Date 1/27/2024

Project

Created with DIALux


Project

Preface

Notes on planning:

The energy consumption quantities do not take into account light


scenes and their dimming levels.
Project

Table of Contents

Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Product data sheets


PARAGON - Panel Edge-lit Light PLPA G2 Series 40W 6500K IP30 (1x Panel Light . . . . . . . . . . . . . . . . . . . . . .7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLPA40L-G2/65)
PARAGON - Surface Downlight PSDH Series 7W 3000K IP20 (1x Surface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downlight PSDH113L7/30)

Site 1

Building 1
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Site 1 - Building 1

Storey 1
Room list / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13.............................

Site 1 - Building 1 - Storey 1

Cửa hàng
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
17
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21.............................
Working plane (Cửa hàng) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . .
23............................

Site 1 - Building 1 - Storey 1

NVS 1
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
26
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
28
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29.............................
Project

Table of Contents

Working plane (NVS 1) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . .31


.............................

Site 1 - Building 1 - Storey 1

NVS 2
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
36
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37.............................
Working plane (NVS 2) / Light scene 1 / Perpendicular illuminance (adaptive) . . . . . . . . . . . . . . . . . . . . . . . .39. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
.............................
Project

Description

5
Project

Luminaire list

Φtotal Ptotal Luminous efficacy


96889 lm 865.9 W 111.9 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

21 PARAGON PLPA40L- Panel Edge-lit Light PLPA G2 Series 40W 6500K IP30 39.9 W 4437 lm 111.2 lm/W
G2/65

4 PARAGON PSDH113L Surface Downlight PSDH Series 7W 3000K IP20 7.0 W 928 lm 132.6 lm/W
7/30

6
Project

Product data sheet

PARAGON - Panel Edge-lit Light PLPA G2 Series 40W 6500K IP30

Article No. PLPA40L-G2/65

P 39.9 W

ΦLuminaire 4437 lm

Luminous efficacy 111.2 lm/W

CCT 6500 K

CRI 80 Polar LDC

LED Edge-lit Panel PLPA40L-G2 delivers superior and ultra-durable


lighting with energy-efficient and long lifespan LED chips, that is up
to 50% more energy efficient compared to fluorescent lighting
solutions. G2 variant still retains its slim profile – 10mm thick – LED
panel in the market and an efficacy level of 110lm/w, that offers
exceptional value and is Perfect for your everyday lighting
application. It is easy to install and almost maintenance-free
throughout its rated lifespan. Paragon’s PLPA series is ideal for both
commercial and residential indoor lighting applications. The
following product comes with 3-year manufacturer’s warranty.

7
Project

Product data sheet

PARAGON - Surface Downlight PSDH Series 7W 3000K IP20

Article No. PSDH113L7/30

P 7.0 W

ΦLuminaire 928 lm

Luminous efficacy 132.6 lm/W

CCT 3000 K

CRI 80 Polar LDC

Surface Downlight PSDH Series deliver superior and ultra-durable


lighting with energy-efficient and long lifespan LED chips and high
quality aluminium alloy heatsink, that is up to 50% more energy
efficient compared to fluorescent lighting solutions. Paragon’s PSDH
series is ideal for commercial indoor lighting applications and
suitable for shopping malls, supermarkets, hotels, offices, conference
rooms, department stores, exhibition center, villas and other lighting
purposes. The following product comes with 3-year manufacturer’s
warranty.

8
Project

Building 1
Luminaire list

Φtotal Ptotal Luminous efficacy


96889 lm 865.9 W 111.9 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

21 PARAGON PLPA40L- Panel Edge-lit Light PLPA G2 Series 40W 6500K IP30 39.9 W 4437 lm 111.2 lm/W
G2/65

4 PARAGON PSDH113L Surface Downlight PSDH Series 7W 3000K IP20 7.0 W 928 lm 132.6 lm/W
7/30

9
Project

Building 1 · Storey 1 (Light scene 1)


Room list

10
Project

Building 1 · Storey 1 (Light scene 1)


Room list

Cửa hàng

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


837.9 W 164.09 m² 5.11 W/m² = 1.65 W/m²/100 lx (Room) 309 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

21 PARAGON PLPA40L- Panel Edge-lit Light PLPA G2 Series 40W 6500K IP30 39.9 W 4437 lm
G2/65

NVS 1

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


14.0 W 1.60 m² 8.76 W/m² = 7.04 W/m²/100 lx (Room) 124 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 PARAGON PSDH113L Surface Downlight PSDH Series 7W 3000K IP20 7.0 W 928 lm
7/30

