TECHNICAL
ENGINE SPECIFICATIONS
Manufacturer CUMMINS
Model KTA38-G2A
Phase 3
Displacement (L) 38
TECHNOPOWER FZC Q4-94, SHARJAH AIRPORT INT’L FREEZONE (SAIF ZONE), SHARJAH, UAE.
Call: +971 6557 9794, Fax: +971 6557 9792, Email: [email protected], Website: www.technopowergroup.com
TPC-900
POWERED BY CUMMINS
KTA38-G2A
TECHNICAL DATA
COOLING SYSTEM
FUEL SYSTEM
LUBRICATING SYSTEM
EXHAUST SYSTEM
FUEL SYSTEM
TECHNOPOWER FZC Q4-94, SHARJAH AIRPORT INT’L FREEZONE (SAIF ZONE), SHARJAH, UAE.
Call: +971 6557 9794, Fax: +971 6557 9792, Email: [email protected], Website: www.technopowergroup.com
TPC-900
POWERED BY CUMMINS
KTA38-G2A
ALTERNATOR SPECIFICATIONS
TECHNOPOWER FZC Q4-94, SHARJAH AIRPORT INT’L FREEZONE (SAIF ZONE), SHARJAH, UAE.
Call: +971 6557 9794, Fax: +971 6557 9792, Email: [email protected], Website: www.technopowergroup.com
DSEGenset®
DC SUPPLY
AUTO START & AUTO MAINS FAILURE CONTROL MODULES CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
5 V for upto 1 minute
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing
supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.
FREQUENCY RANGE
3.5 Hz to 75 Hz
KEY FEATURES • Unbalanced load protection • Start & stop capability via SMS
• Configurable power-up mode • Independent earth fault protection messaging MAGNETIC PICKUP
VOLTAGE RANGE
• MPU fail delay • Breaker control via fascia buttons • 3 configurable maintenance alarms +/- 0.5 V to 70 V
• Enhanced graphical user interface • Fuel and start outputs configurable • Compatible with a wide range of
• Drag & drop advanced PLC editor when using CAN CAN engines, including tier 4 FREQUENCY RANGE
10,000 Hz (max)
• MSC ID within PLC GenComm • 6 configurable DC outputs engine support
override • 2 configurable volt-free relay • Uses DSE Configuration Suite PC INPUTS
• 4-Line back-lit LCD text display outputs Software for simplified DIGITAL INPUTS A TO H
Negative switching
• Multiple Display Languages • 6 configurable analogue/digital configuration
• Five key menu navigation inputs • Licence-free PC software ANALOGUE INPUTS A & F
• LCD alarm indication • Support for 0 V to 10 V & 4 mA to • IP65 rating (with supplied gasket) Configurable as:
• Heated display option available 20 mA sensors offers increased resistance to water Negative switching digital input
0 V to 10 V sensor
• Customisable power-up text and • 8 configurable digital inputs ingress 4 mA to 20 mA sensor
images • Configurable 5 stage dummy load • Modules can be integrated into Resistive sensor
• DSENet expansion compatibility and load shedding outputs building management systems
ANALOGUE INPUTS B, C, D & E
• Data logging facility • CAN, MPU and alternator (BMS) using MODBUS RTU Configurable as:
• Internal PLC editor frequency speed sensing in one Negative switching digital input
• Protections disable feature variant KEY BENEFITS Resistive sensor
• Fully configurable via PC using • Real time clock • Automatically transfers between
OUTPUTS
USB, RS232 & RS485 • Manual and automatic fuel pump mains (utility) and generator OUTPUT A & B (FUEL & START)
communication control (DSE7320 MKll only) for 15 A DC at supply voltage
• Front panel configuration with • Engine pre-heat and post-heat convenience.
