Furnace
Furnace
GAS-FIRED FURNACES
INSTRUCTION TUBULAR HEAT EXCHANGER SERIES
MODELS: P*UR / G9T-UP / FG9-UP (Upflow)
40 - 140 MBH INPUT
MODELS: P*DH / G9T-DH / FG9-DH (Downflow / Horizontal)
40 - 120 MBH INPUT
CONTENTS
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . 2
SPECIFIC UNIT INFORMATION . . . . . . . . . . . . . . . . . . 3
DUCTWORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
ELECTRICAL POWER CONNECTION . . . . . . . . . . . . 12
ELECTRICAL CONTROL CONNECTIONS . . . . . . . . . 13
COMBUSTION AIR AND VENT SYSTEM . . . . . . . . . . 14
CONDENSATE PIPING . . . . . . . . . . . . . . . . . . . . . . . . 24
SAFETY CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . 25
START-UP AND ADJUSTMENTS . . . . . . . . . . . . . . . . 26
FURNACE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . 31
OPERATION AND MAINTENANCE . . . . . . . . . . . . . . . 33
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . 36
EFFICIENCY
RATING
CERTIFIED
GENERAL INFORMATION
DESCRIPTION
This Category IV, dual certified direct vent and 1-pipe vent
IMPROPER INSTALLATION MAY CREATE A
furnace is designed for residential or commercial applica-
CONDITION WHERE THE OPERATION OF THE
tion. It may be installed without modification to the conden-
PRODUCT COULD CAUSE PERSONAL INJURY
sate system in a basement, garage, equipment room, alcove,
OR PROPERTY DAMAGE.
attic or any other indoor location provided the space tempera-
IMPROPER INSTALLATION, ADJUSTMENT, ture is 32 °F or higher and where all required clearance to
ALTERATION, SERVICE OR MAINTENANCE combustibles and other restrictions are met. If the furnace is
CAN CAUSE INJURY OR PROPERTY DAMAGE. being installed where the space temperature is below 32°F,
REFER TO THIS MANUAL FOR ASSISTANCE refer to “BELOW FREEZING LOCATIONS” on page 4.
OR ADDITIONAL INFORMATION, CONSULT A
This furnace is constructed at the factory for natural gas-fired
QUALIFIED INSTALLER, SERVICE AGENCY OR
operation at 0 - 4,500 ft. above sea level, but may be con-
THE GAS SUPPLIER.
verted to operate on propane (LP) gas and at altitudes up to
10,000 ft. For applications at altitudes between 2,000 - 4,500
ft., see “COMBUSTION AIR AND VENT SYSTEM” on
page 14, for required vent length reductions. For applications
at altitudes greater than 4,500 feet, see high altitude instruc-
tions 035-14460-000.
THIS PRODUCT MUST BE INSTALLED IN
STRICT COMPLIANCE WITH THE ENCLOSED High altitude and propane (LP) changes or conversions
INSTALLATION INSTRUCTIONS AND ANY required in order for the appliance to satisfactory meet the
APPLICABLE LOCAL, STATE, AND NATIONAL application must be made by an authorized distributor or
CODES INCLUDING BUT NOT LIMITED TO, dealer. In Canada, a certified conversion station or other
BUILDING, ELECTRICAL AND MECHANICAL qualified agency, using factory specified and/or approved
CODES. parts, must perform the conversion.
INSPECTION
As soon as a unit is received, it should be inspected for possi-
ble damage during transit. If damage is evident, the extent of
the damage should be noted on the carrier's freight bill.
A separate request for inspection by the carrier's agent
The furnace area must not be used as a broom
should be made in writing. Also, before installation the unit
closet or for any other storage purposes, as a fire
should be checked for screws or bolts which may have loos-
hazard bay be created. Never store items such as
ened in transit. There are no shipping or spacer brackets
the following on, near or in contact with the fur-
which need to be removed.
nace.
1.Spray or aerosol cans, rags, brooms, dust mops, vac- NOTES, CAUTIONS & WARNINGS
uum cleaners or other cleaning tools. The installer should pay particular attention to the words:
1.Soap powders, bleaches, waxes or other cleaning NOTE, CAUTION and WARNING. NOTES are intended to
compounds; plastic items or containers; gasoline, clarify or make the installation easier. CAUTIONS are given
kerosene, cigarette lighter fluid, dry cleaning fluids to prevent equipment damage. WARNINGS are given to alert
or other volatile fluid. the installer that personal injury and/or equipment or property
damage may occur if installation procedures are not handled
1.Paint thinners and other painting compounds. properly.
1.Paper bags, boxes or other paper products
Never operate the furnace with the blower door
removed. To do so could result in serious personal
injury and/or equipment damage.
The cooling coil must be installed in the supply air
duct, downstream of the furnace. Cooled air may
not be passed over the heat exchanger.
6-3/8
20 1-1/4 B 3-1/8
2-3/4
6-1/8 4-1/8
8-7/8
1-3/4
45 6
T’STAT
WIRING
7/8” K.G.
OPTIONAL SIDE RETURN 1-3/4
CUT-OUT (EITHER SIDE) 22-3/4
28-1/2 A
A MODELS P*UR/
A B C D E
C
G9T-UP/ FG9-UP
B 40 / 37 / 1000 /”A” 14-1/2 16-1/4 13-1/8 2 2
60 / 55 / 1000 /”B” 17-1/2 19-3/4 16-5/8 2 2
80 / 75 / 1200 /”B” 17-1/2 19-3/4 16-5/8 2 2
28-1/2
WITH K.O. 80 / 75 / 1600 /”C” 21 23-1/4 20-1/8 3 2
1
20 23
REMOVED
100 / 95 / 1400 /”C” 21 23-1/4 20-1/8 3 2
100 / 95 / 2000 /”C” 21 23-1/4 20-1/8 3 2
3/4” 120 / 112 / 2000 /”D” 24-1/2 23-1/4 20-1/8 3 2
FLANGE
D 140 / 130 / 2000 /”D” 24-1/2 23-1/4 20-1/8 3 2
INTAKE FRONT E FRONT
VENT CONNECTION 1. Vent pipe must be increased to 3” on this unit.
CONNECTION TOP IMAGE BOTTOM IMAGE
(vent size)
B 20 D
3/4 VENT CONNECTION
T'STAT WIRING
7/8 K.O.
