Smoke& Ven Cal R1
Smoke& Ven Cal R1
Smoke& Ven Cal R1
For …………………………………
dT = 93 K
And
Ts = To + DT …………………….(4)
Where :
Ts = Smoke temp.
To =Ambient temp. = 303 K
Ts = 396 K
Ms Ts
V = ……………….(5)
To ps
Where :-
V = Required air volumetric flow rate
ps = Smoke density = 1.2 Kg/m3
V = 9.7 M3/Sec.
V = A X v ………………………….(8)
Where v = volumetric flow rate for one fan = 21,000 cfm
OR. v = volumetric flow rate for one fan = 9.7 M3/Sec.
A = duct cross sec. Area
V = desired air velocity in the duct = 6 M/Sec.
A = 1.62 M2
Static pressure ( in.wg) = 0.5 + duct friction loss
where duct friction loss = 0.5 in.wg
Total Static pressure ( in.wg) = 1 in.wg.
input the sugested fans
numbers here .
Conclusion : If u put it as one it gives
System Discription : the total flow required .
Exhaust Smoke Fans :
Nunmers: 2 Nos. Fans/Zone
Capacity: 10,500 cfm (each)
Type : Tubilar ducted
EDIT THE ACTUAL
Location : …………………………………………. NO. AS PER ARCH.
DRAWINGS .
# Determining fresh air intake area :
No. of entrances and doors = 2 doors
Average door size (m) = 2.2 (width) , 2 (height)
= 4.4 m2
Total fresh air intake area = 8.8 m2
V = AXv ………………………….(8)
GENERAL
- All fans used in smoke management and exhaust system ( exhaust and fresh air fans )
shall be capable to withstand 200 oC temp.for 30 min.
- All fans shall be interconnected with fire allarm panel for automatic operation also, shall be
provided with ON /OFF switch near enterances for manual operation by occupants.
Stair Case Pressurization For Internal Stairs .
Qe = KAe (P)1/2
Where :
Ae = 0.003 x (( 2.2 + 1 )X2) X 0 = 0 M2
K = 0.839
P = 50 Pascal.
Qe = 0.839 x Ae x (50)1/2
Qe = 0 M3/Sec. = 0 CFM