Chiller
Chiller
Chiller
WATER-COOLED CHILLER
1 General
1.0 Related Documents:
a. This section of the specifications is subject to the provisions of Division 1, Division 23 in
general and specifically, Section 15670 - General Mechanical Requirements. Work de-
scribed in this section shall comprise an integral part of the work of Division 23 and shall
be referenced by all mechanical trades for purposes of coordination so that a complete
mechanical installation will result without additional cost to the Owner.
a. Unit shall be delivered to job site (Clark Freeport Zone, Mabalacat Pampanga) fully as-
sembled, and charged with refrigerant and oil by the Manufacturer.
b. Unit shall be stored and handled at the site per Manufacturer’s instructions, at the factory,
in transit and at the installation site by the installing contractor
c. Installing contractor shall comply with manufacturer's rigging and installation instructions for un-
loading the unit and moving it to the final location.
1.4 SUBMITTALS
a. Provide factory trained and manufacturer authorized service agent(s) to place units in full
operation.
b. Provide mechanical and electrical support personnel to assist with chiller start-up in provi-
sion of the piping, electrical and related aspects.
2 PRODUCTS
2.0 WATER COOLED CHILLER:
2.0.1 Manufacturer
2.1.1 General:
a. Install and commission, as shown on the schedules and plans, factory assembled,
charged, and tested air-cooled scroll compressor chiller(s) as specified herein. Chiller
shall be designed, selected, and constructed using a refrigerant with Flammability rating of
“1”, as defined by ANSI/ASHRAE STANDARD - 34 Number Designation and Safety Clas-
sification of Refrigerants. Chiller shall include, but is not limited to a complete system with
not less than two refrigerant circuits above 35 tons (123kW), centrifugal compressors, dir-
ect expansion type evaporator, water-cooled heat rejection (cooling tower), refrigerant,
lubrication system, interconnecting wiring, safety and operating controls including capacity
controller, control center, motor starting components, marine box access, ball condenser
access and special features as specified herein or required for safe, automatic operation.
b. Cabinet: External structural members shall be constructed of heavy gauge, galvanized
steel coated with baked on powder paint which, when subject to ASTM B117, 1000 hour,
5% salt spray test, yields minimum ASTM 1654 rating of “6”. Add Wire Panels of heavy
gauge, welded wire-mesh, coated to resist corrosion, to protect condenser coils from in-
cidental damage and restrict unauthorized access to internal components. Factory in-
stalled.
2.1.2 Energy Efficiency Rating (EER)
2.1.3 COMPRESSORS
a. Each refrigerant circuit shall include liquid line shutoff valve with charging port, low side
pressure relief device, filter-drier, solenoid valve, sight glass with moisture indicator, ex-
pansion valves, and flexible, closed-cell foam insulated suction line. Include service isola-
tion valves as a minimum standard.
b. Provide unit with 304 or 316 stainless steel tubing as common tubing material. HEAT EX-
CHANGERS
2.1.5 Refrigerant
2.1.6 Evaporator:
a. One for each refrigeration circuit, either Brazed Plate or Shell and Tube construction.
a. Evaporator shall be brazed-plate stainless steel construction, single or dual circuit heat ex-
changers capable of refrigerant working pressure of 650 psig (3103 kPa) and liquid side
pressure of 150 psig (1034 kPa) Evaporator shall be covered in 1-1/2” (19mm) flexible,
closed cell insulation, thermal conductivity of 0.26k (BTU/HR-FT2-°F]/in.) Maximum.
Brazed plate heat exchangers shall have exposed brazing edges coated with a corrosion
resistant coating at the factory and shall be UL listed.
Or
a . Coils:
– Internally enhanced, seamless stainless-steel tubes mechanically expanded into alu-
minium alloy fins with full height collars. Sub-cooling coil shall be an integral part of con-
denser. Design working pressure shall be 650 PSIG (45 bar gauge).
– Vendor may offer an alternate price for a unit with aluminium tubes to compare with the
stainless-steel tube price.
b . Low Noise Fans:
– Shall be dynamically and statically balanced, direct drive, propeller type fan, providing ver-
tical air discharge and low sound characteristics. Each fan shall sit in its own compartment
to prevent cross flow during fan cycling. Fan guards of heavy gauge coated or galvanized
steel. Fan Blades shall be of heavy gauge or cast aluminium.
c. Fan Motors:
– Provide high efficiency, direct drive, 3 pole, (1150 rpm +/-) 3 phase, insulation class “F”,
current protected, Totally Enclosed Air-Over/Fan Cooled (TEFC), rigid mounted, with
double sealed, permanently lubricated, ball bearings.
