AJ275647019268en 000201
AJ275647019268en 000201
AJ275647019268en 000201
Design Guide
VLT® Midi Drive FC 280
vlt-drives.danfoss.com
Contents Design Guide
Contents
1 Introduction 6
1.1 Purpose of the Design Guide 6
1.2 Additional Resources 6
1.3 Definitions 6
1.3.1 Frequency Converter 6
1.3.2 Input 6
1.3.3 Motor 6
1.3.4 References 7
1.3.5 Miscellaneous 7
1.4 Document and Software Version 9
1.5 Approvals and Certifications 9
1.5.1 CE Mark 9
1.5.2 Low Voltage Directive 9
1.5.3 EMC Directive 9
1.6 Safety 10
2 Product Overview 11
2.1 Enclosure Size Overview 11
2.2 Electrical Installation 12
2.2.1 Motor Connection 14
2.2.2 AC Mains Connection 15
2.2.3 Control Terminal Types 16
2.2.4 Wiring to Control Terminals 17
2.3 Control Structures 17
2.3.1 Control Modes 17
2.3.2 Control Principle 19
2.3.3 Control Structure in VVC+ 19
2.3.4 Internal Current Control in VVC+ Mode 20
2.3.5 Local (Hand On) and Remote (Auto On) Control 20
2.4 Reference Handling 21
2.4.1 Reference Limits 22
2.4.2 Scaling of Preset References and Bus References 23
2.4.3 Scaling of Analog and Pulse References and Feedback 23
2.4.4 Dead Band Around Zero 24
2.5 PID Control 27
2.5.1 Speed PID Control 27
2.5.2 Process PID Control 30
2.5.3 Process Control Relevant Parameters 31
2.5.4 Example of Process PID Control 32
3 Application Examples 45
3.1 Introduction 45
3.1.1 Encoder Connection 45
3.1.2 Encoder Direction 45
3.1.3 Closed-loop Drive System 45
3.2 Application Examples 46
3.2.1 AMA 46
3.2.2 Speed 46
3.2.3 Start/Stop 47
3.2.4 External Alarm Reset 48
3.2.5 Motor Thermistor 48
3.2.6 SLC 48
7 Specifications 75
7.1 Power-dependent Specifications 75
7.2 Mains Supply (3-phase) 76
7.3 Motor Output and Motor Data 77
7.4 Ambient Conditions 77
7.5 Cable Specifications 78
7.6 Control Input/Output and Control Data 78
7.7 Connection Tightening Torques 81
7.8 Fuses and Circuit Breakers 81
7.9 Efficiency 82
7.10 Acoustic Noise 83
Index 86
1 1 1 Introduction
Pull-out
Analog inputs
The analog inputs are used for controlling various
functions of the frequency converter.
There are 2 types of analog inputs:
• Current input: 0–20 mA and 4–20 mA.
• Voltage input: 0–10 V DC.
Analog outputs
The analog outputs can supply a signal of 0–20 mA, or 4–
20 mA.
rpm
Automatic motor adaptation, AMA
The AMA algorithm determines the electrical parameters
Illustration 1.1 Break-away Torque
for the connected motor at standstill.
Brake resistor
The brake resistor is a module capable of absorbing the
ηVLT
brake power generated in regenerative braking. This
The efficiency of the frequency converter is defined as the
regenerative brake power increases the DC-link voltage,
ratio between the power output and the power input.
and a brake chopper ensures that the power is transmitted
Start-disable command to the brake resistor.
A start-disable command belonging to the control
CT characteristics
commands in group 1. See Table 1.1 for more details.
Constant torque characteristics used for all applications
Stop command such as conveyor belts, displacement pumps, and cranes.
A stop command belonging to the control commands in
Digital inputs
group 1. See Table 1.1 for more details.
The digital inputs can be used for controlling various
functions of the frequency converter.
1.3.4 References
Digital outputs
The frequency converter features 2 solid-state outputs that
Analog reference
can supply a 24 V DC (maximum 40 mA) signal.
A signal transmitted to the analog inputs 53 or 54 can be
voltage or current. DSP
Digital signal processor.
Binary reference
A signal transmitted to the serial communication port.
For FC 280 frequency converters, cosϕ1 = 1, therefore: disappeared, and the trip state is cancelled by activating
reset or, in some cases, by being programmed to reset Technical specifications cannot be deduced from the CE 1 1
automatically. Do not use trip for personal safety. mark.
Trip lock
Trip lock is a state entered in fault situations when the 1.5.2 Low Voltage Directive
frequency converter is protecting itself and requiring
physical intervention. For example, a short circuit on the Frequency converters are classified as electronic
output triggers a trip lock. A locked trip can only be components and must be CE labeled in accordance with
canceled by cutting off mains, removing the cause of the the Low Voltage Directive. The directive applies to all
fault, and reconnecting the frequency converter. Restart is electrical equipment in the 50–1000 V AC and the 75–
prevented until the trip state is canceled by activating 1600 V DC voltage ranges.
reset or, sometimes, by being programmed to reset
automatically. Do not use trip lock for personal safety. The directive mandates that the equipment design must
VT characteristics ensure the safety and health of people and livestock, and
Variable torque characteristics used for pumps and fans. the preservation of material by ensuring the equipment is
properly installed, maintained, and used as intended.
VVC+ Danfoss CE labels comply with the Low Voltage Directive,
If compared with standard voltage/frequency ratio control, and Danfoss provides a declaration of conformity at
voltage vector control (VVC+) improves the dynamics and request.
stability, both when the speed reference is changed and in
relation to the load torque.
1.5.3 EMC Directive
60° AVM
Refer to the switching pattern 60° asynchronous vector Electromagnetic compatibility (EMC) means that electro-
modulation. magnetic interference between pieces of equipment does
1.4 Document and Software Version not hinder their performance. The basic protection
requirement of the EMC Directive 2014/30/EU states that
This manual is regularly reviewed and updated. All devices that generate electromagnetic interference (EMI) or
suggestions for improvement are welcome. Table 1.2 shows whose operation could be affected by EMI must be
the document version and the corresponding software designed to limit the generation of electromagnetic
version. interference and shall have a suitable degree of immunity
to EMI when properly installed, maintained, and used as
Edition Remarks Software version intended.
MG07B1 The first edition of this manual 1.1
A frequency converter can be used as standalone device or
Table 1.2 Document and Software Version as part of a more complex installation. Devices in either of
these cases must bear the CE mark. Systems must not be
1.5 Approvals and Certifications CE marked but must comply with the basic protection
requirements of the EMC directive.
Frequency converters are designed in compliance with the
directives described in this section. Applied standards and compliance for STO
Using STO on terminals 37 and 38 requires fulfillment of all
provisions for safety including relevant laws, regulations,
1.5.1 CE Mark and guidelines.
The CE mark (Communauté européenne) indicates that the The integrated STO function complies with the following
product manufacturer conforms to all applicable EU standards:
directives. • IEC/EN 61508: 2010 SIL2
• IEC/EN 61800-5-2: 2007 SIL2
The EU directives applicable to the design and • IEC/EN 62061: 2012 SILCL of SIL2
manufacture of frequency converters are:
• The Low Voltage Directive. • IEC/EN 61326-3-1: 2008
1 1 1.6 Safety
Frequency converters contain high-voltage components
and have the potential for fatal injury if handled
improperly. Only qualified personnel are allowed to install
and operate the equipment. Do not attempt repair work
without first removing power from the frequency converter
and waiting the designated duration of time for stored
electrical energy to dissipate.
2 Product Overview
2 2
2.1 Enclosure Size Overview
Enclosure size depends on power range.
Enclosure K1 K2 K3 K4 K5
size
130BA870.10
130BA809.10
130BA810.10
130BA810.10
130BA810.10
Enclosure
IP20 IP20 IP20 IP20 IP20
protection
Power
range
[kW (hp)] 0.37–2.2 (0.5–3.0) 3.0–5.5 (5.0–7.5) 7.5 (10) 11–15 (15–20) 18.5–22 (25–30)
3-phase
380–480 V
Power
range
[kW (hp)] 0.37–1.5 (0.5–2.0) 2.2 (3.0) 3.7 (5.0) – –
3-phase
200–240 V1)
Power
range
[kW (hp)]
0.37–1.5 (0.5–2.0) 2.2 (3.0) – – –
single-
phase
200–240 V1)
130BE202.15
RFI
91 (L1/N) (U) 96
Power 92 (L2/L) (V) 97
input 93 (L3) (W) 98
95 PE (PE) 99
Motor
Switch mode
power supply * (-DC) 88
10 V DC 24 V DC (+DC/R+) 89 Brake
15 mA 100 mA resistor
50 (+10 V OUT) + - + -
+10 V DC (R-) 81
0−10 V DC 53 (A IN) **
Relay 1
03
0−10 V DC 54 (A IN) 250 V AC, 3 A
0/4−20 mA 02
55 (COM A IN) 01
12 (+24 V OUT)
13 (+24 V OUT)
P 5-00
24 V (NPN)
18 (D IN) 0 V (PNP)
24 V (NPN)
19 (D IN) 0 V (PNP) (A OUT) 42 Analog output
0/4−20 mA
24 V (NPN)
27 (D IN/OUT) 0 V (PNP) ***
24 V ON = Terminated
1 2
ON
OFF = Open
0V 5V
24 V (NPN)
29 (D IN) 0 V (PNP)
S801 0V
RS485
(N RS485) 69 RS485
24 V (NPN) interface
32 (D IN) 0 V (PNP) (P RS485) 68
24 V (NPN)
33 (D IN) 0V (COM RS485) 61
0 V (PNP)
(PNP) = Source
37 (STO1)**** (NPN) = Sink
38 (STO2)****
A=Analog, D=Digital
* Built-in brake chopper is only available on 3-phase units.
** Terminal 53 can also be used as digital input.
*** Switch S801 (bus terminal) can be used to enable termination on the RS485 port (terminals 68 and 69).
**** Refer to chapter 4 Safe Torque Off (STO) for the correct STO wiring.
130BD391.11
2
3
2 2
1
Back
OK
Hand Auto
On Reset On
9 10
L1
L2
U
L3
V
PE
W
PE
8 7
1 PLC 6 Minimum 200 mm (7.9 in) between control cables, motor, and
mains.
2 Frequency converter 7 Motor, 3-phase and PE
3 Output contactor (generally not recommended) 8 Mains, single-phase, 3-phase, and reinforced PE
4 Grounding rail (PE) 9 Control wiring
5 Cable shielding (stripped) 10 Equalizing minimum 16 mm2 (6 AWG)
130BD531.10
2 2 WARNING V
W
98
INDUCED VOLTAGE U 97
96
Induced voltage from output motor cables that run
together can charge equipment capacitors, even when
the equipment is turned off and locked out. Failure to
run output motor cables separately or use shielded
cables could result in death or serious injury.
