Smoke& Ven Cal R1

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 4

Mechanical Smoke Ventilation Calculations

For …………………………………

Mechanical Ventilation system for ………………………


# Assumptions:-
Fire Area = 3x3 = 9 sq.m
Smoke Plume High (Y) = 2.5 M
Total height (H) = 3.5 M
Smoke layer thickness (db) = H - Y = 1 M
Floor Area = sq.m

# Determining the heat release


HEAT RELEASE =
Q = q x A …………………………(1) 93 KW/M2 FOR FURNATURE
where q = 93 KW/sq.M (for vehicles) 310 KW/M2 FOR CELLULOSICS
Refference :- BS7436 tables with aid of NFBA 204M tables . (‫)ورق كارتون للتعبئه والتغليف و منتجات قطنية‬
260 KW/M2 FOR VIHICLES(car park)
From equation (1)
Qs = 837 kw

# Determining smoke mass flow rate Ms


Ms = 0.188 PY 3/2 ………………… (2)
where P = Fire Perimeter = 12 M
Y = Clear height of smoke plume = 2.5 M
From equation (2)
Ms = 0.188 x12 x 2.53/2
Ms = 8.9 kg/s.

# Determining plume temperature rise :


Qs
dT = ………….(3)
Ms x Cps

dT = 93 K
And
Ts = To + DT …………………….(4)
Where :
Ts = Smoke temp.
To =Ambient temp. = 303 K

Ts = 396 K

# Determining the required air flow rate :

Ms Ts
V = ……………….(5)
To ps
Where :-
V = Required air volumetric flow rate
ps = Smoke density = 1.2 Kg/m3

V = 9.7 M3/Sec.

= 20,584 CFM ~~= 21,000 CFM


# Determining duct size and fan static pressure :-

V = A X v ………………………….(8)
Where v = volumetric flow rate for one fan = 21,000 cfm
OR. v = volumetric flow rate for one fan = 9.7 M3/Sec.
A = duct cross sec. Area
V = desired air velocity in the duct = 6 M/Sec.

A = 1.62 M2
Static pressure ( in.wg) = 0.5 + duct friction loss
where duct friction loss = 0.5 in.wg
Total Static pressure ( in.wg) = 1 in.wg.
input the sugested fans
numbers here .
Conclusion : If u put it as one it gives
System Discription : the total flow required .
Exhaust Smoke Fans :
Nunmers: 2 Nos. Fans/Zone
Capacity: 10,500 cfm (each)
Type : Tubilar ducted
EDIT THE ACTUAL
Location : …………………………………………. NO. AS PER ARCH.
DRAWINGS .
# Determining fresh air intake area :
No. of entrances and doors = 2 doors
Average door size (m) = 2.2 (width) , 2 (height)
= 4.4 m2
Total fresh air intake area = 8.8 m2

V = AXv ………………………….(8)

Where V = The required fresh air supply


= 21,000 CFM
= 9.7 M3/Sec.
Assuming average air velocity through doors to be 2m/s ( to allow door opening for
occupants evacuation )
in case if the enterances
A= 4.86 m2
area is less than the
The required area is less than doors and enterance areas required area , so, the
SO, Enterance area is sufficient as fresh air supply openings . fresh air fans are required
.
Fresh Air Fans:
Fresh Air Fans capacity shall be half of exhaust air capacity depending on the doors and
park ramp opening to deliver adequate fresh air amount for the other half of the floor area .
Fresh Air properties shall be :
Nunmers: 2 Nos. Fans
Capacity: 5,250 cfm (each)
Type : Tubilar ducted
Location : ………………………………………….
Total Static pressure ( in.wg) = 1 in.wg.

GENERAL

- All fans used in smoke management and exhaust system ( exhaust and fresh air fans )
shall be capable to withstand 200 oC temp.for 30 min.

- All fans shall be interconnected with fire allarm panel for automatic operation also, shall be
provided with ON /OFF switch near enterances for manual operation by occupants.
Stair Case Pressurization For Internal Stairs .

No. Of Floors = Gr. + Floors + Roof = 2 Floors

No. Of Doors = (Gr. + (Typical Floors) + (Roof ) = 0 Doors

Door Size = 2.2 H , 0.8 W

Qe = KAe (P)1/2

Where :
Ae = 0.003 x (( 2.2 + 1 )X2) X 0 = 0 M2

K = 0.839
P = 50 Pascal.

Qe = 0.839 x Ae x (50)1/2

Qe = 0 M3/Sec. = 0 CFM

Incase One Door Opened :

VA 0.75 x 2.2 x 0.8


Qo = = = 2.2 M3/Sec. = 4659.6 M3/Sec.
0.6 0.6
M3/Sec.

You might also like