Chiller

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 19

DIVISION – SECTION 23 62 13

WATER-COOLED CHILLER

1 General
1.0 Related Documents:
a. This section of the specifications is subject to the provisions of Division 1, Division 23 in
general and specifically, Section 15670 - General Mechanical Requirements. Work de-
scribed in this section shall comprise an integral part of the work of Division 23 and shall
be referenced by all mechanical trades for purposes of coordination so that a complete
mechanical installation will result without additional cost to the Owner.

1.1 SCOPE OF THE WORK:


a. “Provide,” meaning “Furnish and Install,” as described in these specifications and as
shown on the drawings, a complete replacement air cooled chiller system.
b. New Chiller: Provide Microprocessor controlled, multiple-scroll compressor, water-cooled,
liquid chillers of the scheduled capacities as shown and indicated on the Drawings, includ-
ing but not limited to:
– Chiller package
– Electrical power and control connections
– Chilled water connections
– Charge of refrigerant and oil installed at the factory for factory mounted evaporator, or provided
on site if the evaporator is shipped separately for field installation and piping by contractor).
c. This installation, sized for 5 no. (4 duty and 1 stand by lead/lag operation) of 625 tons
cooling each, requires a dual circuited unit configuration with control to effect a seamless
operation of the overall unit, but with either circuit able to run independently of the other as
in the case of the loss of one circuit compressor or its related evaporator, including
devices and controls. Owner will consider, and invites, presentation of two separate 625
ton units, the pair to be provided with controls to make the function equivalent to a
“twinned” pair capable of “either one, or both” operation. This is thought to be equivalent
to the dual compressor, independent circuit function of a single machine.

1.2 QUALITY ASSURANCE


a. Manufacturer's Qualifications:
– A manufacturer of the packaged system for environment control with a minimum
of five years of experience in the production of these systems. Manufacturer shall
have a permanent, local (Clark Free Port Zone, +/- 150 kms) sales representation and a
local maintenance and repair facility (fixed base, with skilled factory trained technicians)
capable of 4 hour, day or night, response to a trouble call.
b. Installer’s Qualifications:
– A firm with at least 7 years of successful installation experience and not less than 7 similar in-
stallations on projects with chilled water installations similar to that required for this project
c. Codes and Standards:
Products shall be Designed, Tested, Rated and Certified in accordance with, and installed in compliance with
applicable sections of the following Standards and Codes:

– ANSI/ASHRAE Standard 15 – Safety Code for Mechanical Refrigeration


– ASHRAE 90.1– Energy Efficiency compliance.
– ANSI/NFPA Standard 70 – National Electrical Code (N.E.C.).
– ASME Boiler & Pressure Vessel Code, Section VIII, Division 1.
– ARI Standard 550/590 and 551/591 – Air Cooled Water-Chilling Packages.
– Conform to Intertek Testing Services, formerly ETL, for construction of chillers and provide
ETL/CETL Listing label.
– Manufactured in facility registered to ISO9002.
– OSHA - Occupational Safety and Health Act
d. Factory Test: Chiller shall be pressure-tested, evacuated and fully charged with refrigerant
and oil, and shall be factory operational run tested with water flowing through the vessel.
e. Guaranty/Warranty
– Manufacturer shall Warrant all equipment and material of its manufacture against de-
fects in workmanship and material for a period of five year from date of initial start-up or
eighteen (18) months from date of shipment, whichever occurs first. Warranty to in-
clude all involved and required “parts and labor”. Parts shall be genuine factory parts
equivalent to the original. Labor shall be provided by a factory trained and manufac-
turer authorized service agency. Parts replaced during the warranty period shall be
warranted in and of themselves for a full year from the date of any required replace-
ment/repair
The installing Contractor shall provide full warranty of the chiller installation and related
for one year from the date of proven (function conveyed to Owner with reliable
operation assured) beneficial use by Owner.

1.3 DELIVERY AND HANDLING

a. Unit shall be delivered to job site (Clark Freeport Zone, Mabalacat Pampanga) fully as-
sembled, and charged with refrigerant and oil by the Manufacturer.
b. Unit shall be stored and handled at the site per Manufacturer’s instructions, at the factory,
in transit and at the installation site by the installing contractor
c. Installing contractor shall comply with manufacturer's rigging and installation instructions for un-
loading the unit and moving it to the final location.

1.4 SUBMITTALS

a. Product Data: (Manufacturer)


– Submit overall dimension drawings, factory and field wiring diagrams, and product data
including glycol solution flow, pressure drops, total power consumption, water entering
and leaving temperature conditions under all operating modes.
– Basis of unit selection and performance with supporting documentation shall be fur-
nished with bid. Guaranteed maximum annual operating cost based on scheduled am-
bient temperature patterns shall be supplied with the bid.
b. Record Drawings:
c. Maintenance Data: (Manufacturer)
– Provide electrical wiring diagrams, installation and maintenance instructions and an
Owner's Operating and Maintenance manual with each unit.

1.5 INSTRUCTION OF OWNER'S PERSONNEL: (Chiller manufacturer and installing


Contractor Scope)

a. Provide factory trained and manufacturer authorized service agent(s) to place units in full
operation.
b. Provide mechanical and electrical support personnel to assist with chiller start-up in provi-
sion of the piping, electrical and related aspects.