NVS 2

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


14.0 W 1.61 m² 8.71 W/m² = 6.36 W/m²/100 lx (Room) 137 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

2 PARAGON PSDH113L Surface Downlight PSDH Series 7W 3000K IP20 7.0 W 928 lm
7/30

11
Project

Building 1 · Storey 1
Luminaire list

Φtotal Ptotal Luminous efficacy


96889 lm 865.9 W 111.9 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

21 PARAGON PLPA40L- Panel Edge-lit Light PLPA G2 Series 40W 6500K IP30 39.9 W 4437 lm 111.2 lm/W
G2/65

4 PARAGON PSDH113L Surface Downlight PSDH Series 7W 3000K IP20 7.0 W 928 lm 132.6 lm/W
7/30

12
Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

13
Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Cửa hàng) 309 lx 37.6 lx 499 lx 0.12 0.075 WP1
Perpendicular illuminance (adaptive) (≥ 500 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Working plane (NVS 1) 124 lx 9.86 lx 160 lx 0.080 0.062 WP2


Perpendicular illuminance (adaptive) (≥ 100 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Working plane (NVS 2) 137 lx 109 lx 155 lx 0.80 0.70 WP3


Perpendicular illuminance (adaptive) (≥ 100 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

14
Project

Building 1 · Storey 1 · Cửa hàng (Light scene 1)


Summary

Ground area 164.09 m² Clearance height 2.670 m

Reflection factors Ceiling: 56.4 %, Mounting height 2.670 m


Walls: 30.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

15
Project

Building 1 · Storey 1 · Cửa hàng (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 309 lx ≥ 500 lx WP1

Uo (g1 ) 0.12 ≥ 0.40 WP1

Energy estimation(2) Consumption [2079.67 - 2446.67] max. 5750 kWh/a


kWh/a

Room Lighting power density 5.11 W/m² –

1.65 W/m²/100 lx –

(1) Based on a rectangular space of 11.601 m x 16.511 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: Retail premises (35.1 Sales area)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

21 PARAGON PLPA40L- Panel Edge-lit Light PLPA G2 Series 40W – 39.9 W 4437 lm 111.2 lm/W
G2/65 6500K IP30

16
Project

Building 1 · Storey 1 · Cửa hàng


Luminaire layout plan

17
Project

Building 1 · Storey 1 · Cửa hàng


Luminaire layout plan

Manufacturer PARAGON P 39.9 W

Article No. PLPA40L-G2/65 ΦLuminaire 4437 lm

Article name Panel Edge-lit Light


PLPA G2 Series 40W
6500K IP30

Fitting 1x Panel Light


PLPA40L-G2/65

21 x Paragon Panel Edge-lit Light PLPA G2 Series 40W 6500K IP30

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.042 m / 1.376 m /
2.670 m 8.200 m 15.200 m 2.670 m 1

X-direction 4 pcs., Centre - 1.042 m 12.076 m 2.670 m 2


centre, Distances not
equal 4.592 m 12.076 m 2.670 m 3

Y-direction 6 pcs., Centre - 7.546 m 12.076 m 2.670 m 4


centre, Distances not
equal 10.500 m 12.076 m 2.670 m 5

Arrangement A1 1.042 m 9.401 m 2.670 m 6

4.592 m 9.401 m 2.670 m 7

7.546 m 9.401 m 2.670 m 8

10.500 m 9.401 m 2.670 m 9

1.042 m 6.726 m 2.670 m 10

4.592 m 6.726 m 2.670 m 11

7.546 m 6.726 m 2.670 m 12

10.500 m 6.726 m 2.670 m 13

18
Project

Building 1 · Storey 1 · Cửa hàng


Luminaire layout plan

X Y Mounting Luminaire
height

1.042 m 4.051 m 2.670 m 14

4.592 m 4.051 m 2.670 m 15

7.546 m 4.051 m 2.670 m 16

10.500 m 4.051 m 2.670 m 17

1.042 m 1.376 m 2.670 m 18

4.592 m 1.376 m 2.670 m 19

7.546 m 1.376 m 2.670 m 20

10.500 m 1.376 m 2.670 m 21

19
Project

Building 1 · Storey 1 · Cửa hàng


Luminaire list

Φtotal Ptotal Luminous efficacy


93177 lm 837.9 W 111.2 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

21 PARAGON PLPA40L- Panel Edge-lit Light PLPA G2 Series 40W 6500K IP30 39.9 W 4437 lm 111.2 lm/W
G2/65

20
Project

Building 1 · Storey 1 · Cửa hàng (Light scene 1)