CONDENSATE
CONDENSATE DRAIN ACCESS
DRAIN ACCESS 1-3/4
3-1/4 x 3
3-1/4 x 3
5-1/4
35
16-3/4
45 AIR INTAKE 18-1/2 3-3/4
3-5/8 x 3-5/8 1-1/4 AIR INTAKE
(G CONN. SIZE/ 3-5/8 x 3-5/8
PIPE SIZE) 3-3/4 (G CONN. SIZE/
PIPE SIZE)
GAS INLET 7-1/2 1-1/4
1-1/4 x 2-1/2
6-1/4
4-1/8 ALT. GAS INLET
2-3/4 1-1/4 x 2-1/2
A 28-1/2
FRONT LEFT SIDE RIGHT SIDE
B A
1-3/8 MODELS P*DH /
G9T-DH / FG9-DH A B C D E F G
VENT CONNECTION 40/37/1000/A 14-1/2 13-1/4 11-3/4 2 5-1/8 2-1/2 2
(VENT SIZE
19-1/4
20 POWER 60/55/1200/B 17-1/2 16-1/4 14-3/4 2 6-5/8 2-1/4 2
WIRING C
7/8 K.O. 80/75/1200/B 17-1/2 16-1/4 14-3/4 2 6-5/8 2-1/4 2
80/75/1600/C 21 19-3/4 18-1/4 2 8-3/8 2-1/4 2
8 100/95/2000/C 21 19-3/4 18-1/4 2 8-3/8 2-1/4 2
1-7/8 5-3/8
120/112/2000/D 24-1/2 23-1/4 21-3/4 2 (3)1 10-1/8 2-1/4 3
H
E F
FRONT FRONT 1. VENT PIPE MUST BE INCREASED TO 3" ON THIS MODEL.
TOP IMAGE BOTTOM IMAGE ALL DIMENSION ARE IN INCHES, AND ARE APPROXIMATE.
RETURN END RETURN END
1. Handle an air volume appropriate for the served space Attach the supply plenum to the fur-
and within the operating parameters of the furnace spec- nace outlet duct connection flanges.
ifications. This is typically through the use of S
cleat material when a metal plenum is
2. Be installed in accordance with standards of NFPA
used. The use of an approved flexible
(National Fire Protection Association) as outlined in
duct connector is recommended on all
NFPA pamphlets 90A and 90B (latest editions) or appli-
installations. This connection should be
cable national, provincial, local fire and safety codes.
sealed to prevent air leakage.
3. Create a closed duct system. The supply duct system
If a matching cooling coil is used, it
must be connected to the furnace outlet and the return
may be placed directly on the furnace
duct system must be connected to the furnace inlet. Both
outlet and sealed to prevent leakage.
supply and return duct systems must terminate outside
Follow the coil instructions for installing
the space containing the furnace.
the supply plenum.
4. Complete a path for heated or cooled air to circulate
On all installations without a coil, a removable access panel
through the air conditioning and heating equipment and
is recommended in the outlet duct such that smoke or
to and from the conditioned space.
reflected light would be observable inside the casing to indi-
cate the presence of leaks in the heat exchanger. This
access cover shall be attached in such a manner as to pre-
vent leaks.
The cooling coil must be installed in the supply air RETURN DUCT CONNECTION
duct downstream of the furnace. Cooled air must Return air may enter the furnace through the side(s) or bot-
not be passed over the heat exchanger. tom depending on the type of application. Return air may
not be connected into the rear panel of the unit. Refer to
When the furnace is used in conjunction with a cooling coil,
the "Filter Installation" section of this instruction for the type of
the coil must be installed parallel with, or in the supply air side
application desired for specific installation details.
of the furnace to avoid condensation in the primary heat
exchanger. NOTE: In order to achieve the airflow indicated in the table, it
is recommended those applications over 1800 CFM use
When a parallel flow arrangement is used, the dampers or return air from two sides, one side and the bottom or bottom
other means used to control air flow must be adequate to pre- only. For single return application, see data and notes on
vent chilled air from entering the furnace, and if manually blower performance data tables in this manual.
operated, must be equipped with means to prevent operating
of either unit unless the damper is in the full heat or cool posi-
tion.
FILTER INSTALLATION - UPFLOW 4. Install the filter(s) if provided. Cut filter if necessary to
All applications require the use of a filter. A high velocity filter match air opening in cabinet. Filter should extend
and retainer are provided for field installation on P*UR & beyond opening edge as much as possible to prevent air
G9T-UP models. FG9-UP models must have a field-supplied from bypassing the filter. DO NOT remove stiffening rods
filter and mounting hardware. from inside the filter. Shorten the rods, if necessary, to
match final filter size.
Internal Installation
5. Position the filter between the wire retainer and the cabi-
1. Select desired filter position (left/right side, and/or bot- net wall (or floor) so it completely covers the cabinet air
tom). Remove the corresponding cabinet cut-outs per opening and secure the filter in place at the front of the
instructions provided. cabinet by fastening the closed (looped) end of the
2. Install snap-in retainer clips into the corresponding slots retainer wire under the flanged edge of the cabinet.
from the outside rear of the cabinet (Refer to Figure 3.) When properly installed the filter should fit flush with all
To prevent cabinet air leaks, install snap-in plugs (pro- four sides of the cabinet wall.
vided) into the unused slots at the outside rear of the NOTE: Air velocity through throw-away type filters may not
cabinet. exceed 300 feet per minute. All velocities over this require the
use of high velocity filters.
Side Return - External Filter
Locate and knock out the square corner locators. These indi-
cate the size of the cutout to be made in the furnace side
FURNACE
(REAR CABINET) LEFT panel. Refer to Figure 5.
SIDE
RIGHT SLOTS
SIDE
SLOTS
BOTTOM SLOTS
CABINET
SLOT
PLUG UNUSED
CABINET SLOTS
FILTER SUPPORT WITH PLUGS
The return duct may be attached to the furnace by S-cleat, Horizontal Installations
bend tabs or other approved methods. Be sure to seal the For installation of an air conditioning coil in a horizontal appli-
duct to the furnace to prevent air leakage. cation, the perforations in the wrapper flanges must be bent
Where the return duct system is not complete, the return con- away from the heat exchanger to create duct flanges so the
nection must run full size to a location outside the utility room air conditioning coil can be properly seated on the furnace.
or basement. For further details, consult Section 5.3 (Air for Refer to the installation instructions supplied with the air con-
Combustion and Ventilation) of the National Fuel Gas Code, ditioning coil for additional information and completion of the
ANSI Z223.1, or CAN/CGA B149.1 or .2, Installation Code - coil installation.
latest editions. NOTE: Duct pliers or other suitable tool can be used to bend
Bottom Return perforations. To help bend flanges in a straight line, scribe a
Bottom return applications normally pull return air through a line between the perforations prior to bending.
base platform or return air plenum. Be sure the return plat- DOWNFLOW APPLICATION
form structure is suitable to support the weight of the furnace.
Refer to Figure 1 on Page 5, for unit dimensions. Be sure to DOWNFLOW FILTERS
seal the furnace to plenum connection to prevent air leakage. A top return filter rack is supplied with
The bottom panel is equipped with a perforated opening for the furnace. Two 14" x 20" permanent
easy removal. Tabs must be cut with sheet metal snips to washable filters are supplied with each
allow removing knock-out. Scribe marks are included for unit.
forming flanges for attachment of the return air ductwork. Downflow furnaces typically are
NOTE: If an external mounted filter rack is being used, see installed with the filters located above
the instructions provided with that accessory for proper hole the furnace, extending into the return
cut size. air duct.
Upflow attic installations must meet all minimum clearances Any branch duct must attach to the ver-
to combustibles and have floor support with required service tical ductwork above the filter height
accessibility. (FH) and for proper installation refer to
Figure 6 .