2 PRODUCTS
2.0 WATER COOLED CHILLER:

2.0.1 Manufacturer

a. Acceptable Manufacturers: Subject to compliance with requirements, provide an air-


cooled chiller of one of the following:
– Euroklimat (Contact Ms Erika Jael Rivo – 09999770088)
– Dunham Bush (Contact Mr. Robert Guido 09189078961)
– Carrier Corp.
– Sinko
– Or approved equal

2.1 CHILLER MATERIALS AND COMPONENTS

2.1.1 General:

a. Install and commission, as shown on the schedules and plans, factory assembled,
charged, and tested air-cooled scroll compressor chiller(s) as specified herein. Chiller
shall be designed, selected, and constructed using a refrigerant with Flammability rating of
“1”, as defined by ANSI/ASHRAE STANDARD - 34 Number Designation and Safety Clas-
sification of Refrigerants. Chiller shall include, but is not limited to a complete system with
not less than two refrigerant circuits above 35 tons (123kW), centrifugal compressors, dir-
ect expansion type evaporator, water-cooled heat rejection (cooling tower), refrigerant,
lubrication system, interconnecting wiring, safety and operating controls including capacity
controller, control center, motor starting components, marine box access, ball condenser
access and special features as specified herein or required for safe, automatic operation.
b. Cabinet: External structural members shall be constructed of heavy gauge, galvanized
steel coated with baked on powder paint which, when subject to ASTM B117, 1000 hour,
5% salt spray test, yields minimum ASTM 1654 rating of “6”. Add Wire Panels of heavy
gauge, welded wire-mesh, coated to resist corrosion, to protect condenser coils from in-
cidental damage and restrict unauthorized access to internal components. Factory in-
stalled.
2.1.2 Energy Efficiency Rating (EER)

a. Integrated Part Load Value (IPLV): 16-18.

2.1.3 COMPRESSORS

a. Compressors: Shall be by Copeland, of the hermetic, centrifugal-type, including:


– Compliant design with axial and radial sealing.
– Refrigerant flow through the compressor with 100% suction gas cooled motor. Motors
shall be two-pole (3600 rpm,) squirrel-cage induction type, with capacity control slide
valve, rolling element bearings, and differential refrigerant pressure oil pump.
– Demonstrably adequate suction side liquid separation chamber and oil sump to provide
refrigerant and oil handling capability.
– Microprocessor controlled compressor crankcase heaters to provide/prevent liquid mi-
gration.
– Annular discharge check valve and reverse vent assembly to provide low-pressure
drop, silent shutdown and reverse rotation protection.
– In-line filter drier with moisture indication device.
– Oil Level sight-glass.
– High side/Low side fittings with gasket caps for introduction of refrigerant and monitor-
ing of pressures.
– Brazed-type connections for fully hermetic refrigerant circuits.
– Provide initial refrigerant and oil charge and any refrigerant and/or oil required during
the period of the warranty.
– Vibration isolator mounts for compressors.

2.1.4 REFRIGERANT CIRCUIT COMPONENTS

a. Each refrigerant circuit shall include liquid line shutoff valve with charging port, low side
pressure relief device, filter-drier, solenoid valve, sight glass with moisture indicator, ex-
pansion valves, and flexible, closed-cell foam insulated suction line. Include service isola-
tion valves as a minimum standard.
b. Provide unit with 304 or 316 stainless steel tubing as common tubing material. HEAT EX-
CHANGERS

2.1.5 Refrigerant

a. Do not use chlorofluorocarbon (CFC)-based refrigerants.


b. Use R 410a, 134a or R- 513 a

2.1.6 Evaporator:

a. One for each refrigeration circuit, either Brazed Plate or Shell and Tube construction.

2.1.7 Brazed Plate:

a. Evaporator shall be brazed-plate stainless steel construction, single or dual circuit heat ex-
changers capable of refrigerant working pressure of 650 psig (3103 kPa) and liquid side
pressure of 150 psig (1034 kPa) Evaporator shall be covered in 1-1/2” (19mm) flexible,
closed cell insulation, thermal conductivity of 0.26k (BTU/HR-FT2-°F]/in.) Maximum.
Brazed plate heat exchangers shall have exposed brazing edges coated with a corrosion
resistant coating at the factory and shall be UL listed.
Or

b. Shell and Tube:


– The evaporator shall be a tube-in-shell heat exchanger design with internally finned
0.035 copper tubes roller expanded into the tube sheet. The evaporator design shall be
tested and stamped in accordance with ASME for a refrigerant side with working pres-
sure of 450 psig. The evaporator shall be designed for a water-side working pressure
of 150 psig.
– Water connections shall have one water pass with a series of internal baffles. Each
shell to have a vent, a drain and fittings for temperature control sensors and insulated
with 50 mm Kflex or equal insulation (K = 0.26).
– Installing contractor must include accommodations in the chilled water piping to allow
proper drainage and venting of the heat exchanger. A strainer with a mesh size between
0.5 and 1.5mm (40 mesh) is required upstream of the heat exchanger to prevent clogging.
– Either type of cooler shall have thermostatically controlled heaters to protect to -20°F
(29°C) ambient in off-cycle. Either type of cooler shall have 3”, 150 PSIG, raised face
flanges for field installation on cooler nozzles and field piping.