OUTPUTS C & D
PIN protection functions • Hours counter provides accurate 8 A AC at 250 V AC (Volt-free)
• Power save mode • Engine run-time scheduler information for monitoring and
• 3 phase generator sensing and • Engine idle control for starting & maintenance periods AUXILIARY OUTPUTS E, F, G, H, I & J
stopping • User-friendly set-up and button 2 A DC at supply voltage
protection
• 3 phase mains (utility) sensing and • Fuel usage monitor and low fuel layout for ease of use DIMENSIONS
protection (DSE7320 MKII only) level alarms • Multiple parameters are monitored OVERALL
• Automatic load transfer control • Simultaneous use of RS232 and & displayed simultaneously for full 245 mm x 184 mm x 51 mm
9.6” x 7.2” x 2.0”
(DSE7320 MKII only) RS485 communication ports visibility
• Generator current and power • True dual mutual standby using • The module can be configured to PANEL CUT-OUT
monitoring (kW, kvar, kVA, pf) RS232 or RS485 for accurate suit a wide range of applications for 220 mm x 160 mm
8.7” x 6.3”
• Mains current and power engine hours balancing. user flexibility
monitoring (kW, kvar, kVA, pf) • MODBUS RTU support with • PLC editor allows user configurable MAXIMUM PANEL THICKNESS
(DSE7320 MKII only) configurable MODBUS pages. functions to meet user specific 8 mm
• kW and kvar overload and reverse • Advanced SMS messaging application requirements. 0.3”
power alarms (additional external modem STORAGE TEMPERATURE RANGE
• Over current protection required) -40°C to +85°C
-40 °F to +185 °F
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457 055-203/12/20 (2)
DSEGenset®
ELECTRO-MAGNETIC COMPATIBILITY
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
DSENET ®
RS232 AND USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT INPUTS INPUT STOP SUPPLY 8-35V
DEUTZ
DSE7310/20 MKII ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA
MAINS (UTILITY) N/C VOLT FREE GENERATOR/ N/O VOLT FREE GENERATOR CHARGE FUEL & CRANK ELECTRONIC
SENSING OUTPUT LOAD CURRENT OUTPUT SENSING ALTERNATOR OUTPUTS ENGINES &
DSE7320 MKII ONLY (Flexible with CAN) MAGNETIC PICK-UP
VOLTS VOLTS D+
W/ L +
ISO 9001
Registered
Quality
Managem
ent 015
❖ Engine Datasheet
ENGINE MODEL CURVE NUMBER
KTA38-G2A C-621-D
USED FOR 900KVA GENERATOR
ENGINE FAMILY CPL NUMBER
CCEC D23 CQ609
EXHAUST SYSTEM
Maximum Allowable Back Pressure – in.Hg (kPa)……………………………………………………………………………………………………………………
3.0 (10)
6.0 (152)
Exhaust Pipe Size Normally Acceptable in.(mm)……………………………………………………………………………………………………………………
COOLING SYSTEM
Coolant Capacity - Engine Only - U.S. gal (litre)…………………………………………………………………………………………………………………… 31.2 (118)
- With Heat Exchanger 344 (325)
[100 (38°C)] - U.S. quart (litre)……………………………………………………………………………………………………………………
Maximum Coolant Friction Head External to Engine – PSI(kPa)……………………………………………………………………………………………………………………
5.0 (35)
Maximum Static Head of Coolant Above Engine Crankshaft Centerline ft (m) …………………………………………………………………………………………………………………
25 (7.6)
Maximum Air Restriction Across Radiator – in.H2O (kPa)……………………………………………………………………………………………………………………
0.5 (0.12)
Standard (modulating) Thermostat Range - °F (°C) …………………………………………………………………………………………………………………… 180-200 (82-93)
35 (241)
Maximum Coolant Pressure (Exclusive of Pressure Cap) – PSI (kPa)……………………………………………………………………………………………………………………
Minimum Allowable Pressure Cap –PSI (kPa)…………………………………………………………………………………………………………………… 10 (69)
Maximum Allowable Top Tank Temperature -°F (°C)…………………………………………………………………………………………………………………… 220 (104)
Minimum Recommended Top Tank Temperature -°F (°C)…………………………………………………………………………………………………………………… 160 (71)
Minimum Allowable Fill Rate –U.S.GPM(L/min)…………………………………………………………………………………………………………………… 5 (18.9)
Maximum Allowable Initial Fill Time –min.…………………………………………………………………………………………………………………… 5
Minimum Allowable Coolant Expansion Space – % of System Capacity ……………………………………………………………………………………………………………………
5
Maximum Allowable Deaeration Time – min.…………………………………………………………………………………………………………………… 25