DOWNFLOW/HORIZONTAL MODELS
The filter rack (provided) should be securemd to the center of
COOLING COIL TRANSITION the front and rear flanges at the furnace top. Drill a hole
These furnace models are equipped with perforations in the through the front and rear duct flange into the filter rack and
supply air wrapper flanges that allow for easy application of secure it with a sheet metal screw.
an air conditioning coil to the furnace without the use of sheet NOTE: For easier filter access in a downflow configuration, a
metal transition pieces. These perforations can be bent in removable access panel is recommended in the vertical run
either direction depending on the type of application - either of the return air duct immediately above the furnace.
downflow or horizontal left and right. Refer to either the
Refer to the unit rating plate for furnace model then see the
"Downflow Application" or "Horizontal Application" section
dimensions page of this instruction for return air plenum
below for specific instructions on how to install the coil.
dimensions. Install the plenum following instructions under
Downflow Installations “DUCTWORK” on page 7, in this instruction.
For installation of an air conditioning coil in a downflow appli- SUPPLY AIR DUCTS
cation, the perforations in the wrapper flanges must be bent
Installations on combustible material or floors must use a
in towards the heat exchanger to allow for the coil duct flange
combustible floor base (shown in Figure 7 - 1CB0314, 17, 21
to recess into the furnace. Refer to the installation instruc-
& 24) as specified on the rating plate. Follow the instructions
tions supplied with the air conditioning coil for additional infor-
supplied with the combustible floor base accessory.
mation and completion of the coil installation.
This base can be replaced with a matching cooling coil, prop-
NOTE: Duct pliers or other suitable tool can be used to bend
erly sealed to prevent leaks. Follow the cooling coil instruc-
perforations. To help bend flanges in a straight line, scribe a
tions for installing the plenum.
line between the perforations prior to bending.
All downflow application supply duct systems must be
designed and installed in accordance with the standards of
NFPA 90A and 90B, and/or all local codes.
DOWNFLOW/HORIZONTAL MODELS
FILTER RACK
(FACTORY SUPPLIED) HORIZONTAL APPLICATION
A
CASING SIZE DIMENSION FH
16-1/4 12-3/4
22-1/4 11
26-1/4 8-1/4
FILTER
DUCTWORK RACK
FH
SHEET METAL
FIBERGLASS TAPE GAS PIPING IN FRONT OF
UNDER FLANGE FURNACE
COMBUSTION AIR
OPENINGS IS
RECOMMENDED
COMBUSTIBLE FLOOR 30” MIN.
BASE ACCESSORY
WORK AREA
12”
This appliance is design certified for line contact for furnaces When suspending the furnace from rafters or floor joists using
installed horizontally. The intersection of the furnace top and rod, pipe or straps, refer to the Physical and Rating Data
sides form a line. This line may be in contact with combustible Table for downflow/horizontal furnace weights to determine
material. Refer to the "SPECIFIC UNIT INFORMATION" sec- suitable means of suspension.
tion of this manual for further information on installation loca- Angle supports should be placed at the supply air end and
tion and limitations. near the blower deck (Refer to Figure 9 ). Do not support
at return air end of unit.
Units may also be suspended by using straps or other mate-
rial at the same location. All four suspension points must be
If this furnace is installed over a finished space, a level to ensure quiet furnace operation.
condensate safety pan must be installed.
Minimum 4.5 In. W.C. 11 In. W.C. Never apply a pipe wrench to the body of the com-
bination automatic gas valve. A wrench must be
Maximum 13.9 In. W.C. 13.9 In. W.C. placed on the projection or wrench boss of the
NOTE: An accessible manual shutoff valve must be installed valve when installing piping to it.
upstream of the furnace gas controls and within 6 feet of the
furnace. ELECTRICAL POWER CONNECTION
Field wiring to the unit must conform to and be grounded in
E X T E R N A L M A N U A L accordance with the provisions of the National Electrical
S H U T O F F V A L V E
T O G A S T O G A S
Code ANSI/NFPA No. 70-latest edition, Canadian Electric
S U P P L Y S U P P L Y Code C22.1 Part 1 - (latest edition) and/or local codes. Elec-
tric wires which are field installed shall conform with the tem-
G R O U N D J O IN T U N IO N perature limitation for 63°F/35°C rise wire when installed in
M A Y B E IN S T A L L E D
IN S ID E O R O U T S ID E U N IT accordance with instructions. Refer the rating plate or Physi-
cal and Rating Data Tables in these instructions for specific
furnace electrical data.
Provide a power supply separate from all other circuits. Install
overcurrent protection and disconnect switch per local/
national electrical codes. The switch should be close to the
unit for convenience in servicing. With the disconnect switch
D R O P L E G in the OFF position, check all wiring against the unit wiring
D R O P L E G
label. Also, see the wiring diagram in this instruction.
G A S V A L V E NOTE: The furnace’s control system depends on correct
polarity of the power supply and a proper ground connection.
Refer to the “FURNACE CONTROL DIAGNOSTICS” on
page 36 for symptoms of reversed power supply polarity.
NOTE: A 1/8” NPT plug is included in the inlet side of the gas
valve for measuring incoming gas pressure.
Use copper conductors only.
The furnace must be isolated from the gas supply piping sys-
tem by closing its individual external manual shutoff valve Connect the power supply as shown on the unit wiring label
during any pressure testing of the gas supply piping system on the inside of the blower compartment door. The black fur-
at pressures equal to or less than 1/2 psig (3.48 kPa). nace lead must be connected to the L1 (hot) wire from the
The furnace and its individual shutoff valve must be discon- power supply. The white furnace lead must be connected to
nected from the gas supply piping system during any pres- neutral. Also, the green equipment ground wire must be con-
sure testing of that system at test pressures in excess of 1/2 nected to the power supply ground.
psig (3.48 kPa). Remove the screws retaining the wiring box cover. Route the
power wiring through the opening in the unit into the junction
box with a conduit connector or other proper connection.
Make wiring connections and replace the wiring box cover
and screws. Refer to Figures 11or 12.
Compounds used on threaded joints of gas piping
An alternate wiring method is to use a field provided 2 x 4 box
must be resistant to the action of liquefied petro-
and cover on the outside of the furnace. Route the furnace
leum gases. After connections are made, leak-test
leads into the box using a protective bushing where the wires
all pipe connections.
pass through the furnace pane.
After all gas piping connections are completed,
leak test all joints, fittings and furnace connections
with rich soap and water solution, commercially
available bubble type leak detection fluid, or other
approved means.
Do not use an open flame or other source of
ignition for leak testing.
L1
ELECTRICAL CONTROL CONNECTIONS
(HOT) N
BLK/BLK GND Install the field-supplied thermostat. The thermostat instruc-
WHT/WHT tions for wiring are packed with the thermostat. With the ther-
GRN/GRN WHT
mostat set in the OFF position and the main electrical source
BLK GRN
disconnected, complete the low-voltage wiring from the ther-
mostat to the terminal board on the ignition module. Connect
JUNCTION Class 2 control wiring as shown in Figure 14. Electronic ther-
BOX
mostats may require a common connection as shown dashed
in Figure 14.