2.1.8 Water Cooled Condenser:

a . Coils:
– Internally enhanced, seamless stainless-steel tubes mechanically expanded into alu-
minium alloy fins with full height collars. Sub-cooling coil shall be an integral part of con-
denser. Design working pressure shall be 650 PSIG (45 bar gauge).
– Vendor may offer an alternate price for a unit with aluminium tubes to compare with the
stainless-steel tube price.
b . Low Noise Fans:
– Shall be dynamically and statically balanced, direct drive, propeller type fan, providing ver-
tical air discharge and low sound characteristics. Each fan shall sit in its own compartment
to prevent cross flow during fan cycling. Fan guards of heavy gauge coated or galvanized
steel. Fan Blades shall be of heavy gauge or cast aluminium.
c. Fan Motors:
– Provide high efficiency, direct drive, 3 pole, (1150 rpm +/-) 3 phase, insulation class “F”,
current protected, Totally Enclosed Air-Over/Fan Cooled (TEFC), rigid mounted, with
double sealed, permanently lubricated, ball bearings.

2.1.9 CONTROLS

a. General:
– Provide functions for automatic start, stop, operating, and protection sequences across
the range of scheduled conditions and transients. All controls, including sensors, shall be
factory mounted and tested prior to shipment. Units shall be UL listed.
b. Microprocessor Enclosure:
– NEMA 4X powder painted steel cabinet with a gasket sealed protective cover.
c. Microprocessor Control Center:
– Local independent control or a remote “Run/Stop” signal from the BacNet System. Provide
for subsequent automatic control of compressor start/stop, anti- coincidence and anti-re-
cycle timers, automatic pump-down on shutdown, condenser fan staging, evaporator
pump, evaporator heater, unit alarm contacts, and chiller operation from 0°F to 125°F (-
18°C to 52°C) ambient. Automatic reset to normal chiller operation after power failure.
– Provide for digital communications to BacNet system via MODBUS TCP. Software stored
in non-volatile memory, with programmed setpoints retained in lithium battery backed real
time clock (RTC) memory for minimum 5 years.
– Forty-character liquid crystal display, descriptions in English, numeric data in English (or
Metric) units. Sealed keypad with sections for Set points, Display/Print, Entry, Unit Op-
tions & Clock, and On/Off Switch.
– Programmable Setpoints (within Manufacturer limits): display language; chilled liquid tem-
perature setpoint and range, remote reset temperature range, set daily schedule/holiday
for start/ stop, manual override for servicing, low and high AMBIENT Cut outs, number of
compressors, low liquid temperature cut-out, low suction pressure cut-out, high discharge
pressure cut-out, anti-recycle timer (compressor start cycle time), and anti-coincident timer
(delay compressor starts).
d . Display Data:
– Return and leaving liquid temperatures low leaving liquid temperature cut out setting, low
ambient temperature cut-out setting, outdoor air temperature, metric data, suction pres-
sure cut-out setting. Each system suction pressure, discharge pressure, liquid temperat-
ure reset, anti-recycle timer status for each compressor. Anti-coincident system starts
timer condition, compressor run status, no cooling load condition, day, date and time, daily
start/ stop times, holiday status, automatic or manual system lead/lag control. Lead sys-
tem definition, compressor starts/operating hours (each), status of hot gas valves, evapor-
ator heater and fan operation, run permissive status, number of compressors running, li-
quid solenoid valve status, load & unload timer status, water pump status.
e . System Safeties:
– Shall cause individual compressor systems to perform auto shut down; manual reset re-
quired after the third trip in 90 minutes. Includes: high discharge pressure, low suction
pressure, high-pressure switch, and motor protector. Compressor motor protector shall
protect against damage due to high input current or thermal overload of windings.
f . Unit Safeties:
– Shall be automatic reset and cause compressors to shut down if low ambient, low leaving
chilled liquid temperature, under voltage, and flow switch operation. Contractor shall
provide flow switch and wiring per chiller manufacturer requirements.
g . Alarm Contacts:
– Low ambient, low leaving chilled liquid temperature, low voltage, low battery, and (per
compressor circuit): high discharge pressure, and low suction pressure.
h. Analog Signals:
4-20ma chilled water supply and return temperatures. Discrete Signals:
24VDC or 120VAC run status, local LOR switch status.

2.1.10 Manufacturer

a. Approved Manufacturer: Shall provide any controls not listed above, necessary for auto-
matic chiller operation. Contractor shall provide field control wiring necessary to interface
chiller control system with BacNet system.
– Euroklimat (Contact Ms Erika Jael Rivo – 0999 977 0088)
– Dunham Bush (Contact Mr. Robert Guido 0918 9078 961)
– Carrier
– Or approved equal

2.1.11 POWER CONNECTION AND DISTRIBUTION

a. Power Panels:
– NEMA 3R, powder painted steel cabinets with a gasketed protective cover. Provide main
power connection(s), control power connections, compressor and fan motor start contact-
ors, current overloads, and factory wiring.
– Installing contractor must include accommodations in the chilled water piping to allow
proper drainage and venting of the heat exchanger. A strainer with a mesh size between
0.5 and 1.5mm (40 mesh) is required upstream of the heat exchanger to prevent clogging.
– Compressor, control and an motor power wiring shall be fully contained within the unit en-
closure, or shall be routed through liquid tight conduit.

