GENERAL NOTES AND

SPECIFICATIONS:

1.) ALL ELECTRICAL WORKS


15.0 m
INDICATED HERE IN SHALL BE

C9
DONE IN ACCORDANCE WITH
DESIGN ANALYSIS THE LATEST EDITION OF
4.0 m 3.5 m 4.0 m 3.5 m PHILIPPINE ELECTRICAL CODE
SHORT CIRCUIT ANALYSIS PART 1, THE REQUIREMENTS OF
R
D LINE TO NUETRAL FAULT @240V-X1 THE OFFICE OF BUILDING
FAULT X1 OFFICIAL AND THE ELECTRIC

C8
3 STEP 1: Isec= Transformer Volt-Amperes
Secondary Voltage
SERVING AREA.
RE ACU
2.)THE ELECTRICAL
S2 = 50,000 SUPPLY/SERVICE VOLTAGE IS
230
C7
C6
230V, SINGLE PHASE, TWO

C3
S WIRES, 60Hz.
3
= 217.39 Amps
2.5 m

3.) CONTRACTOR SHALL VERIFY


Isec

3.5 m
STEP 2: Isc (sym)= %Z AND ORIENT THE ACTUAL
C1

2
LOCATIONS OF CONCRETE
S2 S = 217.39 TERMINAL.
1.5 m

0.04 4.) ALL INSTALLATION SHALL BE


S = 5434.75 CONCEALED FROM VIEW,
SAY, 10 kAIC MAIN CKT. BREAKER WIRING SHALL BE INCASED IN
PVC PIPE OR FLEXIBLE CONDUIT

8.5 m
C2

1.5 m
EXCEPT POWER SERVICE
4.0 m

S
WHICH SHALL BE IN RSC.
8.5 m

S 2
3
VOLTAGE DROP CALCULATION: 5.) THE MINIMUM SIZE OF THE
S
WIRE SHALL BE 2-3.5 mm2 AND
(a) VOLTAGE DROP FOR SERVICE DROP WIRE,

C4
ACU 20 mm dia. CONDUIT.
2 6.) ALL MATERIALS SHALL BE
40 METERS, 14 MM ALUMINUM WIRE.
3 NEW AND APPROVED TYPE,
S2 S2
VD= 2 X1000
LXZXI APPROPRIATE FOR BOTH

3.5 m
2
LOCATION AND INTENDED USE.
= 2 X 40 X 0.808 X 94.768 7.) ELECTRICAL INSTALLATION
1000 SHALL BE UNDER A DIRECT
2.0 m

C5

ACU SUPERVISION OF DULY


= 6.13 LICENSED ELECTRICAL
ENGINEER AND REGISTERED
6.13 X 100 MASTER ELECTRICIAN.
%VD= 230 8.) GROUND RESISTANCE SHALL
= 2.67% NOT EXCEED 25 OHMS.
10.) MOUNTING HEIGHTS FOR
(b) VOLTAGE DROP FOR SERVICE ENTRANCE, SWITCHES AND CONVENIENCE
2
10 METERS, 8.0 MM THW CU.WIRE. OUTLET SHALL BE 1.37 m or 1370

LIGHTING LAYOUT POWER LAYOUT VD= 2 X1000


LXZXI mm and 0.30 m or 300 mm
RESPECTIVELY,
OTHERWISE
UNLESS
INDICATED IN
= 2 X 10 1000
X 1.26 X 94.768
ARCHITECTURAL PLANS.

= 2.39

%VD= 2.39 X 100


230
= 1.04%

SCHEDULE OF LOADS SINGLE LINE DIAGRAM LOCATION MAP LEGEND


CIRCUIT BREAKER PROTECTION
CKT. NO. LOAD DESCRIPTION QTY. VA VOLTS AMPERE KAIC SIZE OF WIRE AND CONDUIT
AMPERE FRAME AMPERE TRIP
1 LIGHTING OUTLET 8 800 230 3.48 100 10 20 USE: 2-3.5 mm2 & 1-2.0 mm2 THW 20mm dia PVC PIPE DEL PILAR POBLACION,MAGPET
2 SERVICE
USE: 2-3.5 mm & 1-2.0 mm2 THW 20mm dia PVC PIPE
2 LIGHTING OUTLET 6 600 230 2.61 100 10 20 2 GANG CONVENIENCE OUTLET CIRCUIT BREAKER