130BE804.10
130BE232.11
2 2
Illustration 2.4 Mains, Motor, and Grounding Connection for Illustration 2.6 Mains, Motor, and Grounding Connection for 3-
Single-phase Units (K1, K2) phase Units (K4, K5)
130BE212.10
operation 24 V encoder.
Input
Terminal 33 can
Parameter 5-15 Ter be used for
[0] No
33 minal 33 Digital pulse input.
1 2 operation
Input
Functional safety
37, 38 – STO
inputs.
3
Analog inputs/outputs
Programmable
Illustration 2.7 Control Terminal Locations analog output.
The analog
signal is 0–
Parameter 6-91 Ter
[0] No 20 mA or 4–
130BE214.10
1 2 42 minal 42 Analog
37 38 12 13 18 19 27 29 32 33 61 68 69
operation 20 mA at a
Output
maximum of
500 Ω. Can also
be configured as
3
digital outputs.
42 53 54 50 55
10 V DC analog
supply voltage.
15 mA
Illustration 2.8 Terminal Numbers
maximum
50 – +10 V DC
commonly used
for potenti-
See chapter 7.6 Control Input/Output and Control Data for ometer or
terminal ratings details. thermistor.
Analog input.
Default Only voltage
Terminal Parameter Description Parameter group
setting mode is
53 6-1* Analog input –
Digital I/O, pulse I/O, encoder supported. It can
53
24 V DC supply also be used as
voltage. digital input.
Maximum Analog input.
12, 13 – +24 V DC Parameter group
output current is Selectable
54 6-2* Analog input –
100 mA for all between voltage
54
24 V loads. or current mode.
Parameter 5-10 Ter Common for
18 minal 18 Digital [8] Start 55 – – digital and
Input analog inputs.
Digital inputs.
Parameter 5-11 Ter
[10] Table 2.2 Terminal Descriptions - Digital Inputs/Outputs,
19 minal 19 Digital
Reversing Analog Inputs/Outputs
Input
Parameter 5-01 Ter
Selectable for
minal 27 Mode
either digital
Parameter 5-12 Ter
input, digital
minal 27 Digital
27 output, or pulse
Input DI [2] Coast
output. The
Parameter 5-30 Ter inverse
default setting is
minal 27 Digital DO [0] No
digital input.
Output operation
Terminal Parameter
Default
Description
2.3 Control Structures
setting
Serial communication A frequency converter rectifies AC voltage from mains into
Integrated RC DC voltage. Then the DC voltage is converted into an AC 2 2
filter for cable current with a variable amplitude and frequency.
shield. ONLY for
61 – – connecting the The motor is supplied with variable voltage/current and
shield when frequency, enabling infinitely variable speed control of 3-
experiencing phased standard AC motors and permanent magnet
EMC problems. synchronous motors.
Parameter group RS485 interface.
68 (+) 8-3* FC port – A control card 2.3.1 Control Modes
settings switch is
Parameter group provided for The frequency converter controls either the speed or the
69 (-) 8-3* FC port – termination torque on the motor shaft. The frequency converter also
settings resistance. controls the process for some applications which use
Relays process data as reference or feedback, for example,
Form C relay temperature and pressure. Setting parameter 1-00 Configu-
output. These ration Mode determines the type of control.
relays are in
various locations Speed control
depending on There are 2 types of speed control:
Parameter 5-40 Fun [1] Control the frequency
01, 02, 03 • Speed open-loop control, which does not require
ction Relay Ready converter config- any feedback from the motor (sensorless).
uration and size.
Usable for AC or • Speed closed-loop PID control, which requires a
DC voltage and speed feedback to an input. A properly optimized
resistive or speed closed-loop control has higher accuracy
inductive loads. than a speed open-loop control.
Select which input to use as speed PID feedback in
Table 2.3 Terminal Descriptions - Serial Communication parameter 7-00 Speed PID Feedback Source.
Torque control
2.2.4 Wiring to Control Terminals The torque control function is used in applications where
the torque on motor output shaft controls the application
Control terminal connectors can be unplugged from the as tension control. Select [2] Torque closed loop or [4]
frequency converter for ease of installation, as shown in Torque open loop in parameter 1-00 Configuration Mode.
Illustration 2.7. Torque setting is done by setting an analog, digital, or bus-
controlled reference. When running torque control, it is
For details about STO wiring, refer to chapter 4 Safe Torque recommended to run a full AMA procedure, because
Off (STO). correct motor data is important in achieving optimal
performance.
NOTICE • Closed-loop in VVC+ mode. This function is used
Keep control cables as short as possible and separate in applications with low to medium dynamic
them from high-power cables to minimize interference. variation of shaft and offers excellent
performance in all 4 quadrants and at all motor
1. Loosen the screws for the terminals. speeds. The speed feedback signal is mandatory.
Ensure that the encoder resolution is at least
2. Insert sleeved control cables into the slots.
1024 PPR, and the shield cable of the encoder is
3. Fasten the screws for the terminals. properly grounded, because the accuracy of the
4. Ensure that the contact is firmly established and speed feedback signal is important. Tune
not loose. Loose control wiring can be the source parameter 7-06 Speed PID Lowpass Filter Time to
of equipment faults or less than optimal get the best speed feedback signal.
operation. • Open-loop in VVC+ mode. The function is used in
See chapter 7.5 Cable Specifications for control terminal mechanically robust applications, but the
cable sizes and chapter 3 Application Examples for typical accuracy is limited. Open-loop torque function
control cable connections.
VLT® Midi Drive FC 280 is a general-purpose frequency converter for variable speed applications. The control principle is
based on VVC+. 2 2
FC 280 frequency converters can handle asynchronous motors and permanent magnet synchronous motors up to 22 kW
(30 hp).
The current-sensing principle in FC 280 frequency converters is based on the current measurement by a resistor in the DC
link. The ground fault protection and short circuit behavior are handled by the same resistor.
130BD974.10
Brake resistor
R+ R-
Load sharing + 82 81
89(+)
L1 91
L2 92
Inrush U 96
L3 93
V 97
M
W 98
RFI switch
Load sharing -
88(-)
P 4-19
130BD371.10
Max. output freq.
P 1-00 P 1-00
P 4-14
Config. mode Config. mode
Motor speed +f max.
high limit (Hz)
High P 3-** Motor
controller
Ref.
Ramp -f max.
Low
+ P 4-12
P 4-19
S Process Motor speed
Max. output freq.
_ low limit (Hz)
P 7-0* +f max.
Illustration 2.10 Control Structure in VVC+ Open-loop Configurations and Closed-loop Configurations
In the configuration shown in Illustration 2.10, parameter 1-01 Motor Control Principle is set to [1] VVC+ and
parameter 1-00 Configuration Mode is set to [0] Speed open loop. The resulting reference from the reference handling system
is received and fed through the ramp limitation and speed limitation before being sent to the motor control. The output of
the motor control is then limited by the maximum frequency limit.
2 2 If parameter 1-00 Configuration Mode is set to [1] Speed closed loop, the resulting reference is passed from the ramp
limitation and speed limitation into a speed PID control. The speed PID control parameters are in parameter group 7-0*
Speed PID Ctrl. The resulting reference from the speed PID control is sent to the motor control limited by the frequency limit.
Select [3] Process in parameter 1-00 Configuration Mode to use the process PID control for closed-loop control of speed or
pressure in the controlled application. The process PID parameters are in parameter groups 7-2* Process Ctrl. Feedb and 7-3*
Process PID Ctrl.
2.3.4 Internal Current Control in VVC+ 2.3.5 Local (Hand On) and Remote (Auto
Mode On) Control
The frequency converter features an integral current limit Operate the frequency converter manually via the local
control. This feature is activated when the motor current, control panel (graphic LCP or numerical LCP) or remotely
and thus the torque, is higher than the torque limits set in via analog/digital inputs or fieldbus.
parameter 4-16 Torque Limit Motor Mode, Start and stop the frequency converter by pressing the
parameter 4-17 Torque Limit Generator Mode, and [Hand On] and [Reset] keys on the LCP. Set-up is required
parameter 4-18 Current Limit. via the following parameters:
When the frequency converter is at the current limit during • Parameter 0-40 [Hand on] Key on LCP.
motor operation or regenerative operation, the frequency
converter tries to get below the preset torque limits as • Parameter 0-44 [Off/Reset] Key on LCP.
quickly as possible without losing control of the motor. • Parameter 0-42 [Auto on] Key on LCP.
Reset alarms via the [Reset] key or via a digital input, when
the terminal is programmed to Reset.
130BP046.10
Hand Auto
Off Reset
on on
130BB893.10
130BD374.10
Relative scaling ref.
No function
P 3-18
Analog ref.
Pulse ref.
P 3-14
Preset relative ref.
P 3-00 P 1-00
(0) Ref./feedback range Configuration mode
(1)
Scale to
(5) -max ref./ Hz
P 5-1x(28)/P 5-1x(29) +max ref.
(6) 100%
Input command:
(7) Catch up/ slow down
-100% Torque P 16-01
Y Remote
Relative Catch up/ ref.
P 3-04 Scale to
X+X*Y slow Nm
(0) X
/100 down
max ref.
P 3-12 %
No function (1)
D1 Catchup Slowdown
value Process
Analog ref. P 5-1x(15) %
Preset '1'
Ref.resource 1
±100% unit
Local bus ref. Freeze ref.
&
DigiPot increase/
decrease
ref.
P 5-1x(21)/P 5-1x(22)
Speed up/ speed down
No function
200% Ref. in %
P 3-16
Pulse ref.
DigiPot
No function
Analog ref.
Ref. resource 3
P 3-17
Pulse ref.
The remote reference is calculated once in every scan 2.4.1 Reference Limits
interval and initially consists of 2 types of reference
inputs: Parameter 3-00 Reference Range, parameter 3-02 Minimum
2 2 1. X (the external reference): A sum (see Reference, and parameter 3-03 Maximum Reference define
parameter 3-04 Reference Function) of up to 4 the allowed range of the sum of all references. The sum of
externally selected references, comprising any all references is clamped when necessary. The relation
combination (determined by the setting of between the resulting reference (after clamping) and the
parameter 3-15 Reference 1 Source, sum of all references are shown in Illustration 2.14 and
parameter 3-16 Reference 2 Source, and Illustration 2.15.
parameter 3-17 Reference 3 Source) of a fixed
preset reference (parameter 3-10 Preset Reference),
P 3-00 Reference Range= [0] Min-Max
130BA184.10
variable analog references, variable digital pulse
references, and various fieldbus references in any Resulting reference
unit the frequency converter is monitoring ([Hz],
[RPM], [Nm], and so on).
