (Dead band) = 2 ℃ OFF
Hysteresis (2 ℃)is rising
ON OFF ON
Hysteresis (Dead band) = 2 ℃ OFF ON
LowOFF ON High(2℃)
Hysteresis
Alarm setting value = 20 ℃ Low 100 ℃ 20 ℃ High ON
Alarm setting value = 20 ℃ Low 100 ℃ Temperature 20 ℃ High
OFF
( When 100 Set
℃ value 20 ℃ (SV)Low
= 100 ℃ )
Alarm setting value = 20 ℃
( When Set value (SV) = 100 ℃ )
100℃ 20℃
High 38
D I G I TA L P I D C O N T R O L L E R ( When Set value (SV) = 100 ℃ )
www.temcoline.com

(2) Hold function


When the low limit alarm is used, when the power is turned on and the
temperature rises, unnecessary low limit alarm occurs during the rise. When
the hold function is enabled, the low alarm can be ignored until the alarm set
value is released once the initial power is turned on.

PV PV
Low limit Low limit
alarm alarm

Hold function : None Hold function

Power ON Power ON (HOLD)

Alarm output ON OFF ON OFF Alarm output OFF OFF ON OFF

39
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

7) Re-transmission group setting


In the re-transmission output mode, process value (PV), set value (SV),
manipulated variable(MV) or sensor power supply (SPS) may be chosen, and the
output will be generated in direct current of 4~20mA. (SPS is DC15V/25mA)
display description setting range condition initial value

Enter to re-transmission
- Option -
setting group

Re-transmission type PV / SV / MV / SPS Option PV


or SPS selection

Upper limit of TC or RTD :


re-transmission EU(100.0%)
Fr-H ~ Fr-L
PV or SV
Voltage :
selection
Lower limit of SL-H ~ SL-L
re-transmission EU(0.0%)
(But, RET.H > RET.L)

PV(Process Value) / SV(Set Value) / MV(Manipulated Variable) / SPS(Power supply for external sensor)

Re-transmission value 4.0 mA 12.0 mA 20.0 mA

RET setting : PV or SV RET.L RET.H


MV (Fixed) 0.0 % 100.0 %
SPS (Fixed) DC Power Supply : DC 15V / 25mA

※ Method for correcting re-transmission output


When re-transmitting output (4 to 20 mA) is used, tolerance may occur due to the conversion resistance
and peripheral equipment error. When necessary, you can easily perform high-precision calibration as described
below.
① If the re-transmission output upper limit (RET.H) is set to 100.0 and the lower limit (RET.L) is set to 0.0.
② Change RET to SV transfer mode, change the SV as the current RET.H (100.0) value, check the transferred
value of the recorder or receiver (ex. 99.6) next note that the RET. L (0.0) value is also changed by transferring
the SV(ex. 0.3). (This must be the same as the setting on the receiving side input range.)
③ Change the transmitted value upper limit (RET.H) to 99.6, and change the transmission output lower limit
(RET.L) to 0.3.
④ When the re-transmission output mode (RET) is changed back to the PV re-transmission output mode,
the correction is completed.

40
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

8) Communication group setting


The communication system of the T50 series is based on RS-485, and is a two-
wire half- duplex type, capable of connecting to a maximum of 32 devices. In
particular, it is a totally independent isolation structure, which very safe and
reliable, and is compatible with most communication protocols used in the
market (PC-Link, TL-Link, Modbus-ASCII, Modbus-RTU, Sync-Master/Slave).
display description setting range condition initial value
Enter to communication
setting group - -

Protocol selection HSTD / HSUM / H-TL


(PC/TL-Link, Modbus-ASCII/ MODA / MODB H-TL
RTU, Sync-Master/Slave) SYNM / SYNS

2400 / 4800 / 9600 /


Baud rate selection (B.P.S) 9600 BPS
19200 [BPS]

Parity check selection NONE / EVEN / ODD NONE


Optional

Stop bit selection 1-bt(bit) / 2-bt(bit) 1-bt

Data Length selection 7-bt(bit) / 8-bt(bit) 8-bt

Address selection 7-bt(bit) / 8-bt(bit) 1

0 ~ 10 (Response time
Response time selection = Handling time + 1
Response time) x 10ms