2 ENTRANCE USE: 2-38 mm2 & 1-14 mm2 2


3 CONVENIENCE OUTLET 7 1260 230 5.48 100 10 20 USE: 2-3.5 mm & 1-2.0 mm2 THW 20mm dia PVC PIPE THW CU. WIRE in 35 mm dia
CIRCUIT HOME-RUN
2 RSC 3 GANG CONVENIENCE OUTLET
4 1.5 hp AIR CONDITIONING UNIT 1 2300 230 10 100 10 30 USE: 2-5.5 mm & 1-5.5 mm2 THW 20mm dia PVC PIPE 3
5 1 hp AIR CONDITIONING UNIT 1 1840 230 8 100 10 30 2 & 1-5.5 mm2 THW 20mm dia PVC PIPE
USE: 2-5.5 mm ACU AIR-CONDITIONING
2 RANGE OUTLET UNIT
6 1 hp AIR CONDITIONING UNIT 1 1840 230 8 100 10 30 USE: 2-5.5 mm & 1-5.5 mm2 THW 20mm dia PVC PIPE R
ALIBAYON ELEM. SCHOOL
7 1 1840 230 8 100 10 30 2 2
REFRIGERATOR 1hp USE: 2-5.5 mm & 1-5.5 mm THW 20mm dia PVC PIPE KILOWATT ALIBAYON SBC S SINGLE GANG SWITCH
DISHWASHER OUTLET
8
9
ELECTRIC RANGE
DISHWASHER
1
1
5000
440
230
230
21.74
1.91
100
100
10
10
30
30
2
2
2
USE: 2-5.5 mm & 1-5.5 mm THW 20mm dia PVC PIPE
2
M HOUR METER D
S2 DOUBLE GANG SWITCH
USE: 2-5.5 mm & 1-5.5 mm THW 20mm dia PVC PIPE REFRIGERATOR OUTLET
FUTURE LOAD 5000 21.74 10 2 2 RE
10 230 100 30 USE: 2-5.5 mm & 1-5.5 mm THW 20mm dia PVC PIPE PANEL BOARD
FLUORESCENT
TOTAL CONNECTION LOAD 20920 90.96 USE: 1-125 AT/225
AF, 60 Hz, SINGLE
PHASE, 1P, MCB
M KILOWATT HOUR METER
CUEVAS RES. INCANDESCENT LAMP

125 AT
FULL LOAD CURRENT @ 80% DEMAND FACTOR: GYMNASIUM
IFL = (90.96-10)0.80 = 64. 768 + 30 = 94. 768 A UTILITY POLE
SERVICE ENTRANCE
USE: 1-125 AT/225 AF, 60Hz, SINGLE PHASE, 1P, MCB 1 20 AT 20 AT
2
3 20 AT 30 AT
4
USE: 2- 38 mm2 THW CU. WIRE + 1-14.0 mm2 GROUND WIRE @ 35 mm RSC 5 30 AT 30 AT
6
30 AT 30 AT
8 JULIAN RES. CHUA RES.
7
ALIBAYON HIGH SCHOOL
9 30 AT 30 AT
10

GROUND

PREPARED / DESIGNED BY: PRC LICENSE #: PROJECT TITLE / LOCATION: CONFORMED BY: SHEET CONTENTS: SCALE: SHEET NO:
DATE OF EXPIRY:
LIGHTING LAY-OUT SINGLE LINE DIAGRAM
PTR #:
1:100
GRACEL JOY L. CHUA, PEE ISSUED AT: CHUA RESIDENCE ELECTRICAL PLAN GRACEL JOY L. CHUA POWER LAY-OUT LOCATION MAP
DATE DRAWN:
E
ISSUED ON:
LEGEND
PROFESSIONAL ELECTRICAL ENGINEER
TIN #: OWNER
DESIGN ANALYSIS 0 1
ADDRESS: PRK. ROSE, BRGY. ALIBAYON MAGPET COTABATO SCHEDULE OF LOADS AUGUST 23, 2024