2.1.12 ACCESSORIES AND OPTIONS

a. Assume microprocessor controlled, factory installed Across-the-Line type compressor mo-


tor starters as standard. Indicate with the pricing document the additive cost of Wye/Delta
and/or variable speed drive motor starting and control devices.

2.1.13 Outdoor Ambient Temperature Control

a . Low Ambient Control:


– Support unit operation to low ambient. Provide operable dampers, fan speed control, hot
gas bypass, etc. as needed to support chiller operation at partial to full load in cold
weather.
b . High Ambient Control:
– Support stable unit operation up to 46.5oC (115°F) ambient. Construct unit for reliable and
stable operation in warm ambient conditions with defensive and protective control features
to shut the unit down if adverse conditions.

2.1.14 Power Supply Connections:

a. Single Point Circuit Breaker:


– Provide unit with a single point landing Terminal Block with Circuit Breaker and lockable
external handle (in compliance with Article 44014 of N.E.C.) as part of the unit power and
control panel to isolate power voltage for servicing. Incoming power wiring is required to
comply with the National Electric Code and/or local codes. Indicate need, or not, for low
voltage power supply for crankcase heaters or other ancillary requirements. Effect a com-
plete system.
– Pressure Transducers and Readout Capability Discharge Pressure Transducers: Permits
unit to sense and display discharge pressure.
– Control Power Transformer: Provide integral voltage reduction transformer(s) to convert
480VAC-3-60 unit power voltage to 120VAC, single phase, 60 hertz, 500 VA capacity.
Factory- mounting to include primary and secondary wiring between the transformer and
the control panel.
– Motor Current Module: Capable of monitoring compressor motor current. Provide inherent
protection against compressor reverse rotation, phase-loss and phase imbalance. Provide
option of one factory-mounted module per electrical system.
– Power Factor Correction Capacitors: Provided to correct unit compressor factors to a
0.90-0.95.

2.1.15 Condenser Coil & Tubing Environmental Protection:


a. Post-Coated Dipped (required if not constructed of aluminium or stainless steel):
– Dipped-cured coating on condenser coils for seashore and other corrosive applications
(with the exception of strong alkalis, oxidizers, and wet bromine, chlorine and fluorine in
concentrations greater than 100ppm).
– Provide a corrosion protective coating in the factory to all copper tubing and copper/brass
devices in the refrigeration system.

2.1.16 Coated, Factory Mounted, Protective Chiller Panels.

a . Louvered Panels (full unit):


– Painted steel as per remainder of unit cabinet, to protect condenser coils from hail and in-
cidental damage, visually screen internal components, and deter unauthorized access to
internal components.

2 . 1 . 1 7 Flow Switch (Field-mounted):

a. Vapor proof SPDT, NEMA 4X switch, 150 PSIG, -20°F to 250°F

2.1.18 Differential Pressure Switch:

a. Alternative to an above-mentioned flow switch. 300 psi max. Working pressure SPDT 5
amp 125/250VAC switch, Range 3-45 PSIG (0.2-3 bar gauge), dead band 0.5 - 0.8 psi,
with 1/4” NPTE Pressure Connections.

2.1.19 Evaporator Options:


– Provide DX (direct expansion) Cooler with 150 PSIG water-side, 650 PSIG refrigerant-side
design working pressure.
2.1.20 Service Isolation valves:

a. Provide service suction and discharge (ball type) isolation valves per system. Include a
factory mounted system high-pressure relief valve in compliance with ASHRAE 15.

2.1.21 Hot Gas By-Pass:

a. Include this feature to support continuous, stable operation at capacities below the min-
imum step of unloading to as low as 5% capacity (depending on both the unit & operating
conditions) by introducing an artificial load on the cooler. Install hot gas by-pass on both
refrigerant circuits.

2.1.22 Building Automation System (EMS) Reset Interface:

a. Chiller to accept 4 to 20mA, 0 to 10 VDC, or discrete contact closure input (24VDC or


120VAC) to reset the leaving chilled liquid temperature.

2.1.23 Sound Reduction (Factory-mounted):

a. Provide unit with “Ultra quiet,” low speed, reduced noise fans.
b. Provide compressor acoustic sound blankets.

2.1.24 Vibration Isolation (Field-Mounted):

a. Neoprene Pad Isolators. Raise the unit above direct contact with the concrete pad and let
the isolators serve to accept any unevenness of the pad.

3 PART 3 - EXECUTION
3.0 INSTALLATION

3.0.1 General:

a. Rig and install in full accordance with Manufacturer’s requirements, Project Drawings, and
Contract Documents.

3.0.2 Location:

a. Locate chiller as indicated on drawings, including cleaning and service maintenance clear-
ance per Manufacturer instructions. Adjust and level chiller on support structure. If equip-
ment provided exceeds height of scheduled chiller, installing contractor is responsible for
any additional costs associated with extending the height of parapet or screening walls/en-
closures

3.0.3 Components:

a. Installing Contractor shall provide and install all auxiliary devices and accessories for fully
operational chiller.
3.0.4 Electrical:

a. Coordinate electrical requirements and connections for all power feeds with Electrical
Contractor (Division 16) and Owner’s maintenance electrician.