The T50 series has a totally isolated input-output structure. A maximum of 32


devices may be connected to it, but this number may vary according to the site
and the line conditions.
(1) Communication protocols in detail
① HSTD / HSUM
PC-Link is used by some in Korea, developed by 2 corporations.
② H-TL (TL-Link)
This is Temcoline's own protocol. The multi-remote surveillance program,
which is included in the optional communications package for the T50 series,
uses this protocol.(For the reference, this program has advanced recording
functions)
③ MODA (Modbus-ASCII)
This ASCII-based protocol is commonly used in the industry, and is easy to use.
④ MODB (Modbus-RTU)
This binary-based protocol is the most widely used standard protocol in the
industry, and has a high speed.
⑤ Sync-Master/Slave
A system of Sync communication is configured with a master controller and
a number of slave controllers(up to 200 units). The slave controllers are set
to operate in the same way as the master controller, this time running information
(SV1, SV2, SV3, SV No.) is transmitting to slave controllers from master controller.
41
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

(2) Modbus protocol and T50 series


The Modbus communication protocol function code in the T50 series is comprised of a
function code that reads and writes D-REGISTER, and another that searches for Loop-
Back. For more information, please refer to the separately distributed Temcoline protocol, or
contact us by our website or our customer service center.
[ Modbus protocol support code ]
Code Description

03 D-REGISTER consecutive READ The device is capable of reading up to 32 consecutive D-Register contents.

06 Single D-REGISTER WRITE The D-Register contents can be edited one at a time.

16 D-REGISTER consecutive WRITE The device is capable of writing up to 25 consecutive D-Register contents.

The Modbus support device uses as address #400001~400999 in the 16-bit holding
register range, which includes 400001~465536.
When using a touchscreen for interface, the read/write addresses must be set at 400001
(D-Reg. 000) ~ 400700 (D-Reg. 699) for Pro-Face products.
For EasyView products, the device setting must be at 4x (16-bit), and the address at 001
(D-Reg. 000) ~ 700 (D-Reg. 699).
In Modbus communication, the address will be designated as the real
communication frame address +1. This is because the user may choose
addresses from #400001 onward. (Example: #400001 = D-Reg. 000)

(3) Modbus communication setting


① Modbus-ASCII
COM.P : MODA, BPS : 9600, PRTY : EVEN, STOP : 1-BT(bit), DTLN : 7-BT(bit)
② Modbus-RTU
COM.P : MODB, BPS : 9600, PRTY : EVEN, STOP : 1-BT(bit), DTLN : 8-BT(bit)

(4) Sync-Master/Slave Communication set

RS-485
RS-485 결선
connection
T54 x n
T54 x n 120Ω
T54 x n 120Ω

MASTER
MASTER Slave #01
Slave #01 Slave
Slave #n
#n
① Communication line wire
suggested to use twisted pair
Sync-Slave
Sync-Slave Sync-Slave
Sync-Slave
“SYnS”
"SYnS"설정setting
설정 “SYnS”
"SYnS"설정setting
설정 shield wire.
Sync-Master
② Termination resister must be
Sync-Master
"SYnM" setting
설정
“SYnM” 설정 SV
SV BIAS
BIAS값값
value SV
SV BIAS
BIAS값 값
value connected two pieces(120Ω
RBS==00
RBS RBS =
RBS = -15
-15 1/4W) only at both ends.

Master controller can be set only one and others should be set as Slave. In Sync
communication, no need to set Address and communication option. When set in Slave (Syns),
it works RBS menu.

42
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

READ ONLY READ/WRITE


(5) T50 D-REGISTER MAPPING PROHIBIT(READ ONLY) RESERVED
ADDRESS PROCESS CONTROL PROGRAM PID AUTO ALM & HBA RET/COM/RSP OUT & IN
Modbus Absolute 0 100 200 300 400 500 600
400 001 0 SVNO HBA1 RET OUT
400 002 1 N.PV SV1 H1DB RET.H O.ACT
400 003 2 N.SV ZONE SV2 HBS RET.L CT
400 004 3 N.SVNO FAST SV3 H.ADJ CTC
400 005 4 DP.I ARW H.HLD HYS
400 006 5 M.OUT AT.M H.EXT PO
400 007 6 H.OUT DIS AT HOC POC
400 008 7 C.OUT OL-H
400 009 8 PID.NO UP.RT OL-L
400 010 9 ALM.STS DN.RT
400 011 10 RTMU 1.P A1TY COM.P INP
400 012 11 RIFT 1.I A2TY BPS UNIT
400 013 12 1.D A3TY PRTY FR-H
400 014 13 1.MR A1DB STOP FR-L
400 015 14 HCM1 1.Pc A2DB DTLN DP-P
400 016 15 1.Ic A3DB ADDR SL-H
400 017 16 ADE.STS 1.Dc AL-1 RSPN SL-L
400 018 17 ERR.STS RST/(ALM) 1.DB AL-2 FILT
400 019 18 MOD.STS Run/Stop 1.RP AL-3 BIAS
400 020 19 Auto/Man. A1Pn B.OUT
400 021 20 M.MVn 2.P A2Pn
400 022 21 2.I A3Pn BS.P1
400 023 22 2.D A1DY BS.P2
Limit Controller
400 024 23 2.MR A2DY BS.P3
400 025 24 Hi.Lo 2.Pc A3DY BS0
400 026 25 RS.Md 2.Ic BS1
400 027 26 HoLd 2.Dc BS2
400 028 27 Peak Hold 2.DB BS3
400 029 28 Keep Time 2.RP BS4
400 030 29
※ Notes
400 031 30 HoPt(DAY) 3.P 1. Address: Absolute address is the address
400 032 31 HoPt(MINUTE) 3.I where actual data is stored. However, in the
case of Modbus, depending on the PLC and
400 033 32 3.D the panel manufacturer, the address may be
400 034 33 3.MR assigned by +1.