2. Y (the relative reference): A sum of 1 fixed preset P 3-03
reference (parameter 3-14 Preset Relative Reference)
Forward
and 1 variable analog reference
(parameter 3-18 Relative Scaling Reference
P 3-02
Resource) in [%].
The 2 types of reference inputs are combined in the
following formula:
Sum of all
Remote reference=X+X*Y/100%.
-P 3-02 references
If relative reference is not used, set parameter 3-18 Relative
Scaling Reference Resource to [0] No function and
Reverse
parameter 3-14 Preset Relative Reference to 0%. The digital
-P 3-03
inputs on the frequency converter can activate both the
catch up/slow down function and the freeze reference
function. The functions and parameters are described in Illustration 2.14 Sum of All References When Reference Range
the VLT® Midi Drive FC 280 Programming Guide. is Set to 0
The scaling of analog references is described in parameter
groups 6-1* Analog Input 53 and 6-2* Analog Input 54, and
the scaling of digital pulse references is described in
130BA185.10
P 3-00 Reference Range =[1]-Max-Max
parameter group 5-5* Pulse Input.
Reference limits and ranges are set in parameter group 3-0* Resulting reference
Reference Limits.
P 3-03
Sum of all
references
-P 3-03
130BA186.11
P 3-00 Reference Range= [0] Min to Max
References and Feedback
Resulting reference
References and feedback are scaled from analog and pulse 2 2
inputs in the same way. The only difference is that a
reference above or below the specified minimum and
P 3-03 maximum endpoints (P1 and P2 in Illustration 2.17) are
clamped while feedbacks above or below are not.
Resource output
130BD431.10
Sum of all [Hz]
P 3-02 references
High reference/
feedback value 50 P2
The endpoints P1 and P2 are defined in Table 2.4 depending on the choice of input.
Sometimes, the reference (in rare cases also the feedback) should have a dead band around 0 to ensure that the machine is
stopped when the reference is near 0.
To make the dead band active and to set the amount of dead band, do the following:
• Set either the minimum reference value (see Table 2.4 for relevant parameter) or maximum reference value at 0. In
other words, either P1 or P2 must be on the X-axis in Illustration 2.18.
• Ensure that both points defining the scaling graph are in the same quadrant.
Resource output
130BD446.10
Quadrant 2 Quadrant 1
[Hz] or “No unit”
High reference/feedback 50 P2
value forward
P1
Resource input
Low reference/feedback 0
[mA]
value 1 16 20
Terminal X high
Terminal low
-50 reverse
Quadrant 3 Quadrant 4
Illustration 2.18 Size of Dead Band
Case 1: Positive reference with dead band, digital input to trigger reverse, part I
Illustration 2.19 shows how reference input with limits inside minimum to maximum limits clamps.
130BD454.10
General Reference General Motor
parameters: parameters:
Limited to: -200%- +200%
Reference Range: Min - Max Motor speed direction:Both directions
Minimum Reference: 0 Hz (0,0%) (-40 Hz- +40 Hz)
Maximum Reference: 20 Hz (100,0%)
Motor speed Low limit: 0 Hz
Motor speed high limit: 8 Hz 2 2
Analog input 53
Low reference 0 Hz Ext. reference Reference Limited to:
+
High reference 20 Hz Range: algorithm
0%- +100%
Low voltage 1 V 0.0% (0 Hz)
Ext. Reference (0 Hz- +20 Hz)
High voltage 10 V 100.0% (20 Hz)
Absolute
0 Hz 1 V
Ext. source 1
20 Hz 10V Reference
Range:
Range:
0.0% (0 Hz) Reference is scaled
according to min 0.0% (0 Hz)
100.0% (20 Hz)
max reference giving a 100.0% (20 Hz)
speed.!!!
Dead band
Hz
20
Scale to Hz
speed 20
V
1 10
V
1 10
Speed
setpoint
Range: -20
Digital input 19 -20 Hz
Digital input Low No reversing +20 Hz
High Reversing
Motor PID
Motor Range:
control -8 Hz Motor
+8 Hz
Illustration 2.19 Clamping of Reference Input with Limits inside Minimum to Maximum
Case 2: Positive reference with dead band, digital input to trigger reverse, part II
Illustration 2.20 shows how reference input with limits outside -maximum to +maximum limits clamps to the input low and
high limits before adding to external reference, and how the external reference is clamped to -maximum to +maximum by
2 2 the reference algorithm.
130BD433.11
General Reference General Motor
parameters: parameters:
Limited to: -200%- +200%
Reference Range: -Max - Max Motor speed direction: Both directions
Minimum Reference: Don't care (-40 Hz- +40 Hz)
Motor speed Low limit: 0 Hz
Maximum Reference: 20 Hz (100.0%) Motor speed high limit: 10 Hz
Analog input 53
Low reference 0 Hz + Ext. reference Reference Limited to:
High reference 20 Hz Range: algorithm -100%- +100%
Ext. Reference Low voltage 1 V 0.0% (0 Hz) (-20 Hz- +20 Hz)
High voltage 10 V 150.0% (30 Hz)
Absolute
0 Hz 1 V Ext. source 1
30 Hz 10 V Reference
Range:
Range:
0.0% (0 Hz) Reference is scaled
150.0% (30 Hz) according to 0.0% (0 Hz)
max reference giving a 100.0% (20 Hz)
speed.!!!
Dead band
30 Hz
Scale to
speed 20 Hz
V
1 10
V
1 10
Speed
setpoint
Range: -20 Hz
Digital input 19 -20 Hz
Digital input Low No reversing +20 Hz
High Reversing
Motor PID
Motor Range:
control –10 Hz Motor
+10 Hz
Illustration 2.20 Clamping of Reference Input with Limits outside -Maximum to +Maximum
130BD372.11
L1
L2
L3
N
PE
F1
12
91 92 93 95
27
L1 L2 L3 PE
18
50
53
55
U V W PE
32
33
96 97 98 99
M 24 Vdc
Follow the steps in Table 2.7 to program the speed control (see explanation of settings in the programming guide)
In Table 2.7, it is assumed that all other parameters and switches remain at their default setting.
Set acceptable limits for the motor speed and frequency. Parameter 4-12 Motor 0 Hz
Speed Low Limit [Hz]
Parameter 4-14 Motor 50 Hz
Speed High Limit [Hz] 2 2
Parameter 4-19 Max 60 Hz
Output Frequency
4) Configure the speed control and select the motor control principle:
Activation of speed control Parameter 1-00 Configu- [1] Speed closed loop
ration Mode
Selection of motor control principle Parameter 1-01 Motor [1] VVC+
Control Principle
5) Configure and scale the reference to the speed control:
Set up analog input 53 as a reference source. Parameter 3-15 Reference 1 Not necessary (default)
Source
Scale analog input 53 0 Hz (0 V) to 50 Hz (10 V) 6-1* Analog Input 1 Not necessary (default)
6) Configure the 24 V HTL encoder signal as feedback for the motor control and the speed control:
Set up digital input 32 and 33 as encoder inputs. Parameter 5-14 Terminal [82] Encoder input B
32 Digital Input
Parameter 5-15 Terminal [83] Encoder input A
33 Digital Input
Select terminal 32/33 as speed PID feedback. Parameter 7-00 Speed PID [1] 24 V Encoder
Feedback Source
7) Tune the speed control PID parameters:
Use the tuning guidelines when relevant or tune manually. 7-0* Speed PID Ctrl.
8) Finish:
Save the parameter setting to the LCP for safe keeping. Parameter 0-50 LCP Copy [1] All to LCP
The process PID control can be used to control application parameters that can be measured by a sensor (for example
2 2 pressure, temperature, flow) and affected by the connected motor through a pump, fan, or other connected devices.
Table 2.8 shows the control configurations in which the process control is possible. Refer to chapter 2.3 Control Structures to
see where the speed control is active.
NOTICE
The process control PID works under the default parameter setting, but tuning the parameters is recommended to
optimize the application control performance.
Process PID
130BA178.10
P 7-38
Feed forward 100%
Ref. + 0%
Handling % [unit] % % 0%
_ [unit] [speed] To motor
PID Scale to
speed control
-100%
Feedback *(-1)
Handling 100%
% [unit]
-100%
P 7-30 P 4-10
normal/inverse Motor speed
direction
Illustration 2.22 Process PID Control Diagram
130BD373.10
L1
L2
L3
Illustration 2.23 is an example of a process PID control used
2 2 in a ventilation system:
N
PE
F1
130BA218.10
Cold air
100kW
Heat 12
91 92 93 95
generating
process 27
L1 L2 L3 PE
18
50
Temperature 53
W n °C
transmitter 55
Temperature
U V W PE
54
Fan speed
96 97 98 99 Transmitter
Heat
keep the set temperature constant, use the process control. Illustration 2.24 2-wire Transmitter
2.5.5 Process Controller Optimization integration time until the feedback signal
stabilizes, followed by an increase of 15–50%.
After configuring the basic settings as described in 4. Only use parameter 7-35 Process PID Differentiation
chapter 2.5.5 Programming Order, optimize the proportional Time for fast-acting systems (differentiation time).
gain, the integration time, and the differentiation time The typical value is 4 times the set integration
(parameter 7-33 Process PID Proportional Gain, time. Use the differentiator when the setting of
parameter 7-34 Process PID Integral Time, and the proportional gain and the integration time
parameter 7-35 Process PID Differentiation Time). In most has been fully optimized. Make sure that the
processes, complete the following procedure: lowpass filter dampens the oscillations on the
feedback signal sufficiently.
1. Start the motor.
NOTICE
2. Set parameter 7-33 Process PID Proportional Gain If necessary, start/stop can be activated several times to
to 0.3 and increase it until the feedback signal provoke a variation of the feedback signal.
again begins to vary continuously. Reduce the
value until the feedback signal has stabilized.
Lower the proportional gain by 40–60%.
3. Set parameter 7-34 Process PID Integral Time to 20
s and reduce the value until the feedback signal
again begins to vary continuously. Increase the
2.5.6 Ziegler Nichols Tuning Method Type of Proportional Integral time Differentiation
control gain time
To tune the PID controls of the frequency converter, PI-control 0.45 x Ku 0.833 x Pu –
Danfoss recommends the Ziegler Nichols tuning method. PID tight 0.6 x Ku 0.5 x Pu 0.125 x Pu 2 2
control
PID some 0.33 x Ku 0.5 x Pu 0.33 x Pu
NOTICE
overshoot
Do not use the Ziegler Nichols Tuning method in
applications that could be damaged by the oscillations Table 2.11 Ziegler Nichols Tuning for Regulator
created by marginally stable control settings.
y(t)
Pu
The shield reduces the radiated interference but increases the low-frequency interference on the mains. Connect the motor
cable shield to the frequency converter enclosure and the motor enclosure. This is best done by using integrated shield
clamps to avoid twisted shield ends (pigtails). The shield clamps increase the shield impedance at higher frequencies, which
reduces the shield effect and increases the leakage current (I4).