Minimum Allowable Drawdown – U.S.quart(litre)…………………………………………………………………………………………………………………… 22 (21)
(Drawdown Must Exceed the Volume Not Filled at Initial Fill & Must Not Include Expansion Space)
LUBRICATION SYSTEM
Normal Operating Oil Pressure Range @ Idle – PSI(kPa)……………………………………………………………………………………………………………………
28(193) Minimun
Rated Speed – PSI(kPa)…………………………………………………………………………………………………………………… 43-70 (297-483)
Oil Flow at Rated Speed – U.S.GPM (L/min)…………………………………………………………………………………………………………………… 124 (469)
Maximum Allowable Oil Temperature - °F(°C)……………………………………………………………………………………………………………………250 (121)
Oil Pan Capacity (Option OP6023) High/Low - U.S. gal.(litre)……………………………………………………………………………………………………………………
30-23 (114-87)
FUEL SYSTEM
Type Injection System………………………………………………………………………………………………………...……………… Direct Injection Cummins PT
Maximum Restriction at PT Fuel Injection Pump— with clean fuel filter—in.Hg(mmHg)………………………………………………………………………………………………………
4.0 (102)
— with clean fuel filter—in.Hg(mmHg)………………………………………………………………………………………………………
8.0 (203)
Maximum Allowable Head on Injector Return Line(Consisting of Friction Head and Static Head) —in.Hg(mmHg)…………………………………………………………………………
4.0 (102)
Maximum Fuel Flow to Injection Pump —US gph(liter/hr)………………………………………………………………………………………………………...……………… 160 (606)
ELECTRICAL SYSTEM
Cranking Motor (Heavy Duty,Positive Engagement) —volt………………………………………………………………………………………………………...………………
24
Battery Charging System, Negative Ground —ampere………………………………………………………………………………………………………...………………
35
Maximum Allowable Resistance of Cranking Circuit — ohm ………………………………………………………………………………………………………………………
0.002
Minimum Recommended Battery Capacity
1200
- Cold Soak @ 50 F(10 ) and Above – 0°FCCA ……………………………………………………………………………………………………………………
1280
- Cold Soak @ 32 F to 50°F(0 to 10 ) – 0°FCCA ……………………………………………………………………………………………………………………
1800
- Cold Soak @ 0 F to 32°F(-18 to 0 ) – 0°FCCA ……………………………………………………………………………………………………………………
PERFORMANCE DATA
Minimum Engine Speed –RPM…………………………………………………………………………………………………………………… 625
Maximum No-Load Governed Speed –RPM……………………………………………………………………………………………………………………
Maximum Overspeed Capability –RPM……………………………………………………………………………………………………………………
Estimum Free Field Sound Pressure Lever……………………………………Right Side-dBA………………….
At 3.3 ft(1m) and Full Load Governed Speed…………………………………Left Side-dBA…………………..
(Excludes Noise From intake, Exhaust, ……………………………………….……Front-dBA……….…………
Cooing System and Driven Components)…………………………………………..Rear -dBA…………………
Data shown above represent gross engine performance capabilitles obtainsed and corrected in accordance with ISO-3046 conditions of 100kPa (29.53 inHg) baromaetric pressure [110m (361 ft)
altitude], 25 (77°F) air inlet temperature, and relative humidity of 30% with No. 2 diesel or a fuel corresponding to ASTM D2. See reverse side for application rating guidelines.
The fuel consumption data is based on No.2 diesel fuel weight at 0.85kg/litre (7.1lbs/U.S.Gal).
Power output cureves are based on the engine operating with fuel system, water pump and lubricating oil pump; not included are battery charging alternator, fan, option equipment and driven
components.
50HZ 60HZ
standby prime standby prime
1500
Engine Speed –RPM …………………………………………………………………………………………………………………… 1500 1800 1800
1200(895) 1090(813)
Gross Power Output –BHP (kW) …………………………………………………………………………………………………………………… 1350(1007) 1227(915)
741(5114)
Brake Mean Effective Pressure –PSI (kPa) ……………………………………………………………………………………………………………………674(4648) 695(4795) 674(4648)
Piston Speed –ft/min (m/s)…………………………………………………………………………………………………………………… 1562 ( 7.9 ) 1562 ( 7.9 ) 1875(9.5) 1875(9.5)
115(86)
Motoring Friction Horsepower –HP (kW)…………………………………………………………………………………………………………………… 115( 86 ) 170(127) 170(127)
Intake Air Flow –CFM (L/s) …………………………………………………………………………………………………………………… 2385(1126) 2205(1041) 2900(1369) 2650(1251)
6831(3225) 6218(2936) 7795(3679) 6970(3290)
Exhaust Gas Flow (Dry Manifold) –CFM(L/s)……………………………………………………………………………………………………………………