2.1.9 CONTROLS
a. General:
– Provide functions for automatic start, stop, operating, and protection sequences across
the range of scheduled conditions and transients. All controls, including sensors, shall be
factory mounted and tested prior to shipment. Units shall be UL listed.
b. Microprocessor Enclosure:
– NEMA 4X powder painted steel cabinet with a gasket sealed protective cover.
c. Microprocessor Control Center:
– Local independent control or a remote “Run/Stop” signal from the BacNet System. Provide
for subsequent automatic control of compressor start/stop, anti- coincidence and anti-re-
cycle timers, automatic pump-down on shutdown, condenser fan staging, evaporator
pump, evaporator heater, unit alarm contacts, and chiller operation from 0°F to 125°F (-
18°C to 52°C) ambient. Automatic reset to normal chiller operation after power failure.
– Provide for digital communications to BacNet system via MODBUS TCP. Software stored
in non-volatile memory, with programmed setpoints retained in lithium battery backed real
time clock (RTC) memory for minimum 5 years.
– Forty-character liquid crystal display, descriptions in English, numeric data in English (or
Metric) units. Sealed keypad with sections for Set points, Display/Print, Entry, Unit Op-
tions & Clock, and On/Off Switch.
– Programmable Setpoints (within Manufacturer limits): display language; chilled liquid tem-
perature setpoint and range, remote reset temperature range, set daily schedule/holiday
for start/ stop, manual override for servicing, low and high AMBIENT Cut outs, number of
compressors, low liquid temperature cut-out, low suction pressure cut-out, high discharge
pressure cut-out, anti-recycle timer (compressor start cycle time), and anti-coincident timer
(delay compressor starts).
d . Display Data:
– Return and leaving liquid temperatures low leaving liquid temperature cut out setting, low
ambient temperature cut-out setting, outdoor air temperature, metric data, suction pres-
sure cut-out setting. Each system suction pressure, discharge pressure, liquid temperat-
ure reset, anti-recycle timer status for each compressor. Anti-coincident system starts
timer condition, compressor run status, no cooling load condition, day, date and time, daily
start/ stop times, holiday status, automatic or manual system lead/lag control. Lead sys-
tem definition, compressor starts/operating hours (each), status of hot gas valves, evapor-
ator heater and fan operation, run permissive status, number of compressors running, li-
quid solenoid valve status, load & unload timer status, water pump status.
e . System Safeties:
– Shall cause individual compressor systems to perform auto shut down; manual reset re-
quired after the third trip in 90 minutes. Includes: high discharge pressure, low suction
pressure, high-pressure switch, and motor protector. Compressor motor protector shall
protect against damage due to high input current or thermal overload of windings.
f . Unit Safeties:
– Shall be automatic reset and cause compressors to shut down if low ambient, low leaving
chilled liquid temperature, under voltage, and flow switch operation. Contractor shall
provide flow switch and wiring per chiller manufacturer requirements.
g . Alarm Contacts:
– Low ambient, low leaving chilled liquid temperature, low voltage, low battery, and (per
compressor circuit): high discharge pressure, and low suction pressure.
h. Analog Signals:
4-20ma chilled water supply and return temperatures. Discrete Signals:
24VDC or 120VAC run status, local LOR switch status.
2.1.10 Manufacturer
a. Approved Manufacturer: Shall provide any controls not listed above, necessary for auto-
matic chiller operation. Contractor shall provide field control wiring necessary to interface
chiller control system with BacNet system.
– Euroklimat (Contact Ms Erika Jael Rivo – 0999 977 0088)
– Dunham Bush (Contact Mr. Robert Guido 0918 9078 961)
– Carrier
– Or approved equal
a. Power Panels:
– NEMA 3R, powder painted steel cabinets with a gasketed protective cover. Provide main
power connection(s), control power connections, compressor and fan motor start contact-
ors, current overloads, and factory wiring.
