Transmisor de Presion Diferencial DM 2000 - Dwyer - InProcess

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

PRESSURE

SERIES DM-2000

DIFFERENTIAL PRESSURE TRANSMITTERS


Same Size as Standard Magnehelic Differential Pressure Gage
®

HIGH PRESSURE PORT

1-1/4
[31.75]

LOW PRESSURE PORT

7/16
[11.11] ø4-3/4
17/32 [120.65]
[13.50] 5/32
[3.97]
DM-2000-LCD DM-2100-LCD 1-11/16
[42.86]

The Dwyer Series DM-2000 Differential Pressure Transmitters sense the pressure SPECIFICATIONS
of air and compatible gases and sends a standard 4-20 mA output signal. The DM- Service: Air and non-combustible, compatible gases.
2000 housing is specifically designed to mount in the same diameter cutout as a Wetted Materials: Consult factory.
standard Magnehelic® gage. A wide range of models are available factory calibrated Accuracy: ±1% FS, ±30 Pa model ±4% FS at 70°F.
to specific ranges. Stability: ±1% FS/yr.
Pressure connections are inherent to the glass filled plastic molded housing making Temperature Limits: 20 to 120°F (-6.67 to 48.9°C).
installation quick and easy. Digital push-button zero and span simplify calibration over Pressure Limits: 10 psig (0.69 bar).
typical turn-potentiometers. An optional 3.5 digit LCD shows process and engineering ­Thermal Effect: ±0.055% FS/°F (0.099% FS/°C), ±30 Pa model ±0.13% FS/°F
units. A single push-button allows field selection of 4 to 6 engineering units depending (0.234% FS/°C).
on range. Power Requirements: 10-35 VDC (2 wire).
Output Signal: 4-20 mA.
FEATURES/BENEFITS Zero and Span Adjustments: Digital push-button zero and span.
• Zero and span controls provide easy calibration checks and shorter installation time Loop Resistance: DC: 0 to 1250 Ω maximum.
to get device running and monitoring Current Consumption: DC: 38 mA max.
• Quick response to pressure changes means no delay in signaling and alerting to Electrical Connections: Screw-type terminal block.
critical situations

Differential Pressure Transmitters,


Display: 3.5 digit LCD, 0.7˝ H.
• Easy to read LCD display provides immediate local alerts allowing corrective action Process Connections: 1/8˝ ID tubing.
to be taken quicker to eliminate the problem from becoming widespread Mounting Orientation: Vertical.
• Same size as Magnehelic® simplifies field upgrade to digital pressure gage by Weight: 4.8 oz (136 g).
reducing install steps

Air & Gas


• Tamper proof button configuration to prevent accidental changes to the settings

APPLICATIONS
• Differential pressure across filters
• Fan control
• Static pressures in ducts or buildings
MODEL CHART
Model Range (in w.c.) Pa mm w.c. mBar kPa psi
DM-2001-LCD 0 to .100 24.9 2.54 .249 - -
DM-2002-LCD 0 to .250 62.2 6.35 .622 - -
DM-2003-LCD 0 to .500 124.3 12.70 1.243 .124 -
DM-2004-LCD 0 to 1.000 249 25.4 2.49 .249 -
DM-2005-LCD 0 to 2.00 497 50.8 4.97 .497 -
DM-2006-LCD 0 to 3.00 746 76.2 7.46 .746 .108
DM-2007-LCD 0 to 5.00 1243 127-0 12.43 1.243 .180
DM-2012-LCD 0 to ±.250 0 to ±62.2 0 to ±6.35 0 to ±.622 - -
DM-2013-LCD 0 to ±.500 0 to ±124.3 0 to ±12.70 0 to ±1.243 - -
DM-2019-LCD 0 to ±.200 0 to ±49.8 0 to ±5.08 0 to ±.498 - -
Note: For white overlay change -20 to -21. Example: DM-2102-LCD

ACCESSORIES OPTIONS
Model Description To order add suffix: Description
A-299 Surface mounting bracket -NIST NIST traceable calibration certificate
A-300 Flat flush mounting bracket Example: DM-2002-LCD-NIST
A-302F-A 303 SS static pressure tip with mounting flange; for 3/16˝ -FC Factory calibration certificate
ID rubber or plastic tubing; 4˝ insertion depth; includes Example: DM-2002-LCD-FC
mounting screws
A-320-A Instrument enclosure
A-489 4˝ straight static pressure tip with flange
SCD-PS 100-240 VAC/VDC to 24 VDC power supply

Process Tubing Options: See page 453 (Gage Tubing Accessories)

DWYER INSTRUMENTS, INC. | dwyer-inst.com 63

Pressure_2021.indb 63 7/15/20 8:19 AM