3.0.5 Controls:

a. Coordinate all control requirements and connections with Owner’s IT Department.

3.0.6 Finish:

a. Installing Contractor shall paint damaged and abraded factory finish with touch-up paint
matching factory finish.

3.0.7 Start up:

a. Provide a complete Start up and Commissioning service for the machine as part of the
Purchase Contract for the machine.

- END OF SECTION -

23 62 13

DIVISION 23 - SECTION 23 82 19
FAN COIL UNITS

1 General
1.0.1 Summary
a. Section includes:
– Materials and installation for fan coil units.

1.0.2 Related Sections:


a. Section 01 33 00 – Submittal Procedures.
b. Section 01 74 21 – Construction / Demolition Waste Management and Disposal.
c. Section 01 91 13.13 – Commissioning (Cx) Requirements.
d. Section 23 09 33 – Electric and Electronic Control System for HVAC.
e. Section 26 05 00 – Common Work Results – Electrical

1.0.3 References
a. Health Canada / Workplace Hazardous Materials Information System (WHMIS)]
b. Safety Data Sheets (SDS)
c. American Society of Heating, Refrigeration and Air-Conditioning Engineers (ASHRAE)
d. ASHRAE 79 – Method of Testing for Rating Fan-Coil Conditioners.

2 Submittals
2.0.1 Product Data:
a. Submit manufacturer's printed product literature, specifications and datasheet in accordance with
Section 01 33 00 - Submittal Procedures. Include product characteristics, performance criteria, and
limitations.
– Submit two copies of Workplace Hazardous Materials Information System (WHMIS) Safety Data
Sheets (SDS) in accordance with Section 01 33 00 - Submittal Procedures.
b. Product data to include:
– Filters, fan accessibility.
– Suspension, anchoring of cabinet.
– Physical size.
– Thermostat, transformer, controls where integral.
– Finish.
– kW rating, voltage, phase.
– Cabinet material thicknesses.

2.0.2 Shop Drawings:


a. Submit shop drawings in accordance with Section 01 33 00 - Submittal Procedures.

2.0.3 Quality assurance submittals: submit following in


accordance with Section 01 33 00 - Submittal Procedures.
a. Certificates: submit certificates signed by manufacturer certifying that materials comply with spe-
cified performance characteristics and physical properties.
b. Instructions: submit manufacturer's installation instructions.

2.1 QUALITY ASSURANCE

2.1.1 Health and Safety:


a. Do construction occupational health and safety in accordance with Section 01 35 29.06 - Health
and Safety Requirements.

2.2 DELIVERY, STORAGE, AND HANDLING

2.2.1 Packing, shipping, handling and unloading:


a. Deliver, store and handle in accordance with manufacturer's written instructions and Section
01 61 00 - Common Product Requirements.

2.2.2 Waste Management and Disposal:


a. Construction/Demolition Waste Management and Disposal: separate waste materials for reuse and
recycling in accordance with Section 01 74 21 - Construction/Demolition Waste Management and
Disposal.
b. Divert unused metal and wiring materials from landfill to metal recycling facility approved by Owner.
3 Products
3.0 Manufacturer
– Niagara Fans, (Contact Mr Jason Tan 09178954353, [email protected], Owner;
– System Air by Lincon Manufacturing Phils Inc. (Contact Ms Luzlyn Bermido 09178299424);
– Euroklimat (Contact: Ms Erika Jael Rivo 09999770088)
– Sinko Ymage Trading and Const. (Contact Ms Vangie Magnayon 09178079698)
– Or approved equal

3.1 Fan Coil Units


a. Cabinet: steel, 1.2 mm thick, floor wall or ceiling mounting, recessed. Front inlet/front outlet.
b. Elements: stainless steel sheathed with corrosion protected aluminum fins covering full length of
element capacity as indicated.
c. Blower motors: one speed, single phase.
d. Built-in thermostat with integral relay as indicated. Wall mounted thermostats: type as indicated, to
Section 23 09 33 - Electric and Electronic Control System for HVAC.
e. Fan delay switch.
f. On-Off switch (for wall mount unit only).
g. Two position selector switch (for wall mount unit only).
h. Fresh air duct adapter.
i. Filter: washable and reusable.
j. Trim for flush installation.
k. Finish: three stage phosphatized treatment followed by 2 coats baked enamel with final coat.
l. Assembly fully wired to one outlet location.
m. Multiple knockouts for up to 38 mm diameter conduit.
n. All motors shall be rated minimum of IE3.

4 Execution
4.0.1 MANUFACTURER’S INSTRUCTIONS
a. Compliance:
– Comply with manufacturer's written recommendations or specifications, including product
technical bulletins, handling, storage and installation instructions, and datasheet.