BLOWER COMPARTMENT Apply strain relief to thermostat wires passing through cabi-
DOOR SWITCH net.
TRANSFORMER Y WR G C
Set the heat anticipator in the room thermostat to .45
amps. Setting it lower will cause short cycles. Setting
it higher will cause the room temperature to exceed
IGNITION MODULE
COOL
XFMR
PARK
HUM
L1
NEUTRALS
the setpoints
PARK
HEAT
EAC
CLASS 2 SYSTEM
CONTROL WIRING
TO THERMOSTAT
BURNER COMPARTMENT
BLK BLK (HOT)
NOMINAL
FIGURE 11 : Electrical Wiring - Upflow Models WHT WHT (NEUTRAL) 120 VOLT
NOTE: The power connection leads and wiring box on upflow GRN GRD
units may be relocated to the left side of the furnace. Remove
the screws and cut wire tie holding excess wiring. Reposition
on the left side of the furnace and fasten using holes pro- FIGURE 13 : Power Wiring Connections
vided.
L1
N WIRING INSIDE
HOT ROOM FURNACE CONDENSING
JUNCTION BOX
GRD THERMOSTAT CONTROL UNIT
BLK/BLK
WHT
WHT/WHT
R R
BLK
GRN
GRN/GRN W W TO AIR CONDITIONER
G G CONTROLS
JUNCTION Y Y
BOX
C C
PARK
EAC
XFMR
CLASS 2 SYSTEM
COOL
PARK
HUM
NEUTRALS
L1
CONTROL WIRING
IGNITION MODULE TO THERMOSTAT
ments. Follow the thermostat manufacturer's instructions.
Y WR G C
The 24-volt, 40 VA transformer is sized for the furnace com-
FLUE CHASE
TRANSFORMER ponents only, and should not be connected to power auxiliary
devices such as humidifiers, air cleaners, etc. The trans-
former may provide power for an air conditioning unit
DOOR contactor.
SWITCH BURNER COMPARTMENT
HUM. HOT
BLK
115 VOLT
HUMIDIFIER WHT VENT PIPE
COMBUSTION AIR CEMENTS
EAC SWITCHED PIPE PASSES INTO SOCKET
HUM
CIRCUITS THROUGH TOP PANEL JUST UNDER
TOP PANEL
EAC HOT
CONNECTS TO
COLLAR ON TOP
115 VOLT BLK OF BURNER BOX
ELECTRONIC WHT
AIR CLEANER EAC
NEUTRALS
HUM
4. Three vent terminal elbows (two for vent pipe and one for
VENT PIPE PASSES
THROUGH TOP PANEL
air intake pipe) are already accounted for and should not
be counted in the allowable total indicated in the table
(see vent termination section). These parts are shown
shaded.
For downflow/horizontal models, the two additional
elbows required for the air intake pipe entry into the
burner box are also accounted for and should not be
counted. These parts are shown shaded.
For downflow/horizontal models only two additional
OPTIONAL elbows are also accounted for and also should not be
LEFT SIDE
COMBUSTION counted. These parts are shown shaded.
AIR PIPE
ROUTING COMBUSTION 5. Combustion air and vent piping must be of the same
AIR PIPE diameter.
CONNECTS TO
COLLAR ON 6. All combustion air/vent pipe and fittings must conform to
BOTTOM OF American National Standards Institute (ANSI) standards
BURNER BOX
and American Society for Testing and Materials (ASTM)
standards D1785 (Schedule 40 PVC), D2665 (PVC-
FIGURE 17 : Air Intake and Vent Locations - DWV), F891 (PVC-DWV Cellular Core). D2241 (SDR-21
Downflow/Horizontal and SDR-26 PVC), D2261 (ABS-DWV), or F628 (Sched-
The intake/vent should be located either through the wall ule 40 ABS. Pipe cement and primer must conform to
(horizontal or side vent) or through the roof (vertical vent). ASTM Standards D2564 (PVC) or D2235 (ABS).
Care should be taken to locate side vented systems where 7. The use of flexible connectors or no hub connectors in
trees or shrubs will not block or restrict supply air from enter- the vent system is not allowed. This type connection is
ing or combustion products from leaving the terminal. allowed in the combustion air pipe near the furnace for
Also, the terminal assembly should be located as far as pos- air conditioning coil accessibility.
sible from a swimming pool or a location where swimming Table 4: INTAKE/VENT PIPING - 2 PIPE SYSTEM
pool chemicals might be stored. Be sure the terminal assem-
bly follows the outdoor clearances listed in Table 3 for U.S. Max. Elbows vs. One Way Vent
Models P*UR/ Pipe
installations. In Canada, refer to CAN/CGA-B149.1 or.2 Length (Ft.)*
FG9-UP/G9T-UP Size
Installation Code (latest edition-Venting Systems and Air 5 - 40 45 50 75
Supply).
40 / 37 / 1000 / A
COMBUSTION AIR/VENT PIPE SIZING
60 / 55 / 1000 / B
To select the propeTable 4 or Table 5. The size will be deter- 80 / 75 / 1200 / B
mined by a combination of furnace model, total length of run, 2” 6 5 4 N/A
80 / 75 / 1600 / C
and the number of elbows required. The following rules must
also be observed.Long radius elbows are required for all 100 / 95 / 1400 / C
units. 100 / 95 / 2000 / C
1. Long radius elbows are required for all units. 40 / 37 / 1000 / A
2. Elbows are assumed to be 90 degrees. Two 45 degree 60 / 55 / 1000 / B
elbows count as one 90 degree elbow. 80 / 75 / 1200 / B
3” 8 7 6 5
3. Elbow count refers to combustion air piping and vent pip- 80 / 75 / 1600 / C
ing separately. For example, if the table allows for 5
100 / 95 / 1400 / C
elbows, this will allow a maximum of 5 elbows in the
combustion air piping and a maximum of 5 elbows in the 100 / 95 / 2000 / C
vent piping. 120 / 112 / 2000 / D
3" Only 6 5 4 N/A
140 / 130 / 2000 / D
Table 5: INTAKE/VENT PIPING 2-PIPE SYSTEM 4. Termination should be located where it will not be dam-
aged or exposed to flying stones, balls, etc.
Max. Elbows vs. One Way
Models P*DH/
Pipe Size Vent Length (Ft.)*
5. Termination should be positioned where vent vapors are
FG9-DH/G9T-DH not objectionable.
5-30 35 40 60
40 /37 / 1000 / A VENT CLEARANCES (2-PIPE) U.S. ONLY
60 /55 / 1200 / B Dryer Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft.
80 /75 / 1200 / B 2” 6 5 4 N/A Plumbing Vent Stack . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 ft.
80 /75 / 1600 / C
Gas Appliance Vent Terminal . . . . . . . . . . . . . . . . . . . 3 ft.*
100 /95 / 2000 / C
40 /37 / 800 / A From any mechanical fresh air intake . . . . . . . . . . . . . . 1 ft.