– Installing contractor must include accommodations in the chilled water piping to allow
proper drainage and venting of the heat exchanger. A strainer with a mesh size between
0.5 and 1.5mm (40 mesh) is required upstream of the heat exchanger to prevent clogging.
– Compressor, control and an motor power wiring shall be fully contained within the unit en-
closure, or shall be routed through liquid tight conduit.
a. Alternative to an above-mentioned flow switch. 300 psi max. Working pressure SPDT 5
amp 125/250VAC switch, Range 3-45 PSIG (0.2-3 bar gauge), dead band 0.5 - 0.8 psi,
with 1/4” NPTE Pressure Connections.
a. Provide service suction and discharge (ball type) isolation valves per system. Include a
factory mounted system high-pressure relief valve in compliance with ASHRAE 15.
a. Include this feature to support continuous, stable operation at capacities below the min-
imum step of unloading to as low as 5% capacity (depending on both the unit & operating
conditions) by introducing an artificial load on the cooler. Install hot gas by-pass on both
refrigerant circuits.
a. Provide unit with “Ultra quiet,” low speed, reduced noise fans.
b. Provide compressor acoustic sound blankets.
a. Neoprene Pad Isolators. Raise the unit above direct contact with the concrete pad and let
the isolators serve to accept any unevenness of the pad.
3 PART 3 - EXECUTION
3.0 INSTALLATION
3.0.1 General:
a. Rig and install in full accordance with Manufacturer’s requirements, Project Drawings, and
Contract Documents.
3.0.2 Location:
a. Locate chiller as indicated on drawings, including cleaning and service maintenance clear-
ance per Manufacturer instructions. Adjust and level chiller on support structure. If equip-
ment provided exceeds height of scheduled chiller, installing contractor is responsible for
any additional costs associated with extending the height of parapet or screening walls/en-
closures
3.0.3 Components:
a. Installing Contractor shall provide and install all auxiliary devices and accessories for fully
operational chiller.
3.0.4 Electrical:
a. Coordinate electrical requirements and connections for all power feeds with Electrical
Contractor (Division 16) and Owner’s maintenance electrician.
3.0.5 Controls:
3.0.6 Finish:
a. Installing Contractor shall paint damaged and abraded factory finish with touch-up paint
matching factory finish.
a. Provide a complete Start up and Commissioning service for the machine as part of the
Purchase Contract for the machine.
- END OF SECTION -
23 62 13
DIVISION 23 - SECTION 23 82 19
FAN COIL UNITS
1 General
1.0.1 Summary
a. Section includes:
– Materials and installation for fan coil units.
1.0.3 References
a. Health Canada / Workplace Hazardous Materials Information System (WHMIS)]
b. Safety Data Sheets (SDS)
c. American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE)
d. ASHRAE 79 – Method of Testing for Rating Fan-Coil Conditioners.
2 Submittals
2.0.1 Product Data:
a. Submit manufacturer's printed product literature, specifications and datasheet in accordance with
Section 01 33 00 - Submittal Procedures. Include product characteristics, performance criteria, and
limitations.
– Submit two copies of Workplace Hazardous Materials Information System (WHMIS) Safety Data
Sheets (SDS) in accordance with Section 01 33 00 - Submittal Procedures.
b. Product data to include:
– Filters, fan accessibility.
– Suspension, anchoring of cabinet.
– Physical size.
– Thermostat, transformer, controls where integral.
– Finish.
– kW rating, voltage, phase.
– Cabinet material thicknesses.
4 Execution
4.0.1 MANUFACTURER’S INSTRUCTIONS
a. Compliance:
– Comply with manufacturer's written recommendations or specifications, including product
technical bulletins, handling, storage and installation instructions, and datasheet.
4.0.2 Pre-Installation
a. The unit needs to be handled with care during transportation and it is prohibited to move the
unit by holding on to the blower or blower blade.
b. The unit is designed to take its own weight. As such, do not transfer the load of duct, water
pipes and other accessories to the unit. This may cause the hanger to deform and fail.
c. Before any installation work starts, the following should be checked:
– Chilled water pipes and condensate water drainage pipes must be properly connected and
standby for use.
– Electrical wiring is properly connected and all terminals are tightened to prevent loose
wires.
– Sufficient space must be reserved for installation, service and maintenance purposes.
– Ensure the hanging rod is capable of supporting the weight of the unit and the position of
rods are according to drawing.