4.0.2 Pre-Installation
a. The unit needs to be handled with care during transportation and it is prohibited to move the
unit by holding on to the blower or blower blade.
b. The unit is designed to take its own weight. As such, do not transfer the load of duct, water
pipes and other accessories to the unit. This may cause the hanger to deform and fail.
c. Before any installation work starts, the following should be checked:
– Chilled water pipes and condensate water drainage pipes must be properly connected and
standby for use.
– Electrical wiring is properly connected and all terminals are tightened to prevent loose
wires.
– Sufficient space must be reserved for installation, service and maintenance purposes.
– Ensure the hanging rod is capable of supporting the weight of the unit and the position of
rods are according to drawing.
– Ensure the supply and return duct installed (for units that required ducting) is according to
the specification of the unit

4.0.3 Unit Installation


a. Mount or hang units as indicated.
b. Make power and control connections.
c. Co-ordinate ducting of fresh air with other Divisions at floor.
d. The top connecting pipe is for water outlet and bottom connecting pipe is for water inlet. Dur-
ing installation, do not tighten the pipe with excessive torque to prevent deformation of heat
exchanger. Both inlet and outlet pipes should be insulated, connecting threads should be
sealed using PTFE tape and sufficient gradient should be maintained for condensate water
pipe for proper water drainage.
e. It is recommended to use union for connection of unit to the supply and return water pipes
and to have isolation valves for each unit to ease servicing work / upgrade of equipment in the
future.
f. Water piping should be sufficiently supported at proper intervals to cater for the weight of the
pipes and also water flowing inside. Consideration for expansion and contraction is a must to
prevent leaking and breakage of pipes.
g. A manual air vent is located at the water outlet pipe. During commissioning or changing from
cooling to heating cycle (or vice versa), the valve must be opened to release air that might be
trapped inside the pipe in order to ensure good heat exchange efficiency.

4.0.4 Direction of Pipe Connections


a. Direction of pipes is determined by facing the supply air side of the unit. If the pipes are loc-
ated at the left, they are left piping and vice versa. It is important to specify the piping direction
during ordering to avoid installation problem at site.

4.0.5 Pipes Connection


a. All threaded pipes must be sealed using PTFE tape during connection.
b. After leak testing of water pipes, all pipes must be insulated to prevent heat lost / heat gain.
c. AII valves on the piping system must be located within the area of the drain pan of the unit. If
the site condition does not permit that, additional insulation or an additional drain pan should
be installed to prevent condensation.
d. The drain pan is designed to have gradient to ease the flow of condensate water. To facilitate
the proper drainage of condensate water, it is recommended to install the unit at a gradient of
3 ~ 5mm tilting to the drainage pipe.
e. Condensate water pipe should be insulated to prevent condensation at the outer pipe due to
the cool drainage water. It is recommended that the gradient of the pipe should not be less
than 1:75 to facilitate the flow of drainage water

4.0.6 ELECTRICAL CONNECTION


a. All electrical wiring must be performed by a qualified technician who is certified by the local
authorities.
b. All electrical wires used for wiring must comply to the local codes and regulations.
c. Fluctuation of electricity should be within +/-10% of the rated power supply.
d. During installation, wiring should be connected according to the wiring diagram provided by
the manufacturer and do not wire all of the three speeds of motor together to a single power
source.
e. Earth wire is provided and it is being connected to the casing of the motor for protection. The
unit should be properly GROUNDED to avoid incident of electrical shock.
f. Unit of different model should not share a single 3-speed switch, or the motor will not work
properly or it will be burnt

4.0.7 COMMISSIONING
a. Perform tests in accordance with Section 26 05 00 – Common Work Results - Electrical.
b. Section 01 91 13.13 – Commissioning (Cx) Requirements.

4.0.8 CLEANING
a. Proceed in accordance with Section 01 74 00 - Cleaning.
b. Upon completion and verification of performance of installation, remove surplus materials, ex-
cess materials, rubbish, tools and equipment.

END OF SECTION

DIVISION 23 - SECTION 23 73 00 16
AIR HANDLING UNITS

1 General
1.0 RELATED SECTIONS
a. Section 01 33 00 – Submittal Procedures.
b. Section 01 74 21 – Construction/Demolition Waste Management and Disposal.
c. Section 01 78 00 – Closeout Submittals.
d. Section 23 05 48 – Vibration and Seismic Controls for HVAC Piping and Equipment.
e. Section 23 33 00 – Air Duct Accessories.
f. Section 23 33 15 – Dampers - Operating.
g. Section 23 40 00 – HVAC Air Cleaning Devices.
h. Section 23 72 00 – Air-to-Air Energy Recovery Equipment.
i. Section 23 84 13 – Humidifiers.
1.1 REFERENCES
a. American National Standards Institute/Air-Conditioning and Refrigeration Institute (ANSI/ARI)
– ANSI/ARI 430, Central Station Air Handling Units.
b. Canadian General Standards Board (CGSB)
– CAN/CGSB 1.181, Ready-Mixed Organic Zinc-Rich Coating.
c. Canadian Standards Association (CSA)
– CSA B52, Mechanical Refrigeration Code.
d. Sheet Metal and Air-Conditioning Contractors' National Association (SMACNA).
e. American Bearing Manufacturer’s Association (ABMA)
– ANSI/ABMA 9 Load Ratings and Fatique Life for Ball Bearings
– ANSI/ABMA 11 Load Ratings and Fatique Life for Roller Bearings.
f. Air Movement and Control Association (AMCA)
– AMCA 210, Laboratory Method of Testing Fans for Aerodynamic Performance Rating
(ASHRAE)
– AMCA 300 Reverberaut Room Method for Sound Testing of Fans.
g. American Society of Heating Refrigeration and Air-Conditioning Engineers (ASHRAE).
– ASHRAE 68, Laboratory Method of Testing to Determine the Sound Power in a Duct.
– ANSI/ASHRAE 90.1, (I-P) Energy Standard for Buildings Except Low-Rise Residential Build-
ings.
– ANSI/ASHRAE 52.2, Method of Testing General Ventilation Air-Cleaning Devices for Removal
Efficiency by Particle Size.
h. National Electrical Manufacturer’s Association (NEMA)
– NEMA MG1 Motors and Generators
– NEMA ICS 7-1 Safety Standards for Construction and Guide for Selection, Installation and Op-
eration of Adjustable Speed Drive Systems.