400 035 34 3.Pc 2. X00 002" (N.PV) in the Modbus Address


400 036 35 3.Ic format Upper "x00" is the PLC or touch I / O
address, and lower "002" is the real address.
400 037 36 3.Dc (Please check with related companies)
400 038 37 3.DB
3. T50 D-REG. The address is expressed in decimal
(DEC).It may be used in hexadecimal (HEX)
depending on PLC.
Example) 301 (SV1) → 0x12D(hexadecimal)
400 099 98

When using the communication options, please refer to the separately


provided T50 series communication protocol manual. Only the basics are
outlined here.
43
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

9) Output group setting


The T50 series is categorized into S (standard) and D (heating/cooling) types,and
has both multiple inputs and outputs. The user may select among relay,SSR, or
SCR (4~20mA, DC) for output.
display description setting range condition initial value

Enter to output setting group - - -

0(ON/OFF)/ 1(SSR)/
Device type of output1 2(SCR)/ 3(Relay) Always 1(SSR)
(Refer to p9, 2.2 )
REV (Reverse action)
Action type of control DIR (Direct action) Always REV
Dual (Heating & Cooling)

Device type of output2 1 (SSR) /2 (SCR) /3 (Relay) Heating &


(P9, 2. 2) refer to the 1(SSR)
(cooling) Output configuration) Cooling Model

1 ~ 1000 sec. SSR / RELAY


Cycle time 2 sec.
control

Heating &
Cycle time of cooling output 1 ~ 1000 sec. 2 sec.
Cooling Model

Heating & 1.0


Cooling gain 0.1 ~10.0
Cooling Model

Hysteresis EUS ON/ OFF 2℃


(ON/OFF control mode) (0.0 ~ 100.0%) control

Type of Hysteresis action ON/ OFF


Half / Normal NORM
(ON/OFF control mode) control

Output1 volume when


-0.5 ~ 105.0% Always 0.0%
input disconnected (OUT1)

Output2 volume when Heating &


input disconnected (OUT2) -0.0 ~ 105.0% 0.0%
Cooling Model

Upper limit of output OL-L ~ 105.0% PID control 100.0%

Lower limit of output -0.5% ~ OL-H PID control 0.0%

When PID control is set to Relay output code 3, the output cycle (Ct) is set to
20 seconds and the voltage pulse (SSR) output code is set to 1, the output
cycle (Ct) is automatically set to 2 seconds. When changing the setting, set it
separately.

44
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

(1) Setting output amount for the event that input has been cut off (Po)
If there is a problem with the input sensors or if for any reason the temperature controller does
not function properly, this safety function shuts off internally controlled output or maintains steady
output at a desired level.

(2) Output limitation in high/low (OL-H, OL-L)


Since the T50 series uses the S-PID algorithm, this function is not necessary in most
cases. This function may be used when special circumstances require limiting the
output. Using the default value (0~100.0%) is recommended.
OUTPUT

General-Purpose
usage range

Max. setting range


(-5.0~105.0%)

Output limit [%]

Low limit Hight limit


(OL-L) Setting (OL-H)
range

(3) Selection function for Hysteresis(ON/OFF control mode OUT=0)


(1) HYS.T = “NORM” selection
Hysteresis Hysteresis
ON ON

OFF OFF
_ACT = REV. SV SV
_ACT = DIR.
(heating operation) (Cooling operation)

(2) HYS.T = “HALF” selection


Hysteresis ※ While Hysteresis operation in "HALF" mode,
the operation of Heating and cooling is same,
ON
and "NORM" is factory default.