60 /55 / 1200 / B From any door, window or non-mechanical fresh air or
80 /75 / 1200 / B 3” 8 7 6 5 combustion air intake . . . . . . . . . . . . . . . . . . . . . . . . . . 1 ft.
80 /75 / 1600 / C Above grade and anticipated snow depth . . . . . . . . . . . 1 ft.
100 /95 / 2000 / C
Above grade when adjacent to public walkway . . . . . . 7 ft.
120 /112 / 2000 / D 3" Only 6 5 4 N/A
From electric, gas meters, regulators and relief equipment -
*.
Elbow count does not include (2) 90 ° elbows required min. horizontal distance . . . . . . . . . . . . . . . . . . . . . . . . 4 ft.
to pipe intake into burner box or those required for the
* Does not apply to multiple installations of this furnace
termination. See Step 4 under Combustion Air/Vent
model. Refer to “VENTING MULTIPLE
Pipe Sizing
UNITS" Section on page 17 .
NOTE: If installing furnace at altitudes between 2000 - 4500 In Canada, refer to CAN/CGA-B149.1 or .2 Installation
ft., intake and vent pipe length must be reduced by 10 ft. If the Code (latest edition - Venting Systems and Air Supply)
installation requires the maximum allowable intake and vent
pipe length, the furnace must be converted for high altitude
NOTE: Consideration must be given for degradation of build-
operation. Refer to the proper high altitude application
ing materials by flue gases.
instruction for details.
NOTE: Shaded components of the combustion air/vent sys-
VENT TERMINATION (2-PIPE)
tem shown in Figures 18 to Figure 23 are considered to be
Side wall horizontal vent terminals and roof mounted vertical part of the termination. These components should not be
terminals may be field fabricated. Standard PVC/SRD fittings counted when determining piping limitations. Sidewall termi-
may be used. Terminal configuration must comply as detailed nation may require sealing or shielding of building surfaces
in this section. with a corrosive resistance material to protect against com-
NOTE: Combustion air and vent pipes must terminate bustion product corrosion.
together in the same atmospheric zone, either through a roof
or sidewall. OVERHANG
OVERHANG
VENT
12” MINIMUM
VENT
COMBUSTION AIR
COMBUSTION AIR
2”
OVERHANG
12” MINIMUM
VENT 6”
FIGURE 20 : Horizontal Termination Configuration with Hori- FIGURE 23 : Double Rooftop Termination
zontal Extension
VENTING MULTIPLE UNITS
Each unit must have its own intake/vent piping and termina-
tion. Do not use common pipes for combustion air or venting.
The vent terminals must be located as shown in Figure 22 or
Figure 23.
PIPING ASSEMBLY
12” VERTICAL SEPARATION COMBUSTION AIR
BETWEEN COMBUSTION The final assembly procedure for the vent/combustion air pip-
AIR AND VENT ing is as follows:
VENT
1. Cut piping to the proper length, beginning at the furnace.
2. Deburr the piping inside and outside.
MAINTAIN 12” MINIMUM 3. Chamfer the outer edges of the piping.
CLEARANCEABOVE HIGHEST
ANTICIPATED SNOWLEVEL. 4. Dry-fit the entire vent/combustion air piping assembly.
MAXIMUM OF 24” ABOVE ROOF.
5. Disassemble the piping and apply cement primer and
FIGURE 21 : Vertical Termination cement per the cement manufacturer's instructions.
Primer and cement must conform to ASTM D2564 for
PVC, or ASTM D2235 for ABS piping.
NOTE: Vent pipe must be sloped 1/4” per foot to allow con-
densate to flow back to the furnace. COMBUSTION AIR
Air Source from Inside the Building 3. Louvers, Grilles and Screens
Two permanent openings, one within 12 inches of the top of a. In calculating free area, consideration must be given
the confined space and one within 12 inches of the bottom, to the blocking effects of louvers, grilles and
shall each have a free area of not less than one square inch screens.
per 1,000 Btuh of total input rating of all appliances located in
b. If the free area of a specific louver or grille is not
the space. The openings shall communicate freely with inte-
rior areas having adequate infiltration from the outside. known, refer to Table 6, to estimate free area.
NOTE: At least 100 square inches free area shall be used for NOTE: If mechanically operated louvers are used, a means
to prevent main burner ignition and operation must be pro-
each opening.
vided should louvers close during startup or operation.
Air Source from Outdoors
Table 6: ESTIMATED FREE AREA
1. Two permanent openings, one within 12 inches of the
top of the confined space and one within 12 inches of the Wood or Metal Wood 20-25%*
bottom, shall communicate directly, or by means of Louvers or Grilles Metal 60-70%*
ducts, with the outdoors or to such crawl or attic spaces † 1/4 in. mesh or larger 100%
Screens
that freely communicate with the outdoors.
*.
a. Vertical Ducts - Each opening must have a free Do not use less than 1/4 in. mesh
†.
area of not less than one square inch per 4,000 Btuh Free area or louvers an grilles varies widely; installer should
of total input of all appliances located in the space. follow louver or grille manufacturer’s instructions.
3. The following types of installations may require OUT- 4. All vent pipe and fittings must conform to American
DOOR AIR for combustion, due to chemical exposure. National Standards Institute (ANSI) standards and Amer-
ican Society for Testing and Materials (ASTM) standards
a. Commercial buildings
D1785 (Schedule 40 PVC), D2665 (PVC-DWV), F891
b. Buildings with indoor pools (PVC-DWV Cellular Core), D2241 (SDR-21 and SDR-26
c. Furnaces installed in laundry rooms PVC), D2261 (ABS-DWV), or F628 (Schedule 40 ABS.
Pipe cement and primer must conform to ASTM Stan-
d. Furnaces installed in hobby or craft rooms
dards D2564 (PVC) or D2235 (ABS).
e. Furnaces installed near chemical storage areas
5. The use of flexible connectors or no hub connectors in
f. Permanent wave solutions the vent system is not allowed.
g. Chlorinated waxes and cleaners Table 7: VENT PIPING / 1-PIPE SYSTEM (ALL MODELS)
h. Chlorine based swimming pool chemicals Max. Elbows vs. One Way Vent
i. Water softening chemicals Model Pipe Size Length (Ft.)
j. De-icing salts or chemicals 5-40 45 50 75
All Models Except:
k. Carbon tetrachloride 120 / 112 / 2000 / D 2” 6 5 4 N/A
l. Halogen type refrigerants 140 / 130 / 2000 / D
All Models Except:
m. Cleaning solvents (such as perchloroethylene)
120 / 112 / 2000 / D 3” 8 7 6 5
n. Printing inks, paint removers, varnishes, etc. 140 / 130 / 2000 / D
o. Hydrochloric acids 120 / 112 / 2000 / D
3” Only 6 5 4 N/A
140 / 130 / 2000 / D
p. Cements and glues
q. Antistatic fabric softeners for clothes dryers NOTE: If installing furnace at altitudes between 2000 - 4500
ft., intake and vent pipe length must be reduced by 10 ft. If the
r. Masonry acid washing chemicals
installation requires the maximum allowable intake and vent
VENT PIPE SIZING (1-PIPE SYSTEM) pipe length, the furnace must be converted for high altitude
operation. Refer to the proper high altitude application
Refer to Table 7 to select the proper size piping for venting. instruction for details.