– Ensure the supply and return duct installed (for units that required ducting) is according to
the specification of the unit
4.0.7 COMMISSIONING
a. Perform tests in accordance with Section 26 05 00 – Common Work Results - Electrical.
b. Section 01 91 13.13 – Commissioning (Cx) Requirements.
4.0.8 CLEANING
a. Proceed in accordance with Section 01 74 00 - Cleaning.
b. Upon completion and verification of performance of installation, remove surplus materials, ex-
cess materials, rubbish, tools and equipment.
END OF SECTION
DIVISION 23 - SECTION 23 73 00 16
AIR HANDLING UNITS
1 General
1.0 RELATED SECTIONS
a. Section 01 33 00 – Submittal Procedures.
b. Section 01 74 21 – Construction/Demolition Waste Management and Disposal.
c. Section 01 78 00 – Closeout Submittals.
d. Section 23 05 48 – Vibration and Seismic Controls for HVAC Piping and Equipment.
e. Section 23 33 00 – Air Duct Accessories.
f. Section 23 33 15 – Dampers - Operating.
g. Section 23 40 00 – HVAC Air Cleaning Devices.
h. Section 23 72 00 – Air-to-Air Energy Recovery Equipment.
i. Section 23 84 13 – Humidifiers.
1.1 REFERENCES
a. American National Standards Institute/Air-Conditioning and Refrigeration Institute (ANSI/ARI)
– ANSI/ARI 430, Central Station Air Handling Units.
b. Canadian General Standards Board (CGSB)
– CAN/CGSB 1.181, Ready-Mixed Organic Zinc-Rich Coating.
c. Canadian Standards Association (CSA)
– CSA B52, Mechanical Refrigeration Code.
d. Sheet Metal and Air-Conditioning Contractors' National Association (SMACNA).
e. American Bearing Manufacturer’s Association (ABMA)
– ANSI/ABMA 9 Load Ratings and Fatique Life for Ball Bearings
– ANSI/ABMA 11 Load Ratings and Fatique Life for Roller Bearings.
f. Air Movement and Control Association (AMCA)
– AMCA 210, Laboratory Method of Testing Fans for Aerodynamic Performance Rating
(ASHRAE)
– AMCA 300 Reverberaut Room Method for Sound Testing of Fans.
g. American Society of Heating Refrigeration and Air-Conditioning Engineers (ASHRAE).
– ASHRAE 68, Laboratory Method of Testing to Determine the Sound Power in a Duct.
– ANSI/ASHRAE 90.1, (I-P) Energy Standard for Buildings Except Low-Rise Residential Build-
ings.
– ANSI/ASHRAE 52.2, Method of Testing General Ventilation Air-Cleaning Devices for Removal
Efficiency by Particle Size.
h. National Electrical Manufacturer’s Association (NEMA)
– NEMA MG1 Motors and Generators
– NEMA ICS 7-1 Safety Standards for Construction and Guide for Selection, Installation and Op-
eration of Adjustable Speed Drive Systems.
2 PRODUCTS
2.0 GENERAL
a. Factory assembled components to form units supplying air at designed conditions, as indicated.
b. Certify ratings: to ARI 430 with ARI seal.
c. Horizontal and vertical type, as indicated, having air tight modular components, consisting of cas-
ing, fan section with motor and drive, filter section, dampers, bypass section, heating coil, cooling
coil, humidifier, spray section, mixing box, blender air mixing device or filter mixing box.
2.1 Manufacturer
a. Approved Manufacturers: Subject to compliance with requirements, provide products by the fol-
lowing:
– Niagara Fans, (Contact Mr Jason Tan 09178954353, [email protected], Owner;
– System Air by Lincon Manufacturing Phils Inc. (Contact Ms Luzlyn Bermido 09178299424);
– Euroklimat (Contact: Ms Erika Jael Rivo 09999770088)
– TICA by DB International (Contact Mr Robert Guido 09189078961)
– Or approved equal
2.2 CASINGS
a. Galvanized or phosphate treated steel 1.6 mm thickness outer casing reinforced and braced for ri-
gidity.
b. Walk-in access doors: provide access for maintenance of internal parts with wired glass 200 x 200
mm viewing port or 200mm diameter polycarbonate double porthole.
c. Paint steel parts, where not galvanized, with corrosion resistant paint to CGSB 1.181.
d. Finish structural framed units, inside and out, with rust resistant enamel to Section 09 91 13 – Ex-
terior Painting.
e. Line entire casing with minimum 1 mm thick, solid galvanized, steel liner.