Mount the shield on the enclosure at both ends if a shielded cable is used for the following purposes:
• Fieldbus.
• Network.
• Relay.
• Control cable.
• Signal interface.
• Brake.
In some situations, however, it is necessary to break the shield to avoid current loops.
175ZA062.12
z L1 CS CS
U
I1
z L2 V
z L3 W
z PE PE I2 CS
1
I3
2
CS CS CS
I4 I4
3 4 5 6
1 Ground cable
2 Shield
3 AC mains supply
4 Frequency converter
5 Shielded motor cable
6 Motor
If placing the shield on a mounting plate for the frequency converter, use a metal mounting plate to convey the shield
currents back to the unit. Ensure good electrical contact from the mounting plate through the mounting screws to the
frequency converter chassis.
When using unshielded cables, some emission requirements are not complied with, although the immunity requirements are
observed.
To reduce the interference level from the entire system (unit and installation), make motor and brake cables as short as 2 2
possible. Avoid placing cables with a sensitive signal level alongside mains, motor, and brake cables. Radio interference
higher than 50 MHz (airborne) is especially generated by the control electronics.
The test results in Table 2.12 have been obtained using a system with a frequency converter (with the mounting plate), a
motor, and shielded motor cables.
Filter
type
Supply voltage/Rated power Class A2/EN 55011 Class A1/EN 55011 Class B/EN 55011
(internal
)
3x380–480 V 3x200–240 V 1x200–240 V Conducted Radiated Conducted Radiated Conducted Radiated
0.37–22 kW Minimum 25 m
– – Yes1) – – – –
(0.5–30 hp) (82 ft)
0.37–4 kW Minimum 25 m
A2 filter – – Yes1) – – – –
(0.5–5.4 hp) (82 ft)
0.37–2.2 kW
– – – – – – – –
(0.5–3 hp)
0.37–7.5 kW Minimum 25 m 25 m
– – Yes1) Yes – –
(0.5–10 hp) (82 ft) (82 ft)
11–22 kW Minimum 50 m 50 m
A1 filter – – Yes1) Yes – –
(15–30 hp) (164 ft) (164 ft)
0.37–2.2 kW Minimum 40 m 40 m 15 m
– – Yes1) Yes –
(0.5–3 hp) (131 ft) (131 ft) (49.2 ft)
0.37–22 kW
A2 filter – – – – – – – –
(0.5–30 hp)
EMC
0.37–4 kW
screw – – – – – – – –
(0.5–5.4 hp)
removed
2)
0.37–2.2 kW
– – – – – – – –
(0.5–3 hp)
0.37–7.5 kW Minimum 5 m
A1 filter – – Yes1) – – – –
(0.5–10 hp) (16.4 ft)
EMC
11–22 kW Minimum 5 m
screw – – Yes1) – – – –
(15–30 hp) (16.4 ft)
removed
2)
0.37–2.2 kW Minimum 5 m
– – Yes1) – – – –
(0.5–3 hp) (16.4 ft)
The immunity requirements for frequency converters depend on the environment in which they are installed. The
2 2 requirements for the industrial environment are higher than the requirements for the home and office environment. All
Danfoss frequency converters comply with the requirements for the industrial environment. Therefore, they also comply with
the lower requirements for home and office environment with a large safety margin.
To document immunity against burst transient from electrical phenomena, the following immunity tests have been made on
a system consisting of:
• A frequency converter (with options if relevant)
• A shielded control cable
• A control box with potentiometer, motor cable, and motor.
The tests were performed in accordance with the following basic standards:
• EN 61000-4-2 (IEC 61000-4-2) Electrostatic discharges (ESD): Simulation of electrostatic discharges from human
beings.
• EN 61000-4-3 (IEC 61000-4-3) Radiated immunity: Amplitude modulated simulation of the effects of radar and
radio communication equipment and mobile communications equipment.
• EN 61000-4-4 (IEC 61000-4-4) Burst transients: Simulation of interference caused by switching a contactor, relay,
or similar devices.
• EN 61000-4-5 (IEC 61000-4-5) Surge transients: Simulation of transients caused by, for example, lightning that
strikes near installations.
• EN 61000-4-6 (IEC 61000-4-6) Conducted immunity: Simulation of the effect from radio-transmission equipment
joined by connection cables.
The immunity requirements should follow product standard IEC 61800-3 and Danfoss internal standards. See Table 2.13 for
details.
Galvanic (ensured) isolation is obtained by fulfilling Follow national and local codes regarding protective
requirements for higher isolation and by providing the grounding of equipment with a leakage current >3.5 mA.
relevant creapage/clearance distances. These requirements Frequency converter technology implies high frequency
are described in the EN 61800-5-1 standard. switching at high power. This switching generates a
leakage current in the ground connection. A fault current
in the frequency converter at the output power terminals
The components that make up the electrical isolation, as
might contain a DC component, which can charge the
shown in Illustration 2.27, also comply with the
filter capacitors and cause a transient ground current.
requirements for higher isolation and the relevant test as
The ground leakage current is made up of several contri-
described in EN 61800-5-1.
butions and depends on various system configurations
The PELV galvanic isolation can be shown in 3 locations
including RFI filtering, shielded motor cables, and
(see Illustration 2.27):
frequency converter power.
130BB955.12
Leakage current
terminals must be PELV, for example, the thermistor must
be reinforced/double insulated. a
130BD447.11
4 3 2 1
b
The leakage current also depends on the line distortion. RCD with low f cut-
130BB958.12
Leakage current
130BB956.12
Leakage current
2 2
THDv=0%
130BB957.11
Leakage current [mA]
100 Hz
NOTICE
High leakage current may cause the RCDs to switch off.
To avoid this problem, remove the RFI screw when a
filter is being charged.
130BA167.10
Load
The threshold can be adjusted in parameter 2-14 Brake 2.9.4 Control with Brake Function
voltage reduce, with 70-V range.
The brake is protected against short-circuiting of the brake
2 2 NOTICE resistor, and the brake transistor is monitored to ensure
Make sure that the brake resistor can cope with a that short-circuiting of the transistor is detected. A relay/
voltage of 410 V or 800 V. digital output can be used for protecting the brake resistor
from overloading caused by a fault in the frequency
converter.
Danfoss recommends calculating the brake resistance Rrec
In addition, the brake enables readout of the momentary
according to the following formula. The recommended
power and the mean power for the latest 120 s. The brake
brake resistance guarantees that the frequency converter is
can also monitor the power energizing and make sure that
able to brake at the highest braking torque (Mbr(%)) of
it does not exceed a limit selected in parameter 2-12 Brake
160%.
Power Limit (kW).
130BB671.13
Par. 13-52
SL Controller Event SL Controller Action Comparators are used for comparing continuous variables
(for example output frequency, output current, and analog
Running
Warning
Coast input) to fixed preset values. 2 2
Start timer
130BB672.10
Torque limit Set Do X low Par. 13-11
Digital input X 30/2 Select set-up 2 Comparator Operator
... ... Par. 13-10
Comparator Operand
Par. 13-43 =
Logic Rule Operator 2 TRUE longer than.
Par. 13-12
Comparator Value ...
...
Par. 13-11
Comparator Operator Logic rules
Combine up to 3 boolean inputs (true/false inputs) from
= timers, comparators, digital inputs, status bits, and events
TRUE longer than..
using the logical operators and, or, and not.
...
...
130BB673.10
Par. 13-41 Par. 13-43
Logic Rule Operator 1 Logic Rule Operator 2
Par. 13-40
Logic Rule Boolean 1
Illustration 2.33 Associated Action
Par. 13-42
Logic Rule Boolean 2 ...
... ...
...
Events and actions are each numbered and linked in pairs
(states). This means that when event [0] is fulfilled (attains Par. 13-44
Logic Rule Boolean 3
the value TRUE), action [0] is executed. After this, the
Illustration 2.36 Logic Rules
conditions of event [1] are evaluated and if evaluated true,
action [1] is executed, and so on. Only 1 event is evaluated
at any time. If an event is evaluated as false, nothing
happens (in the SLC) during the current scan interval, and 2.11 Extreme Running Conditions
no other events are evaluated. When the SLC starts, it
evaluates event [0] (and only event [0]) each scan interval. Short circuit (motor phase-to-phase)
Only when event [0] is evaluated true, the SLC executes The frequency converter is protected against short circuits
action [0] and starts evaluating event [1]. It is possible to by current measurement in each of the 3 motor phases or
program 1–20 events and actions. in the DC link. A short circuit between 2 output phases
When the last event/action has been executed, the causes an overcurrent in the frequency converter. The
sequence starts over again from event [0]/action [0]. frequency converter is turned off individually when the
Illustration 2.34 shows an example with 3 event/actions: short circuit current exceeds the permitted value (alarm 16,
Trip lock).
Switching on the output
130BA062.14
Start
event P13-01
Switching on the output between the motor and the
State 1 frequency converter is fully allowed, and does not damage
13-51.0
13-52.0 State 2 the frequency converter. However, fault messages may
Stop 13-51.1
event P13-02 13-52.1 appear.
Stop
event P13-02
State 4
13-51.3
13-52.3
State 3
13-51.2
13-52.2
Stop
event P13-02
Illustration 2.34 Sequence with 3 Events/Actions
175ZA052.12
Mains drop-out t [s]
During a mains drop-out, the frequency converter keeps
2000
running until the DC-link voltage drops below the
minimum stop level, which is: 1000
600
• 314 V for 3x380–480 V. 500
400
• 202 V for 3x200–240 V. 300
200
• 225 V for 1x200–240 V.
100 fOUT = 1 x f M,N(par. 1-23)
fOUT = 2 x f M,N
The mains voltage before the drop-out and the motor load 60
determines how long it takes for the inverter to coast. 50 fOUT = 0.2 x f M,N
40
Static overload in VVC+ mode 30
When the frequency converter is overloaded, the torque 20 IM
10
limit in parameter 4-16 Torque Limit Motor Mode/ 1.0 1.2 1.4 1.6 1.8 2.0 IMN(par. 1-24)
parameter 4-17 Torque Limit Generator Mode is reached, the
Illustration 2.37 ETR
control unit reduces the output frequency to reduce the
load.
If the overload is excessive, a overcurrent which makes the
frequency converter cut out after approximately 5–10 s The X-axis shows the ratio between Imotor and Imotor
may occur. nominal. The Y-axis shows the time in seconds before the
ETR cuts off and trips the frequency converter. The curves
Operation within the torque limit is limited in time (0–60 s) show the characteristic nominal speed at twice the
in parameter 14-25 Trip Delay at Torque Limit. nominal speed and at 0.2 x the nominal speed.