The size will be determined by a combination of furnace
model, total length of run, and the number of elbows required. VENT TERMINATION (1-PIPE SYSTEM)
The following rules must also be observed. Side wall horizontal vent terminals and roof mounted vertical
NOTE: Furnace vent pipe connections are sized for 2-in. terminals may be field fabricated. Standard PVC/SRD fittings
pipe. Any pipe size change must be made outside the fur- may be used. Terminal configuration must comply as detailed
nace casing in a vertical pipe section to allow proper drainage in this section.
of vent connections. When selecting the locations for vent termination, the follow-
ing should be considered:
NOTE: An offset using two 45 degree elbows may be
required for plenum clearance when the vent is increased to 1. Comply with all clearance requirements. Refer to Figure
3". 26 on page 21.
1. Long radius elbows are required for all units. 2. Termination should be positioned where vent vapors will
not damage plants or shrubs or air conditioning equip-
2. Elbows are assumed to be 90 degrees. Two 45 degree
ment.
elbows count as one 90 degree elbow.
3. Termination should be located where it will not be
3. One Vent terminal elbow is already accounted for and
affected by wind gusts, light snow, airborne leaves or
should not be counted in the allowable total indicated in
allow recirculation of flue gases.
the table. See “VENT TERMINAL LOCATION
CLEARANCES" Section on page 21 . This part is shown 4. Termination should be located where it will not be dam-
shaded. aged or exposed to flying stones, balls, etc.
5. Termination should be positioned where vent vapors are
not objectionable.
SOFFIT
VENTS RST
4” 4”
OPQHIPQHJRSTJUKGPVPHUGJPLMFG
WQXWGYIJPHIQUQZPIG[JYHMNJKGFGK
6”
MVJXVP[G\JNWQUWGFGVJQYJXVGPIGV
(10” RECOMMENDED)
ELECTRIC
METER 4” 4”
FGHIJGKLMN
4” FORCED
FURNACE VENT
AIR
INSIDE 3” INTAKE FIGURE 27 : Horizontal Termination Configuration with
CORNER 4” 10” 12” Minimum Clearance
1’ PLUS
SNOW CLEARANCE
Vent piping must be insulated with 1/2” Armaflex FIGURE 30 : Attic Combustion Air Termination
insulation if it will be subjected to freezing temper-
atures such as routing through unheated areas or
through an unused chimney.
NOTE: Vent pipe must be sloped 1/4” per foot to allow con- Be sure to instruct the owner not to block this
densate to flow back to the furnace. intake pipe.
HEAT
PARK
EAC
XFMR
COOL
PARK
HUM
NEUTRALS
L1
For vent pipe sizing, allowable length and elbow usage, see 3.00” MINIMUM
Table 7 on Page 20. Follow all notes, installation procedures LOOP DIA.
Y WR G C
CONDENSATE PIPING Refer to Figure 35 for hose locations and Table 8 for hose cut
lengths. All hoses are identified as shown in Figure 35.
The condensate drain connection is packed in the furnace for
field installation. It consists of a formed hose with a 1/2” NPT For horizontal left airflow (inducer and vent low) or horizontal
male connection. A 1/2” FM x 3/4” PVC slip coupling is pro- right airflow (inducer and vent high), install condensate drain
vided. hoses as follows:
This drain hose may be installed to allow left or right side con- RIGHT AIRFLOW (Inducer High) - Three hoses are required.
densate drain connection, refer to Figures 33 and 34. Cut the Hoses are supplied with furnace. Refer to Figure 35 and
hose to allow for proper fit for left or right exit. Table 8 for application.
LEFT AIRFLOW (Inducer Low) - Two hoses are required.
Inducer outlet to trap is supplied. Condensate pan to trap
must be field supplied using 5/8” I.D. hose material. Refer to
Figure 35 and Table 8, for hose placement and sizing..
Table 8: HORIZONTAL CONDENSATE DRAIN HOSE SIZES -
MODELS P*DH / FG9-DH / G9T-DH
LH DRAIN CABINET SIZE (IN.)
DIMEN. RIGHT AIRFLOW (INDUCER HIGH)
14-1/2 17-1/2 21 24-1/2
A 4-1/2 4-3/4 3-1/2 5-1/4
RH DRAIN
B 7-1/2 10-1/2 14 17-1/2
C 13-1/2 16-1/2 20 23-1/2
LEFT AIRFLOW (INDUCER LOW)
To install the drain hose assembly, remove the 7/8” knockout 3. The furnace contains an internal trap. Therefore, no
in the side panel. Remove the conduit nut from the 1/2” male external trap should be used.
fitting. Push the male fitting through the hole and reinstall the 4. If a condensate pump is used, it must be suitable for use
nut. The use of the 3/4” PVC coupling is optional. with acidic water.
CONVERSION FOR HORIZONTAL APPLICATIONS 5. Where required, a field-supplied neutralizer can be
(DOWNFLOW MODELS ONLY) installed in the drain line, external to the furnace.
Remove the condensate trap and its mounting bracket from NOTE: The condensate drain from the furnace may be con-
the unit side panel. Remove all drain hoses. nected in common with the drain from an air conditioning coil
if allowed by local code. Follow the instructions with the coil
Reinstall the trap/bracket on the side panel which will be on for trapping the drain.
the bottom when the unit is located horizontally. Use the orig-
inal mounting screws.
A
3 1 2
D
4
5
FIGURE 35 : Horizontal Application Condensate Drain Connection (Models P*DH / FG9-DH / G9T-DH)
The initial start-up of the furnace requires the following addi- c. After flame is established, the supply air blower will
tional procedures: start in about 30 seconds.
1. When the gas supply is initially connected to the furnace, NOTE: Burner ignition may not be satisfactory on first startup
the gas piping may be full of air. In order to purge this air, due to residual air in the gas line or until gas manifold pres-
it is recommended that the ground union be loosened sure is adjusted. The ignition control will make 3 attempts to
until the odor of gas is detected. When gas is detected, light before locking out.
immediately retighten the union and check for leaks. 4. With furnace in operation, paint the pipe joints and valve
Allow five minutes for any gas to dissipate before con- gasket lines with a rich soap and water solution, Bubbles
tinuing with the start-up procedure. indicate a gas leak. Take appropriate steps to stop the
leak. If the leak persists, replace the component.
OFF
ON
of the gas obtained from the local gas company). The result is
INLET 117,300 Btuh, which is close to the 120,000 Btuh rating of the
OUTLET furnace.
If the actual input is not within +2% of the furnace rating, with
WRENCH allowance being made for the permissible range of the regu-
BOSS
lator setting (0.3 inches W.C.), replace the orifice spuds with
spuds of the proper size.