1.2 SHOP DRAWINGS AND PRODUCT DATA


a. Submit shop drawings and product data in accordance with Section 01 33 00 - Submittal Proced-
ures.
b. Refer to Shop Drawing Section
c. Indicate following: fan, fan curves showing point of operation, motor drive, bearings, filters, mixing
box, dampers, VAV, coil, include performance data.

1.3 CLOSEOUT SUBMITTALS


a. Provide operation and maintenance data for incorporation into manual specified in Section 01 78
00 - Closeout Submittals.
b. Include following: fan, bearings, motor, damper, VAV control, air volume, total cooling, sensible
cooling, EDB, EWB, OAT.

1.4 WASTE MANAGEMENT AND DISPOSAL


a. Separate and recycle waste materials in accordance with Section 01 74 21 - Construction/Demoli-
tion Waste Management and Disposal, and with the Waste Reduction Workplan.
b. Remove from site and dispose of packaging materials at appropriate recycling facilities. Collect
and separate for disposal paper, plastic, polystyrene, corrugated cardboard, packaging material in
appropriate on-site bins for recycling in accordance with Waste Management Plan.
c. Divert unused metal and wiring materials from landfill to metal recycling facility approved by Owner.
d. Divert unused paint material from landfill to official hazardous material collections site approved by
Owner.
e. Do not dispose of unused paint materials into sewer systems, into lakes, streams, onto ground or in
other locations where it will pose health or environmental hazard.

1.5 EXTRA MATERIALS


a. Provide maintenance materials in accordance with Section 01 78 00 - Closeout Submittals.
b. Provide one spare set of filters.
c. Provide list of individual manufacturer's recommended spare parts for equipment such as bearings
and seals, and addresses of suppliers, together with list of specialized tools necessary for adjust-
ing, repairing or replacing, for placement into operating manual.
d. Spare filters: in addition to filters installed for start-up and commissioning. Immediately prior to ac-
ceptance by Owner, supply 1 complete set of filters for each filter unit or filter bank.

2 PRODUCTS
2.0 GENERAL
a. Factory assembled components to form units supplying air at designed conditions, as indicated.
b. Certify ratings: to ARI 430 with ARI seal.
c. Horizontal and vertical type, as indicated, having air tight modular components, consisting of cas-
ing, fan section with motor and drive, filter section, dampers, bypass section, heating coil, cooling
coil, humidifier, spray section, mixing box, blender air mixing device or filter mixing box.

2.1 Manufacturer
a. Approved Manufacturers: Subject to compliance with requirements, provide products by the fol-
lowing:
– Niagara Fans, (Contact Mr Jason Tan 09178954353, [email protected], Owner;
– System Air by Lincon Manufacturing Phils Inc. (Contact Ms Luzlyn Bermido 09178299424);
– Euroklimat (Contact: Ms Erika Jael Rivo 09999770088)
– TICA by DB International (Contact Mr Robert Guido 09189078961)
– Or approved equal

2.2 CASINGS
a. Galvanized or phosphate treated steel 1.6 mm thickness outer casing reinforced and braced for ri-
gidity.
b. Walk-in access doors: provide access for maintenance of internal parts with wired glass 200 x 200
mm viewing port or 200mm diameter polycarbonate double porthole.
c. Paint steel parts, where not galvanized, with corrosion resistant paint to CGSB 1.181.
d. Finish structural framed units, inside and out, with rust resistant enamel to Section 09 91 13 – Ex-
terior Painting.
e. Line entire casing with minimum 1 mm thick, solid galvanized, steel liner.

2.3 DRAIN PANS


a. Construction: stainless steel, plastic or FRP, rounded corners, double wall.
b. Insulation: extruded foam type, minimum 13 mm thick.
c. Drain connection: in bottom at low point.
d. Installation: slope without sag minimum 1% to ensure no standing water at any time or at any point.
e. Dimensions: minimum 75 mm from upstream face of coil to 150 mm beyond downstream face of
coil or eliminator and to include return bends and headers.

2.4 FANS
a. For centrifugal fans refer to Section 23 34 16
b. Cabinet hung or frame mounted AMCA-rated for sound and performance, centrifugal fans with
backward inclined or air foil wheels, selected to operate in stable part of performance curve and
heavy duty L10 100,000 hours minimum service self-aligning or split pillow block bearings.
c. Provide internally mounted motor as indicated complete with adjustable V-belt drive and guard.
d. Motor: see schedule.
e. Maximum sound power levels, as indicated.

2.5 VIBRATION ISOLATION


a. Flexible connections at inlet and outlet of fan section: to Section 23 33 00 – Air Duct Accessories.
b. Vibration isolators on fan section: to Section 23 05 48 - Vibration and Seismic Controls for HVAC
Piping and Equipment.