At lower speed, the ETR cuts off at lower heat due to less
2.11.1 Motor Thermal Protection cooling of the motor. In that way, the motor is protected
from being overheated even at low speed. The ETR feature
To protect the application from serious damage, VLT® Midi calculates the motor temperature based on actual current
Drive FC 280 offers several dedicated features. and speed. The calculated temperature is visible as a
readout parameter in parameter 16-18 Motor Thermal.
Torque limit
The torque limit protects the motor from being overloaded
independent of the speed. Torque limit is controlled in
parameter 4-16 Torque Limit Motor Mode and
parameter 4-17 Torque Limit Generator Mode.
Parameter 14-25 Trip Delay at Torque Limit controls the time
before the torque limit warning trips.
3 Application Examples
3.1 Introduction
130BE806.10
CW
A
3.1.1 Encoder Connection B 3 3
The purpose of this guideline is to ease the set-up of
encoder connection to the frequency converter. Before Z
setting up the encoder, the basic settings for a closed-loop
speed control system are shown.
CCW
A
130BE805.10
+24 V DC
+24 V DC
GND
B
A
Z
12 13 18 19 27 29 32 33 55
Z
3.2.2 Speed
130BE728.10
Parameters
Function Setting
130BE204.11
FC
Parameter 6-10 T
+24 V 12
3 3 +24 V 13
erminal 53 Low
Voltage
0.07 V*
D IN 18
Parameter 6-11 T
D IN 19
erminal 53 High 10 V*
D IN 27
Voltage
D IN 29
Parameter 6-14 T
D IN 32
33
erminal 53 Low 0
D IN
Brake resistor Ref./Feedb. Value
Parameter 6-15 T
erminal 53 High 50
+10 V 50
+ Ref./Feedb. Value
Transmission A IN 53
A IN 54 Parameter 6-19 T
[1] Voltage
COM 55 erminal 53 mode
-
A OUT 42 *=Default value
0 ~10 V
Notes/comments:
Motor Gearbox
Illustration 3.3 Basic Set-up for Closed-loop Speed Control Table 3.2 Analog Speed Reference (Voltage)
Parameters
3.2 Application Examples 130BE205.11 Function Setting
FC Parameter 6-22 T
3.2.1 AMA +24 V 12 erminal 54 Low 4 mA*
+24 V 13 Current
Parameters D IN 18
Parameter 6-23 T
D IN 19
Function Setting erminal 54 High 20 mA*
130BE203.11
FC D IN 27
Parameter 1-29 A Current
+24 V 12 [1] Enable D IN 29
utomatic Motor Parameter 6-24 T
+24 V 13 complete D IN 32
Adaptation erminal 54 Low 0*
D IN 18 AMA D IN 33
(AMA) Ref./Feedb. Value
D IN 19
D IN 27 Parameter 5-12 T Parameter 6-25 T
*[2] Coast
D IN 29 erminal 27 erminal 54 High 50
inverse +10 V 50
D IN 32 Digital Input + Ref./Feedb. Value
A IN 53
D IN 33 *=Default value Parameter 6-29 T
A IN 54 [0] current
Notes/comments: Set COM 55 erminal 54 mode
parameter group 1-2* Motor -
A OUT 42 *=Default value
4 - 20mA
+10 V 50 Data according to motor Notes/comments:
A IN 53 specifications.
A IN 54 NOTICE
COM 55
If terminal 12 and 27 are
A OUT 42 Table 3.3 Analog Speed Reference (Current)
not connected, set
parameter 5-12 Terminal 27
Digital Input to [0] No
operation.
Parameters
130BB840.11
Function Setting
130BE208.11
FC
Parameter 6-10 T
+24 V 12 Speed
erminal 53 Low 0.07 V*
+24 V 13
Voltage Reference
D IN 18
Parameter 6-11 T
D IN
D IN
19
27 erminal 53 High 10 V*
Start ( 18)
3 3
D IN 29 Voltage
D IN 32 Parameter 6-14 T Freeze ref ( 27)
Ref./Feedb. Value
Speed down ( 32 )
Parameter 6-15 T
+10 V 50 erminal 53 High 50
A IN 53 ≈ 5kΩ Ref./Feedb. Value
A IN 54 Parameter 6-19 T Illustration 3.4 Speed Up/Speed Down
[1] voltage
COM 55 erminal 53 mode
A OUT 42 *=Default value
Notes/comments: 3.2.3 Start/Stop
Parameters
Function Setting
130BE206.11
FC
Table 3.4 Speed Reference (Using a Manual Potentiometer) Parameter 5-10 Ter
+24 V 12
+24 V 13 minal 18 Digital [8] Start
Parameters Input
D IN 18
Function Setting
130BE209.11
Parameters Parameters
Function Setting
130BE211.11
Function Setting
130BE207.11
FC FC Parameter 4-30
Parameter 5-11 T +24 V 12 Motor Feedback [1] Warning
+24 V 12
3 3 +24 V
D IN
13
18
erminal 19
Digital Input
[1] Reset +24 V
D IN
13
18
Loss Function
Parameter 4-31
*=Default value Motor Feedback 50
D IN 19 D IN 19
Speed Error
D IN 27 Notes/comments: D IN 27
Parameter 4-32
D IN 29 D IN 29 Motor Feedback 5 s
D IN 32 D IN 32 Loss Timeout
D IN 33 D IN 33 Parameter 7-00 S
[1] 24 V
peed PID
encoder
Feedback Source
Parameter 5-70 T
+10 V 50 erm 32/33 Pulses 1024*
+10 V 50
A IN
A IN 53 Per Revolution
53
A IN 54 Parameter 13-00
A IN 54
COM 55
SL Controller [1] On
COM 55 Mode
A OUT A OUT 42
42 Parameter 13-01
[19] Warning
Start Event
Parameter 13-02
[44] Reset key
01 Stop Event
Parameter 13-10
R1
02 [21] Warning
03 Comparator
Table 3.7 External Alarm Reset no.
Operand
Parameter 13-11
Comparator *[1] ≈
3.2.5 Motor Thermistor Operator
Parameter 13-12
NOTICE Comparator
Value
61
The Safe Torque Off (STO) function is a component in a Terminal 37 Terminal 38 Torque Warning or
safety control system. STO prevents the unit from alarm
generating the energy that is required to rotate the motor, Energized1) Energized Yes2) No warnings or
thus ensuring safety in emergency situations. alarms.
De-energized3) De-energized No Warning/alarm
The STO function is designed and approved suitable for 68: Safe Torque
Off.
4 4
the requirements of:
• IEC/EN 61508: 2010 SIL2 De-energized Energized No Alarm 188: STO
Function Fault.
• IEC/EN 61800-5-2: 2007 SIL2
Energized De-energized No Alarm 188: STO
• IEC/EN 62061: 2012 SILCL of SIL2 Function Fault.
• EN ISO 13849-1: 2008 Category 3 PL d
Table 4.1 STO Status
To achieve the required level of operational safety, select
1) Voltage range is 24 V ±5 V, with terminal 55 as the reference
and apply the components in the safety control system
terminal.
appropriately. Before using STO, carry out a thorough risk
2) Torque is present only when the frequency converter is operating.
analysis on the installation to determine whether the STO
3) Open circuit, or the voltage within the range of 0 V ±1.5 V, with
function and safety levels are appropriate and sufficient.
terminal 55 as the reference terminal.
The STO function in the frequency converter is controlled Test pulse filtering
via control terminals 37 and 38. When STO is activated, the For safety devices that generate test pulses on the STO
power supply on the high side and low side of the IGBT control lines: If the pulse signals stay at low level (≤1.8 V)
gate driving circuits is cut off. Illustration 4.1 shows the STO for no longer than 5 ms, they are ignored, as shown in
architecture. Table 4.1 shows STO statuses based on Illustration 4.2.
whether terminals 37 and 38 are energized.
130BE587.12
T37/38 5 ms max. Test pulse STO demanded
130BE463.12
Voltage
+UDC
24 V
24 V
12 voltage IGBT
source high-side X3
gate driving
circuit
Time
38
17 V X3 STO request Debounce time
diagnostic
circuit state
37 IGBT
STO valid
X3
low-side
gate driving
circuit
55
STO invalid
Time
Illustration 4.2 Test Pulse Filtering
PELV
130BE213.10
Qualified personnel
Only qualified personnel are allowed to install or operate
this equipment.
Qualified personnel are defined as trained staff, who are
authorized to install, commission, and maintain equipment,
systems, and circuits in accordance with pertinent laws and
regulations. Also, the personnel must be familiar with the
4 4 instructions and safety measures described in this manual.
NOTICE
After installation of STO, perform a commissioning test
as specified in chapter 4.3.3 STO Commissioning Test. A
passed commissioning test is mandatory after first instal-
lation and after each change to the safety installation.
WARNING
RISK OF ELECTRICAL SHOCK Illustration 4.3 Jumper between Terminal 12 (24 V), 37, and 38
The STO function does NOT isolate mains voltage to the
frequency converter or auxiliary circuits, and therefore
does not provide electrical safety. Failure to isolate the 2. Connect a dual-channel safety device (for
mains voltage supply from the unit and wait the time example safety PLC, light curtain, safety relay, or
specified could result in death or serious injury. emergency stop button) to terminals 37 and 38
to form a safety application. The device must
• Perform work on electrical parts of the
comply with the required safety level based on
frequency converter or the motor only after
the hazard assessment. Illustration 4.4 shows the
isolating the mains voltage supply and waiting
wiring schematic of STO applications where the
the discharge time specified in chapter Safety
frequency converter and the safety device are in
Precautions in the VLT® Midi Drive FC 280 the same cabinet. Illustration 4.5 shows the wiring
Operating Guide. schematic of STO applications where external
supply is used.
NOTICE NOTICE
When designing the machine application, consider the The STO signal must be PELV supplied.
timing and distance for a coast to stop (STO). For more
information regarding stop categories, refer to EN 1 130BE424.11
60204-1.
37
130BE425.12
1
+
37
38 24 V source
WARNING
RISK OF INJURY OR DEATH
1 Safety device Reapplying 24 V DC supply to either terminal 37 or 38 4 4
terminates the SIL2 STO state, potentially starting the
Illustration 4.5 STO Wiring, External Supply motor. Unexpected motor start may cause personal
injuries or death.
• Ensure that all safety measures are taken before
3. Complete the wiring according to the instructions reapplying 24 V DC supply to terminals 37 and
in chapter 2.2.1 Electrical Installation, and: 38.
• Eliminate short circuit risks.
• Ensure that the STO cables are shielded Restart Steps to deactivate STO Restart mode configu-
if they are longer than 20 m (65.6 ft) or mode and resume normal ration
outside the cabinet. operation
Manual 1. Reapply 24 V DC Default setting.