MAIN REGULATOR
ON/OFF SWITCH ADJUST
WITH BURNER BOX COVER IN PLACE WITH BURNER BOX COVER REMOVED
GAS VALVE
OUTLET GAS VALVE
PRESSURE TAP
BURNER BOX
BURNER BOX PRESSURE PRESSURE
REFERENCE HOSE OUTLET REFERENCE HOSE
PRESSURE TAP (NOT USED)
TEE
FITTING
BURNER BOX
WITH COVER
6
BURNER BOX 5
WITH COVER 4
3
6 REMOVED 2 3.5 IN
U-TUBE 5
4
1
WATER COLUMN
0
MANOMETER 3 3.5 IN
2
1 GAS PRESSURE
1 WATER COLUMN 2
0 3 SHOWN
1 GAS PRESSURE 4
2 5
3 SHOWN U-TUBE 6
4
5 MANOMETER
6
WITH BURNER BOX COVER IN PLACE WITH BURNER BOX COVER REMOVED
TEE
FITTING
OUTLET
OUTLET PRESSURE
PRESSURE TAP
TAP
6 6
5 5
4 4
3 3
GAS VALVE 2 3.5 IN GAS VALVE 2 3.5 IN
1 1
0 WATER COLUMN 0 WATER COLUMN
1 GAS PRESSURE 1 GAS PRESSURE
2 2
3 SHOWN SHOWN
3
U-TUBE 4 4
5 5
MANOMETER 6 6
U-TUBE
MANOMETER
To use the same speed tap for heating and cooling, the heat LINE
120
90
unused motor leads on Park terminals. Two are provided. 180
FAN OFF
ADJUSTMENT
SWITCHES
FURNACE ACCESSORIES
ELECTRICAL
*ET03700324 Single Stage Thermostat, One-Stage Heat/One-Stage Cool, Non-Programmable
*ET03700124 Deluxe Single Stage Theromstat, One Stage Heat /One Stage Cool, Programmable
2TH13700424 Single Stage Thermostat, One Stage Heat, Round - 2TB17700424 Heat/Cool Subbase
6TH13701024 Single Stage Thermostat, One Stage Heat, Round - 2TB17700424 Heat/Cool Subbase
2TC03700124 Twinning Control
NON-ELECTRICAL
1NP0347 Propane (LP) Conversion Kit
1NP0349 Propane (LP) Conversion Kit
1PS0306
1PS0307
1PS0308 High Altitude Pressure Switch (See Form 650.75-N2.1V for proper application)
1PS0309
1PS0310
1SR0302BK External Side Filter Rack (6-Pack)
1BR0314 External Bottom or Horizontal Filter Rack - Cabinet “A”
1BR0317 External Bottom or Horizontal Filter Rack - Cabinet “B”
1BR0321 External Bottom or Horizontal Filter Rack - Cabinet “C”
1BR0324 External Bottom or Horizontal Filter Rack - Cabinet “D”
1CT0302 Concentric Vent Termination - 2” Vent Pipe
1CT0303 Concentric Vent Termination - 3” Vent Pipe
1CB0314 Combustible Floor Base - Cabinet “A”
1CB0317 Combustible Floor Base - Cabinet “B”
1CB0321 Combustible Floor Base - Cabinet “C”
1CB0324 Combustible Floor Base - Cabinet “D”
FILTER PERFORMANCE NOTE: The filter pressure drop values in Table 10 are typical
values for the type of filter listed and should only be used as a
The airflow capacity data published in Tables 8 & 9 repre-
guideline. Actual pressure drop ratings for each filter type
sents blower performance WITHOUT filters. To determine the
vary between filter manufacturer.
approximate blower performance of the system, apply the fil-
ter drop value for the filter being used or select an appropri-
ate value from the Table 10.
The blower motor continues to operate for the amount of time All filters used with the furnace are the high-velocity, clean-
set by the fan-off delay "Jumper" located on the ignition con- able type. Clean these filters by washing in warm water.
trol board (Figure 16). The heating cycle is complete, and the Make sure to shake all the water out of the filter and have it
furnace is ready for the start of the next heating cycle. reasonably dry before installing it in the furnace. When
If the flame is not detected within 2 seconds of the gas valve replacing filters, be sure to use the same size and type as
opening, the gas valve is shut off and a retry operation originally supplied.
begins. If the flame is lost for 2 seconds during the 10 second FILTER REMOVAL - UPFLOW MODELS
stabilization period, the gas valve is shut off and a retry oper-
To remove a filter from the side or bottom location, push the
ation begins. During a retry operation the ventor starts a 15
closed end of the filter retainer to the left until it clears the lip
second inter-purge and the ignitor warm-up time is extended
on the front of the furnace base, which acts as a catch for the
to 27 seconds. If the flame is established for more than 10
retainer. When the retainer is clear of the flange, it will pivot in
seconds after ignition, during a retry, the control will clear the
the loops.
ignition attempt (retry) counter. If three retries occur during a
call for heat, the furnace will shut down for one hour. If at the Swing the retainer toward the center of the furnace. This will
end of the one hour shut down there is a call for heat, the fur- expose the filter to allow removal. To reinstall the filter, simply
nace will initiate a normal start cycle. If the problem has not reverse this procedure.
been corrected the furnace will again lockout after three
retries.
A momentary loss of gas supply, flame blowout, or a faulty
flame probe circuit will result in a disruption in the flame and
be sensed within 0.8 seconds. The gas valve will de-energize
and the control will begin a recycle operation. A normal igni-
tion sequence will begin after a 15 second inter-purge. If dur-
ing the five recycles the gas supply does not return, or the
fault condition is not corrected the ignition control will lock-out
for 60 minutes.
During burner operation, a momentary loss of power for 50
milliseconds or longer will de-energize the gas valve. When
the power is restored, the gas valve will remain de-energized
and the ignition sequence will immediately restart.
HOT SURFACE IGNITION SYSTEM
BLOWER CARE 4. Remove blower assembly mounting screws and slide the
Even with good filters properly in place, blower wheels and blower assembly out of the slots in the deck. If the two
motors will become dust laden after long months of operation. shipping screws were not previously removed, also
The entire blower assembly should be inspected annually. If remove and discard these two screws located on each
the motor and wheel are heavily coated with dust, they can front corner of the blower assembly.
be brushed and cleaned with a vacuum cleaner. 5. On downflow models only, note the wire/terminal location
The procedure for removing the direct drive blower assembly and then remove the blower wiring from the furnace con-
for cleaning is as follows: trol. Remove the protective boot and disconnect run
capacitor wires. Remove the screws securing the electri-
1. Disconnect the electrical supply to the furnace and cal panel to the blower housing. Pull blower assembly
remove remove the access doors. out of the unit. When cleaning or servicing the blower
2. On downflow/horizontal models only, remove the two assembly, DO NOT remove or change the balance clips
wires leading to the auxiliary limit mounted on the blower on the blower wheel.
housing. 6. To reassemble, reverse the procedure, restore power to
3. On downflow/horizontal models only, remove four top the furnace and verify operation.
panel screws and lift the top panel enough to disengage
and remove the flue chase assembly.