OFF
SV

45
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

10) Input group setting


The T50 series supports a wide range of specifications, including 12 types of
thermocouples (TC), 2 types of platinum resistance thermometers (RTD), and 3
types of current and voltage inputs.
display description setting range condition initial value

Enter to input setting group - - -

1 ~ 33
Type of Input sensor Always 1
(refer to P7, 2)

Temperature unit TC or
℃/℉ ℃
for the input RTD input

Input range of upper limit Always 1370


Within input range
(refer to next page)
Input range of lower limit but, Fr-H > Fr-L -200
Always

Position of decimal point 0/1/2/3 Voltage input mode


(Voltage input mode) 1
(On voltage input) (mV, V)

Scale of upper limit


-1999 ~ 9999 100.0
(Voltage input mode)
But , SL-H > SL-L Voltage input mode
Decimal point (mV, V)
Scale of lower limit 0.0
positioning by DP-P
(Voltage input mode)

Input digital filter OFF / 1~120 sec. Always OFF

Input value compensation EUS (0.0%)


at the lower limit EUS (-100.0~100.0 %) Always

Input value compensation


at upper limit only voltage Voltage input mode EUS (0.0%)
EUS (-100.0~100.0 %)
input (mV, V)

Direction of input value UP


OFF / UP / DOWN Always
during input burn-out

When the input type is changed, all parameters are reverted to their factory
default. This means that before using the T50, the input type needs to be set
first, after which other parameters can be configured. If the input settings
are changed while in use, auto-tuning and other parameters need to be
reconfigured.

46
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

(1) Input type selection


This is the first thing that needs to be checked and set before using the T50,
as the settings here will cause other parameters to be reset to their typically
optimal values for that specific type.
(2) Input unit selection (℃ / ℉)
This selects the unit of temperature measurement to be displayed when using
temperature sensors. The Celsius degree is set as the default, but it may be
changed to the Fahrenheit degree. On products sold in Korea, the units are
fixed to the Celsius degree in compliance with the regulations.
(3) Setting decimal point position (DP-P), and free scale high and low limits (SL-H, SL-L)
This applies only when using voltage inputs (DC V, mV) or currents between
4 to 20mA (1~5V). The user may set ranges, units and decimal point position
as desired. This can be used not only for temperatures but also for a number
of other measurements, including humidity, pressure, and weight.
(4) Digital input filter (FILT)
This function is useful when suboptimal environments cause noises or severe
fluctuations, enabling a digital software filter. The filter's sensitivity may be set
from off to 1~120 seconds. Please be careful when using this function, as it
may affect the control-related algorithms.
(5) Input value bias (BIAS)
This function allows the input values to be compensated. This function is
useful, for example, when sensors can not be placed at desired locations, or
when several different thermometers are used in conjunction. The values may
be compensated to extent desired by the user.

(6) Compensation upper limit of input value(GAIN)


It is used only in the voltage input (current 4 to 20 mA) mode, and can
accurately correct the indication deviation due to the output tolerance of the
sensor modulus and the tolerance of the conversion resistance (250Ω). It is used
with BIAS, BIAS adjusts the offset and GAIN adjusts the slope. For example,
when using the current (4 ~ 20mA) input, the tolerance is corrected by BIAS
when the minimum value (4mA) is input and the tolerance is compensated by
GAIN when the maximum value (20mA) is input.
※ For reference,
[ 4~20mA INPUT ] GAIN compensation BIAS
(Maximum) 20.0 before compensation
GAIN must be done first.
16.0 The T50 series also offers
a powerful compensation
12.0
function that allows
8.0 accurate measurement
even without using a
(Minimum) 4.0 high-precision (± 0.1%)
class with a 4 to 20 mA
BIAS 0 50.0 100.0 conversion resistance
(SL-L) Free Scale Area (SL-H) (250Ω).
47
D I G I TA L P I D C O N T R O L L E R
www.temcoline.com

11) Error indication during operation


(1) B.OUT : INPUT SENSOR error or burn out etc.
(2) +OVR : Out of maximum input range (refer to input group setting) or overheating
(3) -OVR : Out of minimum input range (refer to input group setting) or overcooling
(4) SYS.E : SYSTEM setting error or Memory damage (request for repair)
(5) RJC.E : RJC Sensor damage or PCB burn (request for repair)
(6) EEP.E : EEPROM damage (request for repair)
(7) COM.E : Communication ERROR (request for repair)
(8) AT.E : Auto Tuning Error, Checking heater break or controller

48