• Connect the safety device directly to
restart supply to terminals 37 Parameter 5-19 Terminal
terminals 37 and 38.
and 38. 37/38 Safe Torque Off=[1]
4.3 STO Commissioning 2. Initiate a reset signal Safe Torque Off Alarm
4.3.4 Test for STO Applications in Manual 4. Ensure that the motor becomes operational and
Restart Mode runs within the original speed range.
The commissioning test is successfully completed when all
For applications where parameter 5-19 Terminal 37/38 Safe the above-mentioned steps are passed.
Torque Off is set to the default value [1] Safe Torque Off
Alarm, conduct the commissioning test as follows. NOTICE
See the warning on the restart behavior in
1. Set parameter 5-40 Function Relay to [190] Safe chapter 4.1 Safety Precautions for STO.
Function active.
4 4 2. Remove the 24 V DC voltage supply to terminals 4.4 Maintenance and Service for STO
37 and 38 using the safety device while the
frequency converter drives the motor (that is, the
• The user is responsible for security measures.
3. Reapply 24 V supply to terminal 37, and verify mounted, verify that alarm 188, STO Function Fault
that resetting the alarm is successful. is logged in parameter 15-30 Alarm Log: Error
Code.
4. Remove the 24 V supply for terminal 38 and
verify that the LCP shows alarm 188, STO Function 5. Reapply 24 V supply to terminal 38 and verify
Fault if the LCP is mounted. If the LCP is not that resetting the alarm is successful.
5.1 Introduction
5.1.1 Overview
RS485 is a 2-wire bus interface compatible with multi-drop network topology. The nodes can be connected as a bus, or via
drop cables from a common trunk line. A total of 32 nodes can be connected to 1 network segment.
Repeaters divide network segments, see Illustration 5.1.
5 5
130BB795.10
61 68 69
The default selection depends on the
COMM. GND
P
N protocol selected in
parameter 8-30 Protocol.
The physical layer is RS485, thus utilizing the RS485 port 5.4 FC Protocol Message Framing Structure
built into the frequency converter. The FC protocol
supports different telegram formats: 5.4.1 Content of a Character (byte)
• A short format of 8 bytes for process data. Each character transferred begins with a start bit. Then 8
data bits are transferred, corresponding to a byte. Each
• A long format of 16 bytes that also includes a
character is secured via a parity bit. This bit is set at 1
parameter channel.
when it reaches parity. Parity is when there are an equal
• A format used for texts. number of 1s in the 8 data bits and the parity bit in total.
A stop bit completes a character, consisting of 11 bits in
5.2.2 FC with Modbus RTU all.
195NA036.10
bus reference of the frequency converter.
Start 0 1 2 3 4 5 6 7 Even Stop
bit Parity bit
The control word allows the Modbus master to control
Illustration 5.3 Content of a Character
several important functions of the frequency converter:
• Start.
• Stop of the frequency converter in various ways: 5.4.2 Telegram Structure
- Coast stop.
- Quick stop. Each telegram has the following structure:
• Start character (STX)=02 hex.
- DC brake stop.
• A byte denoting the telegram length (LGE).
- Normal (ramp) stop.
• A byte denoting the frequency converter address
• Reset after a fault trip. (ADR).
• Run at various preset speeds. Several data bytes (variable, depending on the type of
• Run in reverse. telegram) follow.
195NA099.10
The bus reference is commonly used for speed control. It is
also possible to access the parameters, read their values,
STX LGE ADR DATA BCC
and where possible, write values to them. Accessing the
parameters offers a range of control options, including Illustration 5.4 Telegram Structure
controlling the setpoint of the frequency converter when
its internal PI controller is used.
To enable the FC protocol for the frequency converter, set The telegram length is the number of data bytes plus the
the following parameters. address byte ADR and the data control byte BCC.
130BB918.10
PKE IND PWEhigh PWElow
The slave returns the address byte unchanged to the
master in the response telegram.
Parameter
commands
and replies
Parameter
5.4.6 The Data Field
number
The structure of data blocks depends on the type of
Illustration 5.8 PKE Field
telegram. There are 3 telegram types, and the type applies
for both control telegrams (master⇒slave) and response
telegrams (slave⇒master).
Bits 12–15 transfer parameter commands from master to
slave and return processed slave responses to the master.
The 3 types of telegram are:
STX LGE ADR PKE IND PWEhigh PWElow PCD1 PCD2 BCC
15 14 13 12
0 0 0 0 No response.
Illustration 5.6 Parameter Block
0 0 0 1 Parameter value transferred (word).
0 0 1 0 Parameter value transferred (double
word).
Text block
0 1 1 1 Command cannot be performed.
The text block is used to read or write texts via the data
1 1 1 1 Text transferred.
block.
Table 5.6 Response
130BA270.10
STX LGE ADR PKE IND Ch1 Ch2 Chn PCD1 PCD2 BCC
Illustration 5.7 Text Block If the command cannot be performed, the slave sends this
response 0111 Command cannot be performed and issues
the following fault report in Table 5.7.
Fault code FC specification parameter 0-01 Language, select the data value by entering
0 Illegal parameter number. the value in the PWE block. Serial communication is only
1 Parameter cannot be changed. capable of reading parameters containing data type 9 (text
2 Upper or lower limit is exceeded. string).
3 Subindex is corrupted.
4 No array. Parameter 15-40 FC Type to parameter 15-53 Power Card
5 Wrong data type. Serial Number contain data type 9.
6 Not used. For example, read the unit size and mains voltage range in
7 Not used. parameter 15-40 FC Type. When a text string is transferred
9 Description element is not available.
(read), the length of the telegram is variable, and the texts
are of different lengths. The telegram length is defined in
11 No parameter write access.
the 2nd byte of the telegram (LGE). When using text
5 5 15
17
No text available.
Not applicable while running.
transfer, the index character indicates whether it is a read
or a write command.
18 Other errors.
100 –
To read a text via the PWE block, set the parameter
>100 –
command (AK) to F hex. The index character high-byte
130 No bus access for this parameter.
must be 4.
131 Write to factory set-up is not possible.
132 No LCP access.
252 Unknown viewer.
5.4.11 Data Types Supported by the
253 Request is not supported.
Frequency Converter
254 Unknown attribute.
Unsigned means that there is no operational sign in the
255 No error.
telegram.
Table 5.7 Slave Report
Data types Description
5.4.8 Parameter Number (PNU) 3 Integer 16
4 Integer 32
Bits 0–11 transfer parameter numbers. The function of the 5 Unsigned 8
relevant parameter is defined in the parameter description 6 Unsigned 16
in the VLT® Midi Drive FC 280 Programming Guide. 7 Unsigned 32
9 Text string
5.4.10 Parameter Value (PWE) Parameter 4-12 Motor Speed Low Limit [Hz] has a conversion
factor of 0.1. To preset the minimum frequency to 10 Hz,
The parameter value block consists of 2 words (4 bytes), transfer the value 100. A conversion factor of 0.1 means
and the value depends on the defined command (AK). The that the value transferred is multiplied by 0.1. The value
master prompts for a parameter value when the PWE block 100 is thus perceived as 10.0.
contains no value. To change a parameter value (write),
write the new value in the PWE block and send from the
master to the slave.
130BA093.10
119E H 0000 H 0000 H 03E8 H
Table 5.9 Conversion
PKE IND PWE high PWE low 5 5
5.4.13 Process Words (PCD) Illustration 5.10 Response from Master
PCD 1 PCD 2 Read the value in parameter 3-41 Ramp 1 Ramp Up Time.
Control telegram (master⇒slave control word) Reference value
Control telegram (slave⇒master) status word Present output PKE = 1155 hex - Read parameter value in
frequency parameter 3-41 Ramp 1 Ramp Up Time:
• IND = 0000 hex.
Table 5.10 Process Words (PCD)
• PWEHIGH = 0000 hex.
5.5 Examples • PWELOW = 0000 hex.
130BA094.10
5.5.1 Writing a Parameter Value
1155 H 0000 H 0000 H 0000 H
PKE = E19E hex - Write single word in If the value in parameter 3-41 Ramp 1 Ramp Up Time is 10
parameter 4-14 Motor Speed High Limit [Hz]: s, the response from the slave to the master is shown in
• IND = 0000 hex. Illustration 5.12.
Data value 1000, corresponding to 100 Hz, see PKE IND PWE high PWE low
chapter 5.4.12 Conversion.
Illustration 5.12 Response
Coil 0 1
33 Control not ready Control ready
34 Frequency converter not Frequency converter ready
ready
35 Coast stop Safety closed
36 No alarm Alarm
37 Not used Not used
38 Not used Not used
39 Not used Not used
40 No warning Warning
41 Not at reference At reference
42
43
Hand mode
Out of frequency range
Auto mode
In frequency range
5 5
44 Stopped Running
45 Not used Not used
46 No voltage warning Voltage warning
47 Not in current limit Current limit
48 No thermal warning Thermal warning
Table 5.20 Function Codes The PNU (parameter number) is translated from the
register address contained in the Modbus read or write
5.8.11 Modbus Exception Codes telegram. The parameter number is translated to Modbus
as (10 x parameter number) decimal.
For a full explanation of the structure of an exception code
response, refer to chapter 5.8.5 Function Field. Examples
Reading parameter 3-12 Catch up/slow Down Value (16 bit):
The holding register 3120 holds the parameters value. A
value of 1352 (decimal), means that the parameter is set to
12.52%.
Reading parameter 3-14 Preset Relative Reference (32 bit):
The holding registers 3410 and 3411 hold the parameters
values. A value of 11300 (decimal), means that the
parameter is set to 1113.00.
For information on the parameters, size, and conversion
index, see the VLT® Midi Drive FC 280 Programming Guide.
5.10 Examples
The following examples show various Modbus RTU
commands.
5.10.2 Force/Write Single Coil (05 hex) Field name Example (hex)
Slave address 01 (frequency converter address)
Description Function 0F (write multiple coils)
This function forces the coil to either ON or OFF. When Coil address HI 00
broadcast, the function forces the same coil references in Coil address LO 10 (coil address 17)
all attached slaves. Quantity of coils HI 00
Query Quantity of coils LO 10 (16 coils)
The query telegram specifies the coil 65 (parameter write Byte count 02
control) to be forced. Coil addresses start at 0, that is, coil Force data HI 20
65 is addressed as 64. Force data = 00 00 hex (OFF) or FF (Coils 8–1)
00 hex (ON). Force data LO 00 (reference=2000 hex)
Response
The normal response is an echo of the query, returned
after the register contents have been passed.
130BA274.11
Master-follower Bit 03, Coasting
CTW Speed ref. Bit 03=0: The frequency converter immediately releases the
motor (the output transistors are shut off), and it coasts to
a standstill.