All flash code sequences are broken by a 2 second “off” 8 FLASH: This fault is indicated if the flame is lost 5 times (4
period. recycles) during the heating cycle. This could be caused by
low gas pressure or faulty gas valve.
IGNITION CONTROL (P/N 031-01267-001)
9 FLASH: Indicates reversed line voltage polarity. Both
Normal flame sense current is approximately heating and cooling operations will be affected. Check polar-
ity at furnace and branch.
3.7 microamps DC (υa)
11 FLASH: This fault will be indicated if the rollout jumper
Low flame signal control lockout point is wire connection soldered into the board, is broken. If this fault
occurs the control will have to be replaced. This fault may
0.9 microamps DC (υa)
also occur in installations where an improper ground is
present. Prior to replacing control, verify that unit is properly
CONTINUOUS FLASH: This indicates that flame was grounded.
sensed when there was not a call for heat. With this fault
code the control will turn on both the inducer motor and sup- STEADY ON: This fault occurs if the gas valve is energized
ply air blower. This fault would typically be caused by a gas when there is no call for heat. If this happens the ventor is
valve that leaks through or is slow closing. energized and will remain energized for 5 seconds or until the
fault clears itself at which point the ventor de-energizes. This
2 FLASH: This indicates that the normally open pressure failure is counted as a recycle. Check the gas valve and con-
switch contacts are stuck in the closed position. The control trol for proper operation.
confirms these contacts are open at the beginning of each
heat cycle. This would indicate a faulty pressure switch or 60 MINUTE AUTOMATIC RESET FROM LOCKOUT: This
mis-wiring. control includes a "watchdog" type circuit that will reset from
a lockout condition after 60 minutes. Operational faults
3 FLASH: This indicates the normally open pressure switch 1,6,7,8 and Steady On will be reset. This provides protection
contact did not close at the beginning of the heat cycle. This to an unoccupied structure if a temporary condition exists
could be caused by a number of problems; faulty inducer, causing a furnace malfunction. An example would be a low
blocked vent pipe, broken pressure switch hose or faulty incoming gas supply pressure preventing unit operation.
pressure switch. When the gas pressure is restored , at some point the
4 FLASH: This indicates that a primary or auxiliary limit "watchdog" would restart the unit and provide heat for the
switch has opened its normally closed contacts. With this house.
fault code the control will operate the supply air blower and NOTE: If a flame is detected the control flashes the LED for
inducer. This condition may be caused by: dirty filter, improp- 1/8 of a second and then enters a flame stabilization period.
erly sized duct system, incorrect blower speed setting, incor-
rect firing rate or faulty blower motor.
5 FLASH: This fault is indicated if the normally closed con-
tacts in the rollout switch opens. The rollout control is manu-
ally reset. If it has opened, check for proper combustion air, Never jump pressure switch to allow furnace oper-
proper inducer operation, primary heat exchanger failure or ation. To do so will allow furnace to operate under
burner problem. Be sure to reset the switch after correcting potentially hazardous conditions.
the failure condition. Do not try to repair controls. Replace defective
6 FLASH: This indicates that after the unit was operating, controls with UPG Source 1 Parts.
the pressure switch opened 4 times during the call for heat. If Never adjust pressure switch to allow furnace
the main blower is in a "Delay on" mode it will complete it, operation.
and any subsequent delay off period. The ventor continues to
operate until the pressure switch re-closes or a call for heat is
removed.
7 FLASH: This fault code indicates that the flame could not
be established. This no-light condition occured 3 times (2
retries) during the call for heat before locking out. This may
be caused by low gas pressure, faulty gas valve, faulty hot
surface ignitor or burner problem.
EAC
* UNITS SHIPPED WITH HEAT
HEAT
PARK
NEUTRALS
WHT
L1
AND COOL TERMINALS FLAME
HUM
PARK
XFMR
COOL
PRP
JUMPERED. WHT
2 1 HOT SURFACE
SENSOR
BLK IGNITER
BLU 4 P3/S3
FURNACE CONTROL WHT
3
BLK 2
1LP 2
P2/S2
YEL BLK BLK
NO C 1 VENTOR
1 MOTOR
WHT P4/S4
BLK
12 9 6 3
GRN
GND
11 8 5 2 BRN PRI
115V COM
10 7 4 1
P1/S1
ELEMENTARY DIAGRAM
COOL LEGEND
HEAT/COOL FUSE
BLOWER DS DISCONNECT SWITCH
RELAY
HEAT MOTOR GV GAS VALVE 1LP PRESSURE SW, BURNER BOX/VENTOR
GND IGN HOT SURFACE IGNITOR 1RC RUN CAPACITOR
1RC
P1/S1 12 PIN PLUG & SOCKET ON IGNITION 1T TRANSFORMER, 40VA
EAC EAC
EAC CONTROL BOARD IDENTIFIED RUN CAPACITOR
WIRING DIAGRAM - UPFLOW MODELS: P*UR / FG9-UP / G9T-UP
P2/S2 4 PIN PLUG & SOCKET ON IGNITION 24V CONNECTION ROOM THERMOSTAT
HUM HUM CONTROL BOARD
FIELD CONNECTION
HUMIDIFIER P3/S3 2 PIN PLUG & SOCKET AT HOT SURFACE
HUMIDIFIER IGNITOR FACTORY WIRING AND DEVICES
RELAY
P4/S4 2 PIN PLUG & SOCKET AT INDUCER ----- FIELD WIRING AND DEVICES
MOTOR
VENTOR
VENTOR MOTOR LS1 PRIMARY LIMIT SWITCH RELAY CONTACTS ON IGNITION
RELAY ROS1 ROLL OUT SWITCH CONTROL BOARD
IGN - CAUTION -
IGNITER OPEN ALL DISCONNECTS BEFORE
RELAY 120V COM SERVICING THIS UNIT
PRI
NOTES:
3A 1T (40VA)
R R
ON 24V SEC 1. ALL FIELD WIRING PER: (A) NATIONAL ELEC. CODE (NEC) AND/OR
G G (B) CANADIAN ELEC. CODE (CEC) AND/OR
AUTO GAS VALVE
RELAYS (C) LOCAL OR CITY CODES.
Y Y 2. IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE
GV REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A
COOL GND TEMPERATURE RATING OF AT LEAST 221ßF (105ßC).
C ROS1
OFF 3. CONNECTORS SUITABLE FOR COPPER CONDUCTORS ONLY.
HEAT 4. ALL REPLACEMENT COMPONENTS MUST BE PROPERLY GROUNDED.
NOTE: THE FURNACE’S CONTROL SYSTEM REQUIRES CORRECT POLARITY OF THE POWER SUPPLY.
1LP LS1
W W NO C 5. PROVIDE DISCONNECTS FOR ALL POWER SUPPLIES.
HEAT/COOL THERMOSTAT
6. MOTORS ARE INHERENTLY PROTECTED.
90+ UPFLOW FURNACE 035-17474-000A
035-17477-001 Rev. A (801)