Calculation objects

21
Project

Building 1 · Storey 1 · Cửa hàng (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Cửa hàng) 309 lx 37.6 lx 499 lx 0.12 0.075 WP1
Perpendicular illuminance (adaptive) (≥ 500 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Retail premises (35.1 Sales area)

22
Project

Building 1 · Storey 1 · Cửa hàng (Light scene 1)


Working plane (Cửa hàng)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Cửa hàng) 309 lx 37.6 lx 499 lx 0.12 0.075 WP1
Perpendicular illuminance (adaptive) (≥ 500 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: Retail premises (35.1 Sales area)

23
Project

Building 1 · Storey 1 · NVS 1 (Light scene 1)


Summary

Ground area 1.60 m² Clearance height 3.000 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.990 m


Walls: 30.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

24
Project

Building 1 · Storey 1 · NVS 1 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 124 lx ≥ 100 lx WP2

Uo (g1 ) 0.080 ≥ 0.40 WP2

Energy estimation(2) Consumption 34.7 kWh/a max. 100 kWh/a

Room Lighting power density 8.76 W/m² –

7.04 W/m²/100 lx –

(1) Based on a rectangular space of 1.530 m x 1.045 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 PARAGON PSDH113L Surface Downlight PSDH Series 7W 3000K – 7.0 W 928 lm 132.6 lm/W
7/30 IP20

25
Project

Building 1 · Storey 1 · NVS 1


Luminaire layout plan

26
Project

Building 1 · Storey 1 · NVS 1


Luminaire layout plan

Manufacturer PARAGON P 7.0 W

Article No. PSDH113L7/30 ΦLuminaire 928 lm

Article name Surface Downlight


PSDH Series 7W
3000K IP20

Fitting 1x Surface Downlight


PSDH113L7/30

2 x Paragon Surface Downlight PSDH Series 7W 3000K IP20

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.261 m / 0.765 m /
2.990 m 0.261 m 0.765 m 2.990 m 1

X-direction 2 pcs., Centre - 0.784 m 0.765 m 2.990 m 2


centre, 0.523 m

Y-direction 1 pcs., Centre -


centre, 1.530 m

Arrangement A1

27
Project

Building 1 · Storey 1 · NVS 1


Luminaire list

Φtotal Ptotal Luminous efficacy


1856 lm 14.0 W 132.6 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 PARAGON PSDH113L Surface Downlight PSDH Series 7W 3000K IP20 7.0 W 928 lm 132.6 lm/W
7/30

28
Project

Building 1 · Storey 1 · NVS 1 (Light scene 1)


Calculation objects

29
Project

Building 1 · Storey 1 · NVS 1 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (NVS 1) 124 lx 9.86 lx 160 lx 0.080 0.062 WP2


Perpendicular illuminance (adaptive) (≥ 100 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)

30
Project

Building 1 · Storey 1 · NVS 1 (Light scene 1)


Working plane (NVS 1)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (NVS 1) 124 lx 9.86 lx 160 lx 0.080 0.062 WP2


Perpendicular illuminance (adaptive) (≥ 100 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)

31
Project

Building 1 · Storey 1 · NVS 2 (Light scene 1)


Summary

Ground area 1.61 m² Clearance height 3.000 m

Reflection factors Ceiling: 70.0 %, Mounting height 2.990 m


Walls: 30.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

32
Project

Building 1 · Storey 1 · NVS 2 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 137 lx ≥ 100 lx WP3

Uo (g1 ) 0.80 ≥ 0.40 WP3

Energy estimation(2) Consumption 34.7 kWh/a max. 100 kWh/a

Room Lighting power density 8.71 W/m² –

6.36 W/m²/100 lx –

(1) Based on a rectangular space of 1.530 m x 1.050 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

2 PARAGON PSDH113L Surface Downlight PSDH Series 7W 3000K – 7.0 W 928 lm 132.6 lm/W
7/30 IP20

33
Project

Building 1 · Storey 1 · NVS 2


Luminaire layout plan

34
Project

Building 1 · Storey 1 · NVS 2


Luminaire layout plan

Manufacturer PARAGON P 7.0 W

Article No. PSDH113L7/30 ΦLuminaire 928 lm

Article name Surface Downlight


PSDH Series 7W
3000K IP20

Fitting 1x Surface Downlight


PSDH113L7/30

2 x Paragon Surface Downlight PSDH Series 7W 3000K IP20

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.263 m / 0.765 m /
2.990 m 0.263 m 0.765 m 2.990 m 1