2.4 FANS
a. For centrifugal fans refer to Section 23 34 16
b. Cabinet hung or frame mounted AMCA-rated for sound and performance, centrifugal fans with
backward inclined or air foil wheels, selected to operate in stable part of performance curve and
heavy duty L10 100,000 hours minimum service self-aligning or split pillow block bearings.
c. Provide internally mounted motor as indicated complete with adjustable V-belt drive and guard.
d. Motor: see schedule.
e. Maximum sound power levels, as indicated.
2.9.1 General:
a. Pre-engineered device with no moving parts, designed to thoroughly mix warm and cold air
streams, to within 3° C at 40 Pa pressure drop and to provide for even velocity distribution profile.
b. Sizing criteria:
– Type: static.
– Size: to suit unit mixing box at mixer area to plenum area of 0.4, and minimum flow rate to max -
imum flow rate of 0.4 plenum, velocity 2.5 m/s
– Pressure drop:40 Pa.
– Capacity:
Outside air: as indicated.
Return air: as indicated.
– Mixed air temperature: 12° C at outside air to supply air ratio of 0.25.
c. Construction:
– 2 mm thick aluminium or 1.6 mm thick stainless steel.
d. Blender section:
– Blender in housing ready for insertion into air handling unit.
– 50 mm flanges on inlet and outlet.
– Complete with 25 mm, 32 kg/m3 density, fibreglass lining and insulated access door.
e. Blender mixing box:
– General: single unit consisting of dampers, blender, mixing section, with provision for floor
mounting.
– Construction: stainless steel duct connection flanges, reinforced for rigidity, finished with corro-
sion resistant paint or zinc coating.
– Dampers: parallel blade, low leakage, proportioning type.
Leakage: not more than 50 l/s.m2 at 750 Pa.
Seals: Neoprene on damper edges, top, bottom, sides of framing.
– Blades of 1.6 mm thick steel, 150 mm maximum wide, locked to steel rods in rustproof bush-
ings.
2.10 COILS
a. Capacity: see schedule.
b. Ratings: ARI certified.
c. Construction:
– Casings: 1.5 mm thick galvanized sheet steel.
d. Supports of galvanized steel channel or double angle frames.
– Blank-off plates. Insulated sandwich construction.
e. Non-freeze steam coils: tube-in-tube type with internal perforated steam distributing tubes. Slope
tubes to drain condensate.
– Tubes: copper, brass or steel.
– Fins: aluminum.
– Headers: cast iron, steel or cast brass.
– Pressure tests: 1.7 MPa.
f. Steam coils: single tube type.
– Tubes: copper, brass or steel.
– Fins: aluminium.
– Headers: cast iron, steel or cast brass.
– Pressure tests: 1.7 MPa.
g. Hot and Chilled water coils: cleanable fins.
– Tubes: copper, brass or steel.
– Fins: aluminium plate or spiral wound.
– Headers: cast iron, steel or cast brass.
– Pressure tests: 1.7 MPa.
– Direct expansion refrigerant coils:
h. Serpentine type, arranged to prevent trapping of oil.
– Liquid distributors to ensure even distribution of liquid refrigerant to all circuits.
– Silver solder or braze joints in refrigerant tubing.
– Evacuate and charge coil with nitrogen and seal before sending to site.
i. Tubes: copper.
j. Fins: aluminium, plate or spiral wound.
k. Headers: copper.
l. Pressure tests: CSA B52 and carry a Canadian Refrigeration Number. Dehydrated. Sealed with ni-
trogen charge.
2.11 HUMIDIFIERS
a. To Section 23 84 13 - Humidifiers.
3 EXECUTION
3.0 INSTALLATION
a. Install units in accordance with manufacturer's instructions and as indicated.
b. Ensure adequate clearance for servicing and maintenance.
3.1 FANS
a. Install fan sheaves required for final air balance.
b. Install flexible connections at fan inlet and fan outlets.
c. Install vibration isolators.
3.3 COMMISSIONING
a. Commission in accordance with Section 01 91 13.13 – Commissioning (Cx) Requirements one day
per unit for start-up and one day for commissioning.
END OF SECTION