Bit
no.: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Bit 03=1: If the other starting conditions are met, the
frequency converter starts the motor.
Illustration 5.13 Control Word According to FC Profile
5 5 In parameter 8-50 Coasting Select, define how bit 03 gates
with the corresponding function on a digital input.
Bit Bit value=0 Bit value=1 Bit 04, Quick stop
00 Reference value External selection lsb Bit 04=0: Makes the motor speed ramp down to stop (set
01 Reference value External selection msb in parameter 3-81 Quick Stop Ramp Time).
02 DC brake Ramp
Bit 05, Hold output frequency
03 Coasting No coasting Bit 05=0: The present output frequency (in Hz) freezes.
04 Quick stop Ramp Change the frozen output frequency only with the digital
05 Hold output Use ramp inputs programmed to [21] Speed up and [22] Speed down
frequency (parameter 5-10 Terminal 18 Digital Input to
06 Ramp stop Start parameter 5-13 Terminal 29 Digital Input).
07 No function Reset
08 No function Jog
NOTICE
09 Ramp 1 Ramp 2
If freeze output is active, the frequency converter can
only be stopped by 1 of the following:
10 Data invalid Data valid
11 Relay 01 open Relay 01 active • Bit 03 Coasting stop.
12 Relay 02 open Relay 02 active • Bit 02 DC braking.
13 Parameter set-up Selection lsb
15 No function Reverse
• Digital input programmed to [5] DC-brake
inverse, [2] Coast inverse, or [3] Coast and reset
Table 5.34 Control Word According to FC Profile inv (parameter 5-10 Terminal 18 Digital Input to
parameter 5-13 Terminal 29 Digital Input).
Explanation of the control bits
Bits 00/01
Bits 00 and 01 are used to select among the 4 reference Bit 06, Ramp stop/start
values, which are preprogrammed in parameter 3-10 Preset Bit 06=0: Causes a stop and makes the motor speed ramp
Reference according to Table 5.35. down to stop via the selected ramp-down parameter.
Bit 06=1: Allows the frequency converter to start the motor
Programmed Parameter Bit Bit
if the other starting conditions are met.
reference 01 00
value In parameter 8-53 Start Select, define how bit 06 ramp stop/
1 Parameter 3-10 Preset Reference [0] 0 0 start gates with the corresponding function on a digital
2 Parameter 3-10 Preset Reference [1] 0 1
input.
3 Parameter 3-10 Preset Reference [2] 1 0 Bit 07, Reset
4 Parameter 3-10 Preset Reference [3] 1 1 Bit 07=0: No reset.
Bit 07=1: Resets a trip. Reset is activated on the leading
Table 5.35 Control Bits signal edge, that is, when changing from logic 0 to logic 1.
Bit 08, Jog
NOTICE Bit 08=1: Parameter 3-11 Jog Speed [Hz] determines the
In parameter 8-56 Preset Reference Select, define how bit output frequency.
00/01 gates with the corresponding function on the
Bit 09, Selection of ramp 1/2
digital inputs.
Bit 09=0: Ramp 1 is active (parameter 3-41 Ramp 1 Ramp
Up Time to parameter 3-42 Ramp 1 Ramp Down Time).
Bit 09=1: Ramp 2 (parameter 3-51 Ramp 2 Ramp Up Time to
parameter 3-52 Ramp 2 Ramp Down Time) is active.
Follower-master
Bit 05 is not used in the status word.
STW Output freq. Bit 06, No error/triplock
Bit 06=0: The frequency converter is not in fault mode.
Bit 06=1: The frequency converter is tripped and locked.
Bit
no.: 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit 07, No warning/warning
Illustration 5.14 Status Word Bit 07=0: There are no warnings.
Bit 07=1: A warning has occurred.
130BA276.11
Master-slave
16bit
Speed reference value is transmitted to the frequency CTW Speed reference
converter in a relative value in %. The value is transmitted
in the form of a 16-bit word. The integer value 16384 Follower-slave
(4000 hex) corresponds to 100%. Negative figures are Actual output
STW
formatted using 2’s complement. The actual output frequency
frequency (MAV) is scaled in the same way as the bus
Illustration 5.15 Actual Output Frequency (MAV)
reference.
130BA277.10
-100% 0% 100%
Par.3-00 set to
Reverse Forward
(1) -max- +max
Par.3-03 0 Par.3-03
0% 100%
(0hex) (4000hex)
Par.3-00 set to
Forward
(0) min-max
Par.3-02 Par.3-03
FC 280 Pm (HO) Rmin Rbr. nom Rrec Pbr avg Ordering Period Cable Thermal Maximum
number cross- relay brake torque
section1) with Rrec
T4 [kW (hp)] [Ω] [Ω] [Ω] [kW (hp)] 175Uxxxx [s] [mm2 [A] [%]
(AWG)]
0.030
PK37 0.37 (0.5) 890 1041.98 989 3000 120 1.5 (16) 0.3 139
(0.04)
0.045
6 6
PK55 0.55 (0.75) 593 693.79 659 3001 120 1.5 (16) 0.4 131
(0.06)
0.061
PK75 0.75 (1.0) 434 508.78 483 3002 120 1.5 (16) 0.4 129
(0.08)
0.092
P1K1 1.1 (1.5) 288 338.05 321 3004 120 1.5 (16) 0.5 132
(0.12)
0.128
P1K5 1.5 (2.0) 208 244.41 232 3007 120 1.5 (16) 0.8 145
(0.172)
0.190
P2K2 2.2 (3.0) 139 163.95 155 3008 120 1.5 (16) 0.9 131
(0.255)
0.262
P3K0 3 (4.0) 100 118.86 112 3300 120 1.5 (16) 1.3 131
(0.351)
0.354
P4K0 4 (5.0) 74 87.93 83 3335 120 1.5 (16) 1.9 128
(0.475)
0.492
P5K5 5.5 (7.5) 54 63.33 60 3336 120 1.5 (16) 2.5 127
(0.666)
0.677
P7K5 7.5 (10) 38 46.05 43 3337 120 1.5 (16) 3.3 132
(0.894)
0.945
P11K 11 (15) 27 32.99 31 3338 120 1.5 (16) 5.2 130
(1.267)
1.297
P15K 15 (20) 19 24.02 22 3339 120 1.5 (16) 6.7 129
(1.739)
1.610
P18K 18.5 (25) 16 19.36 18 3340 120 1.5 (16) 8.3 132
(2.158)
1.923
P22K 22 (30) 16 18.00 17 3357 120 1.5 (16) 10.1 128
(2.578)
FC 280 Pm (HO) Rmin Rbr. nom Rrec Pbr avg Ordering Period Cable Thermal Maximum
number cross- relay brake torque
section1) with Rrec
T4 [kW (hp)] [Ω] [Ω] [Ω] [kW (hp)] 175Uxxxx [s] [mm2] [A] [%]
0.127
PK37 0.37 (0.5) 890 1041.98 989 3101 120 1.5 (16) 0.4 139
(0.170)
0.191
PK55 0.55 (0.75) 593 693.79 659 3308 120 1.5 (16) 0.5 131
(0.256)
0.260
PK75 0.75 (1.0) 434 508.78 483 3309 120 1.5 (16) 0.7 129
(0.349)
0.391
P1K1 1.1 (1.5) 288 338.05 321 3310 120 1.5 (16) 1 132
(0.524)
0.807
P2K2 2.2 (3.0) 139 163.95 155 3312 120 1.5 (16) 2.1 131
(1.082)
1.113
P3K0 3 (4.0) 100 118.86 112 3313 120 1.5 (16) 2.7 131
(1.491)
1.504
P4K0 4 (5.0) 74 87.93 83 3314 120 1.5 (16) 3.7 128
(2.016)
2.088
P5K5 5.5 (7.5) 54 63.33 60 3315 120 1.5 (16) 5 127
(2.799)
2.872
P7K5 7.5 (10) 38 46.05 43 3316 120 1.5 (16) 7.1 132
(3.850)
4.226
P11K 11 (15) 27 32.99 31 3236 120 2.5 (14) 11.5 130
(5.665)
5.804
P15K 15 (20) 19 24.02 22 3237 120 2.5 (14) 14.7 129
(7.780)
7.201
P18K 18.5 (25) 16 19.36 18 3238 120 4 (12) 19 132
(9.653)
8.604
P22K 22 (30) 16 18.00 17 3203 120 4 (12) 23 128
(11.534)
7 Specifications
Weight enclosure protection rating IP20 [kg (lb)] 3.6 (7.9) 3.6 (7.9) 4.1 (9.0) 9.4 (20.7) 9.5 (20.9) 12.3 (27.1) 12.5 (27.6)
Efficiency [%]2) 97.6 97.7 98.0 97.8 97.8 98.1 97.9
Torque characteristics
Starting torque (constant torque) Maximum 160% for 60 s1)
Overload torque (constant torque) Maximum 160% for 60 s1)
Starting current Maximum 200% for 1 s
Torque rise time in VVC+ mode (independent of fsw) Maximum 50 ms
1) Percentage relates to the nominal torque.
STO inputs
Terminal number 37, 38
Voltage level 0–30 V DC
Voltage level, low <1.8 V DC
Voltage level, high >20 V DC
Maximum voltage on input 30 V DC
Minimum input current (each pin) 6 mA
Analog inputs
Number of analog inputs 2
Terminal number 531),
54
Modes Voltage or current
Mode select Software
Voltage level 0–10 V
Input resistance, Ri Approximately 10 kΩ
Maximum voltage -15 V to +20 V
Current level 0/4 to 20 mA (scaleable)
Input resistance, Ri Approximately 200 Ω
Maximum current 30 mA
Resolution for analog inputs 11 bit
Accuracy of analog inputs Maximum error 0.5% of full scale
Bandwidth 100 Hz
The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminal 53 supports only voltage mode and can also be used as digital input.
130BE837.10
PELV isolation
37
Control Mains
38
High
voltage Motor
33
Functional
isolation
RS485 DC bus
NOTICE
HIGH ALTITUDE
For installation at altitudes above 2000 m (6562 ft), contact Danfoss hotline regarding PELV.