X-direction 2 pcs., Centre - 0.788 m 0.765 m 2.990 m 2


centre, 0.525 m

Y-direction 1 pcs., Centre -


centre, 1.530 m

Arrangement A1

35
Project

Building 1 · Storey 1 · NVS 2


Luminaire list

Φtotal Ptotal Luminous efficacy


1856 lm 14.0 W 132.6 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

2 PARAGON PSDH113L Surface Downlight PSDH Series 7W 3000K IP20 7.0 W 928 lm 132.6 lm/W
7/30

36
Project

Building 1 · Storey 1 · NVS 2 (Light scene 1)


Calculation objects

37
Project

Building 1 · Storey 1 · NVS 2 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (NVS 2) 137 lx 109 lx 155 lx 0.80 0.70 WP3


Perpendicular illuminance (adaptive) (≥ 100 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)

38
Project

Building 1 · Storey 1 · NVS 2 (Light scene 1)


Working plane (NVS 2)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (NVS 2) 137 lx 109 lx 155 lx 0.80 0.70 WP3


Perpendicular illuminance (adaptive) (≥ 100 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Store rooms, cold stores (12.1 Store and stockrooms)

39
Project

Glossary

A Formula symbol for a surface in the geometry

Background area The background area borders the direct ambient area according to DIN EN 12464-1 and
reaches up to the borders of the room. In larger rooms, the background area is at least
3 m wide. It is located horizontally at floor level.

CCT (Engl. correlated colour temperature)


Body temperature of a thermal radiator which serves to describe its light colour. Unit:
Kelvin [K]. The lesser the numerical value the redder; the greater the numerical value the
bluer the light colour. The colour temperature of gas-discharge lamps and semi-
conductors are termed "correlated colour temperature" in contrast to the colour
temperature of thermal radiators.

Allocation of the light colours to the colour temperature ranges acc. to EN 12464-1:

Light colour - colour temperature [K]


warm white (ww) < 3, 300 K
neutral white (nw) ≥ 3, 300 – 5,300 K
daylight white (dw) > 5,300 K

Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).

Control group A group of luminaires that are dimmed and controlled together. For each lighting scene,
a control group provides its own dimming value. All luminaires within a control group
share this dimming value. The control groups with their luminaires are automatically
determined by DIALux on the basis of the created light scenes and their luminaire
groups.

CRI (Engl. colour rendering index)


Designation for the colour rendering index of a luminaire or a lamp acc. to DIN 6169:
1976 or CIE 13. 3: 1995.

The general colour rendering index Ra (or CRI) is a dimensionless figure that describes
the quality of a white light source in regards to its similarity with the remission spectra of
defined 8 test colours (see DIN 6169 or CIE 1974) to a reference light source.

40
Project

Glossary

Daylight autonomy Describes what percentage of the daily working time the required illuminance is met by
daylight. The nominal illuminance is used from the room profile, unlike described in EN
17037. The calculation is not done in the centre of the room but at the placed sensor
measuring point. A room is considered sufficiently supplied with daylight if it achieves at
least 50% daylight autonomy.

Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside to
the horizontal illuminance in the outer area under an unobstructed sky.

Formula symbol: D (Engl. daylight factor)


Unit: %

Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.

Energy evaluation Based on an hourly calculation procedure for daylight in indoor spaces, considering the
project geometry and any existing daylight control systems. Orientation and location of
the project are also considered. The calculation uses the specified system power of the
luminaires to determine the energy demand. A linear relationship between power and
luminous flux in the dimmed state is assumed for daylight-controlled luminaires. Times
of use and nominal illuminance are determined from the usage profiles of the spaces.
Switched-on luminaires that are explicitly excluded from control also consider the
specified times-of-use. The daylight control systems use a simplified control logic that
closes them at an outdoor horizontal illuminance of 27,500lx.

The calendar year 2022 is used as a reference only. It is not a simulation of this year. The
reference year is only used to assign the days of the week to the calculated results. The
changeover to summer time is not considered. The reference sky type used is the
average sky described in CIE 110 without direct sunlight.

The method was developed together with the Fraunhofer Institute for Building Physics
and is available for review by the Joint Working Group 1 ISO TC 274 as an extension of
the previous annual regression-based method.

Eta (η) (light output ratio)


The light output ratio describes what percentage of the luminous flux of a free radiating
lamp (or LED module) is emitted by the luminaire when installed.