2.6 VARIABLE VOLUME DEVICES


a. Adjustable inlet vanes operated from centre mechanism linked to each damper vane or canti-
levered vane mechanism as indicated.
– Support vanes in self lubricated bronze bearings.
– On DWDI fans interconnect vanes to operate simultaneously.
– Provide locking devices for manual operation.
b. Variable fan width sleeve mechanism with control linkage as indicated.
– For DWDI fans, provide interconnected linkage to operate simultaneously.
– Provide locking devices for manual operation.
– Variable speed drives as indicated: motors to be suitable for variable speed drive. Variable
speed drives in accordance with Section 26 29 10 – Motor Starters to 600 V.

2.7 FILTER BOX


a. Material to match casing. For flat plus rigid type filter arrangement.
– Provide access to filter through hinged door with suitable hardware.
– Provide blank-off plates and gaskets to prevent air bypass.
– Filters: to Section 23 40 00 – HVAC Air Cleaning Devices.
– Activated Carbon Filter

2.8 MIXING BOX


a. Material to match casing and produce uniformly mixed air temperature within plus or minus 5 oC of
design across face of outlet.
b. Dampers:
– Dampers for mixing boxes: to Section 23 33 15 - Dampers - Operating.

2.9 BLENDER STATIC AIR MIXING DEVICE

2.9.1 General:
a. Pre-engineered device with no moving parts, designed to thoroughly mix warm and cold air
streams, to within 3° C at 40 Pa pressure drop and to provide for even velocity distribution profile.
b. Sizing criteria:
– Type: static.
– Size: to suit unit mixing box at mixer area to plenum area of 0.4, and minimum flow rate to max -
imum flow rate of 0.4 plenum, velocity 2.5 m/s
– Pressure drop:40 Pa.
– Capacity:
 Outside air: as indicated.
 Return air: as indicated.
– Mixed air temperature: 12° C at outside air to supply air ratio of 0.25.
c. Construction:
– 2 mm thick aluminium or 1.6 mm thick stainless steel.
d. Blender section:
– Blender in housing ready for insertion into air handling unit.
– 50 mm flanges on inlet and outlet.
– Complete with 25 mm, 32 kg/m3 density, fibreglass lining and insulated access door.
e. Blender mixing box:
– General: single unit consisting of dampers, blender, mixing section, with provision for floor
mounting.
– Construction: stainless steel duct connection flanges, reinforced for rigidity, finished with corro-
sion resistant paint or zinc coating.
– Dampers: parallel blade, low leakage, proportioning type.
 Leakage: not more than 50 l/s.m2 at 750 Pa.
 Seals: Neoprene on damper edges, top, bottom, sides of framing.
– Blades of 1.6 mm thick steel, 150 mm maximum wide, locked to steel rods in rustproof bush-
ings.

2.10 COILS
a. Capacity: see schedule.
b. Ratings: ARI certified.
c. Construction:
– Casings: 1.5 mm thick galvanized sheet steel.
d. Supports of galvanized steel channel or double angle frames.
– Blank-off plates. Insulated sandwich construction.
e. Non-freeze steam coils: tube-in-tube type with internal perforated steam distributing tubes. Slope
tubes to drain condensate.
– Tubes: copper, brass or steel.
– Fins: aluminum.
– Headers: cast iron, steel or cast brass.
– Pressure tests: 1.7 MPa.
f. Steam coils: single tube type.
– Tubes: copper, brass or steel.
– Fins: aluminium.
– Headers: cast iron, steel or cast brass.
– Pressure tests: 1.7 MPa.
g. Hot and Chilled water coils: cleanable fins.
– Tubes: copper, brass or steel.
– Fins: aluminium plate or spiral wound.
– Headers: cast iron, steel or cast brass.
– Pressure tests: 1.7 MPa.
– Direct expansion refrigerant coils:
h. Serpentine type, arranged to prevent trapping of oil.
– Liquid distributors to ensure even distribution of liquid refrigerant to all circuits.
– Silver solder or braze joints in refrigerant tubing.
– Evacuate and charge coil with nitrogen and seal before sending to site.
i. Tubes: copper.
j. Fins: aluminium, plate or spiral wound.
k. Headers: copper.
l. Pressure tests: CSA B52 and carry a Canadian Refrigeration Number. Dehydrated. Sealed with ni-
trogen charge.

2.11 HUMIDIFIERS
a. To Section 23 84 13 - Humidifiers.

2.12 STRAIGHT HEAT PIPE DEVICES


a. As indicated and as per Section 23 72 00 – Air-to-Air Energy Recovery Equipment.

3 EXECUTION
3.0 INSTALLATION
a. Install units in accordance with manufacturer's instructions and as indicated.
b. Ensure adequate clearance for servicing and maintenance.

3.1 FANS
a. Install fan sheaves required for final air balance.
b. Install flexible connections at fan inlet and fan outlets.
c. Install vibration isolators.

3.2 DRIP PANS


a. Install deep seal P-traps and trap seal primer on drip lines.
b. Depth of water seal to be 1.5 times static pressure at this point.

3.3 COMMISSIONING
a. Commission in accordance with Section 01 91 13.13 – Commissioning (Cx) Requirements one day
per unit for start-up and one day for commissioning.

END OF SECTION

You might also like