Pulse inputs
Programmable pulse inputs 2 7 7
Terminal number pulse 29, 33
Maximum frequency at terminal 29, 33 32 kHz (push-pull driven)
Maximum frequency at terminal 29, 33 5 kHz (open collector)
Minimum frequency at terminal 29, 33 4 Hz
Voltage level See the section on digital input
Maximum voltage on input 28 V DC
Input resistance, Ri Approximately 4 kΩ
Pulse input accuracy (4–32 kHz) Maximum error: 0.1% of full scale
Digital outputs
Programmable digital/pulse outputs 1
Terminal number 271)
Voltage level at digital/frequency output 0–24 V
Maximum output current (sink or source) 40 mA
Maximum load at frequency output 1 kΩ
Maximum capacitive load at frequency output 10 nF
Minimum output frequency at frequency output 4 Hz
Maximum output frequency at frequency output 32 kHz
Accuracy of frequency output Maximum error: 0.1% of full scale
Resolution of frequency output 10 bit
1) Terminal 27 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Analog outputs
Number of programmable analog outputs 1
Terminal number 42
Current range at analog output 0/4–20 mA
Maximum resistor load to common at analog output 500 Ω
Accuracy on analog output Maximum error: 0.8% of full scale
Resolution on analog output 10 bit
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Relay outputs
Programmable relay outputs 1
Relay 01 01–03 (NC), 01–02 (NO)
Maximum terminal load (AC-1)1) on 01–02 (NO) (resistive load) 250 V AC, 3 A
Maximum terminal load (AC-15)1) on 01–02 (NO) (inductive load @ cosφ 0.4) 250 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 01–02 (NO) (resistive load) 30 V DC, 2 A
Maximum terminal load (DC-13)1) on 01–02 (NO) (inductive load) 24 V DC, 0.1 A
Maximum terminal load (AC-1)1) on 01–03 (NC) (resistive load) 250 V AC, 3 A
Maximum terminal load (AC-15)1)on 01–03 (NC) (inductive load @ cosφ 0.4) 250 V AC, 0.2 A
Maximum terminal load (DC-1)1) on 01–03 (NC) (resistive load) 30 V DC, 2 A
Minimum terminal load on 01–03 (NC), 01–02 (NO) 24 V DC 10 mA, 24 V AC 20 mA
1) IEC 60947 parts 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation.
Control characteristics
Resolution of output frequency at 0–500 Hz ±0.003 Hz
System response time (terminals 18, 19, 27, 29, 32, and 33) ≤2 ms
Speed control range (open loop) 1:100 of synchronous speed
Speed accuracy (open loop) ±0.5% of nominal speed
Speed accuracy (closed loop) ±0.1% of nominal speed
All control characteristics are based on a 4-pole asynchronous motor.
CAUTION
PERSONAL INJURY AND EQUIPMENT DAMAGE RISK
Malfunction or failing to follow the recommendations
may result in personal risk, and damage to the frequency
converter and other equipment.
• Select fuses according to recommendations.
Possible damage can be limited to be inside the
frequency converter.
Enclosure size Power [kW (hp)] Non-UL fuse Non-UL circuit breaker UL fuse
0.37 (0.5) JJS-3
0.55–0.75 gG-10
JJS-6
(0.74–1.0)
K1 PKZM0-16
1.1–1.5
JJS-10
(1.48–2.0) gG-20
2.2 (3.0) JJS-15
3.0–5.5
K2 gG-25 PKZM0-20 JJS-25
(4.0–7.5)
7.5
K3 gG-25 PKZM0-25 JJS-25
(10)
11–15
K4 gG-50 – JJS-50
(15–20)
18.5–22
K5 gG-80 – JJS-80
(25–30)
1.01
1.0
0.99
Relative Efficiency
0.98
0.97
0.96
0.95
0.94
0.93
0.92
0% 50% 100% 150% 200%
% Speed
100% load 75% load 50% load 25% load
Illustration 7.2 Typical Efficiency Curves
Table 7.11 dU/dt Data for FC 280, 1.5 kW (2.0 hp), 3x200–240 V
Cable Mains
130BE889.10
K1 Derating Curve
length voltage Rise time UPEAK dU/dt 100%
[m (ft)] [V] [μsec] [kV] [kV/μsec] 90%
5 (16.4) 240 0.072 0.468 5.25 80%
50 (164) 240 0.208 0.592 2.28 70%
Output Current
60%
Table 7.12 dU/dt Data for FC 280, 2.2 kW (3.0 hp), 3x200–240 V 50% 45C
40% 50C
Cable Mains
30% 55C
length voltage Rise time UPEAK dU/dt
20%
[m (ft)] [V] [μsec] [kV] [kV/μsec]
10%
5 (16.4) 240 0.092 0.526 4.56
0%
50 (164) 240 0.28 0.6 1.72 0 2 4 6 8 10 12 14 16
Switching Frequency [kHz]
Table 7.13 dU/dt Data for FC 280, 3.7 kW (5.0 hp), 3x200–240 V
Illustration 7.3 K1 Derating Curve
Cable Mains
length voltage Rise time UPEAK dU/dt
130BE890.10
K2 Derating Curve
7 7 [m (ft)]
5 (16.4)
[V]
240
[μsec]
0.088
[kV]
0.414
[kV/μsec]
3.79 100%
90%
50 (164) 240 0.196 0.593 2.41
80%
70%
Table 7.14 dU/dt Data for FC 280, 1.5 kW (2.0 hp), 1x200–240 V
Output Current
60%
130BE891.10
K3 Derating Curve
some conditions, derating must be done manually. 100%
In other conditions, the frequency converter automatically 90%
performs a degree of derating when necessary. Derating is 80%
done to ensure the performance at critical stages where 70%
Output Current
130BE892.10
K4 Derating Curve
100%
90%
80%
70%
Output Current
60%
50% 45C
40% 50C
30% 55C
20%
10%
0%
0 2 4 6 8 10 12 14 16
Switching Frequency [kHz]
K5 Derating Curve
100% 7 7
90%
80%
70%
Output Current
60%
50% 45C
40% 50C
30% 55C
20%
10%
0%
0 2 4 6 8 10 12 14 16
Switching Frequency [kHz]
B EMC precaution..................................................................................... 55
F
C
FC profile
Cable length........................................................................................... 78 FC profile............................................................................................. 68
Cable size................................................................................................. 14 FC with Modbus RTU...................................................................... 56
Protocol overview............................................................................ 55
Catch up/slow down........................................................................... 22
Floating delta......................................................................................... 15
CE mark....................................................................................................... 9
Freeze output........................................................................................... 6
Coast............................................................................................................ 6
Freeze reference.................................................................................... 22
Coasting............................................................................................ 68, 69
Function code........................................................................................ 64
Control
Characteristic..................................................................................... 80 Fuse............................................................................................................ 81
word...................................................................................................... 68
Wiring................................................................................................... 17 G
Control card GLCP control key................................................................................... 20
+10 V DC output............................................................................... 80
Performance...................................................................................... 80 Grounded delta..................................................................................... 15
RS485 serial communication....................................................... 80 Grounding........................................................................................ 14, 15
USB serial communication............................................................ 80
Control structure H
Open loop........................................................................................... 20
Hardware set-up................................................................................... 55
Cross-section.......................................................................................... 78
Hold output frequency....................................................................... 68
Customer relay...................................................................................... 52
D I
IEC 61800-3...................................................................................... 15, 77
Data type, supported.......................................................................... 58
IND............................................................................................................. 58
DC brake.................................................................................................. 68
Index (IND).............................................................................................. 58
Dead band............................................................................................... 24
Dead band around 0........................................................................... 24
Derating................................................................................................... 77
Input Outputs
Current................................................................................................. 15 Analog output.............................................................................. 7, 79
Power.................................................................................................... 15 Digital output.................................................................................... 79
Terminal............................................................................................... 15
Inputs P
Analog input................................................................................. 7, 78
Digital input................................................................................ 20, 78 Parameter number (PNU).................................................................. 58
Pulse input.......................................................................................... 79 PELV.................................................................................................... 48, 80
Intermediate circuit...................................................................... 44, 83 PELV, protective extra low voltage................................................. 39
Intermittent duty cycle......................................................................... 8 Power cycle............................................................................................... 8
Internal current control, VVC+ mode............................................ 20 Preset reference.................................................................................... 23
Process PID control.............................................................................. 30
J Protection................................................................................................ 39
Jog......................................................................................................... 6, 68 Pulse feedback....................................................................................... 23
Pulse reference.................................................................................. 7, 23
L
LCP.................................................................................................... 6, 8, 20 Q
Leakage current.................................................................................... 39 Qualified personnel............................................................................. 10
Low Voltage Directive........................................................................... 9
R
M Rated motor current.............................................................................. 6
Machinery Directive............................................................................... 9 Rated motor speed................................................................................. 7
Mains RCD............................................................................................................... 8
AC mains............................................................................................. 15
Isolated mains................................................................................... 15 Read holding registers (03 hex)....................................................... 66
drop-out.............................................................................................. 44 Reference limit....................................................................................... 22
Supply..................................................................................................... 8
Relay output........................................................................................... 80
Supply (L1, L2, L3)............................................................................ 76
Supply data........................................................................................ 75 Reset alarm............................................................................................. 20
Mechanical holding brake................................................................. 40 RFI filter.................................................................................................... 15
Modbus communication................................................................... 55 Rise time.................................................................................................. 83
Modbus exception code.................................................................... 64 RS485
RS485............................................................................................. 54, 56
Modbus RTU........................................................................................... 60
installation and set-up................................................................... 54
Modbus RTU overview....................................................................... 60
Moment of inertia................................................................................ 44 S
Motor Safety precautions............................................................................... 10
Cable..................................................................................................... 14
output.................................................................................................. 77 Serial communication.................................................................... 7, 80
phase.................................................................................................... 43 Short circuit............................................................................................ 43
thermal protection................................................................... 44, 70
SIL2............................................................................................................... 9
voltage................................................................................................. 83
Motor-generated overvoltage.................................................... 44 SILCL of SIL2.............................................................................................. 9
Slip compensation.................................................................................. 8
N Special conditions................................................................................ 84
Network configuration....................................................................... 60 Speed PID......................................................................................... 17, 20
Network connection............................................................................ 54 Speed PID control................................................................................. 27
NLCP control key................................................................................... 20 Speed reference.................................................................................... 46
Standard and compliance for STO.................................................... 9
O Static overload in VVC+ mode......................................................... 44
Open loop............................................................................................... 80 Status word............................................................................................. 69
Output current...................................................................................... 79
STO
Activation............................................................................................ 51
Automatic restart...................................................................... 51, 52
Commissioning test........................................................................ 51
Deactivation....................................................................................... 51
Maintenance...................................................................................... 52
Manual restart............................................................................ 51, 52
Technical data................................................................................... 53
Supply voltage....................................................................................... 79
Switching on the output.................................................................... 43
Synchronous motor speed.................................................................. 7
T
Telegram length (LGE)......................................................................... 56
Terminal tightening torque.............................................................. 81
Thermistor.......................................................................................... 8, 48
Torque
characteristic..................................................................................... 77
control.................................................................................................. 17
Trip................................................................................................................ 8
V
Voltage level........................................................................................... 78
VVC+..................................................................................................... 9, 20
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
*MG07B102*
132R0142 MG07B102 03/2016