Unit: %

41
Project

Glossary

g1 Often also Uo (Engl. overall uniformity)


Designates the overall uniformity of the illuminance on a surface. It is the quotient from
Emin to Ē and is required, for instance, in standards for illumination of workstations.

g2 Actually it designates the "non-uniformity" of the illuminance on a surface. It is the


quotient of Emin to Emax and is generally only relevant for certifying the emergency
lighting acc. to EN 1838.

Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be determined
anywhere in space (inside or outside). The illuminance is not a product feature because it
is a recipient value. Luxometers are used for measuring.

Unit: Lux
Abbreviation: lx
Formula symbol: E

Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.

Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.

Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.

Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.

LENI (Engl. lighting energy numeric indicator)


Lighting energy numeric indicator acc. to EN 15193

Unit: kWh/(m² * a)

42
Project

Glossary

LLMF (Engl. lamp lumen maintenance factor)/acc. to CIE 97: 2005


Lamp flux maintenance factor that takes the luminous flux reduction into account of a
luminaire or an LED module in the course of the operating time. The lamp flux
maintenance factor is specified as a decimal digit and can have a maximum value of 1
(no luminous flux reduction existing).

LMF (Engl. luminaire maintenance factor)/acc. to CIE 97: 2005


Luminaire maintenance factor that takes the soiling into account of the luminaire in the
course of the operating time. The luminaire maintenance factor is specified as a decimal
digit and can have a maximum value of 1 (no soiling existing).

LSF (Engl. lamp survival factor)/acc. to CIE 97: 2005


Lamp survival factor that takes the total failure into account of a luminaire in the course
of the operating time. The lamp survival factor is specified as a decimal digit and can
have a maximum value of 1 (no failures existing within the time concerned or prompt
replacement after the failure).

Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It is
the only photometric value that the human eye can perceive.

Unit: Candela per square metre


Abbreviation: cd/m²
Formula symbol: L

Luminous efficacy Ratio of the emitted luminous flux Φ [ lm] to the absorbed electrical power P [W] Unit:
lm/W.

This ratio can be formed for the lamp or LED module (lamp or module light output), the
lamp or module with control gear (system light output) and the complete luminaire
(luminaire light output).

Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux.

Unit: Lumen
Abbreviation: lm
Formula symbol: Φ

Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit.

Unit: Candela
Abbreviation: cd
Formula symbol: I

43
Project

Glossary

Maintenance factor See MF

MF (Engl. maintenance factor)/acc. to CIE 97: 2005


Maintenance factor as decimal number between 0 and 1 that describes the ratio of the
new value of a photometric planning parameter (e.g. of the illuminance) to a
maintenance value after a certain time. The maintenance factor takes into account the
soiling of luminaires and rooms as well as the luminous flux reduction and the failure of
light sources.
The maintenance factor is taken into account either overall or determined in detail acc.
to CIE 97: 2005 by the formula RMF x LMF x LLMF x LSF.

P (Engl. power)
Electric power consumption

Unit: watt
Abbreviation: W

R(UG) max Measure of the psychological glare in indoor spaces.


In addition to the luminance of luminaires, the level of the R(UG) value also depends on
the observer position, the viewing direction and the ambient luminance. The calculation
is made according to the table method, see CIE 117. Among other things, EN 12464-
1: 2021 specifies maximum permissible R(UG) - values R( UGL) for various indoor workplaces.

Reflection factor The reflection factor of a surface describes how much of the striking light is reflected
back. The reflection factor is defined by the colour of the surface.

RMF (Engl. room maintenance factor)/acc. to CIE 97: 2005


Room maintenance factor that takes the soiling into account of the space encompassing
surfaces in the course of the operating time. The room maintenance factor is specified
as a decimal digit and can have a maximum value of 1 (no soiling existing).

Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.

44
Project

Glossary

UGR (max) (unified glare rating)


Measure for the psychological glare effect in interiors.
In addition to luminaire luminance, the UGR value also depends on the position of the
observer, the viewing direction and the ambient luminance. Among other things, EN
12464-1 specifies maximum permissible UGR values for various indoor workplaces.

UGR observer Calculation point in the room, for the DIALux the UGR value is determined. The location
and height of the calculation point should correspond to the typical observer position
(position and eye level of the user).

Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN 12464
-1. The height corresponds with the height at which the visual task is executed.

Wall zone Circumferential area between working plane and walls which is not taken into account
for the calculation.

Working plane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.

45