4plan 16-02-2024-Model

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

A B C D E F G H I J

350

10KVA UPS OUTPUT PANEL 4


1 1
R Y B

GLAND PLATE
GLAND PLATE MFM

C 500mm

MCB 63 A A
C 4P 10 KA -3
500mm B
2
A 2
L
B
E
L
E BUS BAR 125 A
350mm
1200 FRONT BACK
ON OFF TRIP
MCB 63 A
A 350mm 4P 10 KA -2 A
3 L MCCB 80 A
L 3
4P 36 KA -1
L L
E E
Y Y 350mm
Spare
350mm
GLAND PLATE INCOMER
GLAND PLATE
ATS 80A 4P, E
4 4
C-CHANEL
SIDE VIEW
500mm 300mm 300mm
TOP /BOTTOM VIEW

400
1100 350

5 1100 5
STAND

FRONT VIEW
NOTES:-
PANEL-SIZE 1200X1100X350 1. ALL DIMENSIONS ARE IN MM.
2. FABRICATION-2 mm. THK. OUTSIDE
AND 1.6 mm. THK. MS. SHEET. INSIDE
6 3. PANEL SHOULD BE INDOOR TYPE & EPOXY POWDER
6
COATED 7032 SIEMENS GREY
1. ANGLE IRON 40X40X5 MM 2. BUS BAR COLOUREDS INSULATED WITH HEAT SHRINKABLE SLEEVE
4. PROTECTOIN CLASS - IP54
3. ALL MCCB ICS =100% ICU 4. MIN CLEARANCE IN BUS BAR B/W PHASE TO PHASE 25MM 5. CABLE ENTRY - BOTTOM-TOP
5.FEEDER NAME ON EACH MCCB DOOR 6. EARTHING STUD
6.All Switchgear MCCBs make L&T/ABB

THIS DRAWING IS THE PROPERTY OF CALLISTO AND ANY UNAUTHORISED USE THEREOF BY COPYING OR OTHERWISE BY ANY PARTY WHATSOEVER IS STRICTLY PROHIBITED
PROJECT: GWALIOR AIRPORT REVISION NO: TITTLE: M/S- CALLISTO(YOU THINK WE DO)
WITH SIGN & DATE Add- CITY CENTER GWALIOR (M.P) 474002
A GENERAL ARRANGEMENT
CUSTOMER: KPC PROJECT B
PANEL MANUFACTURER
OUT DOOR TYPE FEEDER PILLAR
C
7 P.O.& DATE : D DRAWN DESIGN CHECKD. APPRVD. SCALE: DRG.NO: 7
JOB REFERENCE NO: E KUNDAN 1:1 (SHEET - 1 OF 1)
QTN / LOI NO & DATE: 10138 SUBMITTED FOR QUOTATION APPROVAL REFERENCE INFORMATION RECORD CONSTRUCTION
A B C D E F G H I J