997(536) 981(527)
Exhaust Gas Temperature - Dry Manifold °F(°C)…………………………………………………………………………………………………………………… 935(502) 905(485)
7741(136) 7058(124) 7720(136)
Heat Rejection-to-Ambient (Dry Manifold) —BTU/min(kW)…………………………………………………………………………………………………………………… 7015(123)
31249(549) 28346(626) 31200(548) 28210(496)
Heat Rejection-to-Coolant (Dry Manifold) —BTU/min(kW)……………………………………………………………………………………………………………………
Heat Rejection-to-exhuast (Dry Manifold)—BTU/min(kW)……………………………………… 35665(627) 35632(626) 41969(738) 38763(681)
310 ( 19.6 ) 310 ( 19.6 ) 390(24.6)
Engine Coolant Flow –U.S.GPM(L/s) …………………………………………………………………………………………………………………… 390(24.6)
❖ Alternator Datasheet
LA404G728D3
THREE-PHASE SYNCHRONOUS GENERATOR
WINDING QY12 Datasheet for 4 poles -50Hz @ 1500rpm/ 60Hz @ 1800rpm
Ambient Temperature 环境温度 40°C Method of Cooling 冷却方式 Air cooling 风冷
Temperature Rise 温升 125°C Direction of Rotation 旋转方向 Clockwise 顺时针
Insulation Class 绝缘等级 H Maximum Over-speed 最高转速 2250r/min
Power Factor 功率因数 0.8 Degree of Protection / Enclosure 防护等级 IP23
Excitation 励磁方式 Brushless 无刷 Altitude 海拔 1000m
Winding Pitch 绕组节距 2/3 Stator winding 定子绕组 双层叠绕绕组 DLL
Pole 极数 4 Number of Terminal 终端数量 6
With damping cage 带阻
Duty 工作制 S1- Continuous Rotor 转子 尼
Waveform 电话干扰因数 TIF<50 THF<2%
Waveform distortion 波形畸变率 BS EN 61000-6-2&BS EN 61000-6-4,VDE 0875G,VDE0874N
Radio interference 无线电干扰 Noload<1.5%,Non-distorting balanced linear load<5%
Standard 标配 Selection 选配 PMG
AVR MODEL AVR 型号
MX341B MX321 MX341B MX321
Voltage Regulation - in steady state condition 电压调节 ±0.5 ±0.5 ±0.5 ±0.5
Short Circuit Current Capacity 短路电流容量 3540A
Electrical Characteristic
Frequency 频率 Hz 50 60
Voltage ( series star )电压 Y V 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
Voltage ( parallel star )电压 YY V N/A N/A N/A N/A N/A N/A N/A N/A
Voltage ( series delta )电压 V 220 230 240 254 240 254 266 277
Rated power at Class H (125ºC) temperature rise kVA 865 910 910 825 986 1043 1090 1138
额定功率在 H(125ºC)温升 kW 692 728 728 660 788.8 834.4 872 910.4
4/4% 93.4 93.5 93.8 94.2 93.2 93.3 93.5 93.6
Efficiency at Class H (P.F.=0.8)绝缘等级 H (P.F.=0.8)效率 3/4% 94.3 94.4 94.6 94.8 94.1 94.2 94.3 94.3
2/4% 94.8 94.8 94.8 94.6 94.3 94.4 94.4 94.5
4/4% 94.9 95 95 95.5 94.7 94.7 94.8 94.9
Efficiency at Class H (P.F.=1.0)绝缘等级 H (P.F.=1.0)效率 3/4% 95.6 95.7 95.8 95.9 95.3 95.5 95.5 95.6
2/4% 95.8 95.9 95.9 95.8 95.5 95.7 95.7 95.7
Reactances (%) at Class H 绝缘等级 H 考核时的电抗
Direct axis synchronous reactance unsaturated 直轴同步电抗 Xd 2.83 2.69 2.5 2.02 3.23 3.05 2.92 2.8
Direct axis transient reactance saturated 直轴瞬态电抗 X'd 0.15 0.14 0.13 0.1 0.17 0.16 0.15 0.14
Direct axis subtransient reactance saturated 直轴瞬变电抗 X"d 0.1 0.1 0.09 0.07 0.12 0.11 0.1 0.1
Quadrature axis synchronous reactance unsaturated 交轴同步电抗 Xq 2.35 2.23 2.07 1.67 2.68 2.53 2.42 2.32
Quadrature axis subtransient reactance saturated 交轴起始瞬态电抗 X"q 0.27 0.26 0.24 0.19 0.31 0.29 0.28 0.27
Leakage reactance 漏抗 X1 0.07 0.08 0.06 0.05 0.08 0.07 0.07 0.07
Negative sequence reactance saturated 负序电抗饱和 X2 0.19 0.18 0.16 0.13 0.21 0.2 0.19 0.18
Zero sequence reactance unsaturated 零序电抗不饱和 X0 0.03 0.03 0.03 0.02 0.03 0.03 0.03 0.03
Short-circuit ratio 短路比 Kcc 0.3534 0.3717 0.4000 0.4950 0.3096 0.3279 0.3425 0.3571
• Ensure the engine is at rest and the module is in STOP mode by pressing the
(Stop/Reset) button.
• The first ‘#’ changes to ‘0’. Press the (Up) or (Down) button to adjust it to the correct value.
• Press the (Right) button when the first digit is correctly entered. The digit previously entered now shows ‘#’ for security.
• Repeat this process for the other digits of the PIN number. Press the (Left) button to move back to adjust one of the previous
DSE7310 MKII & DSE7320 MKII digits.
• When the (Tick) button is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not correct,
the PIN must be re-entered.
• If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is
displayed:
EDITING A PARAMETER
• Enter the editor as described above.
• Press the (Up) or (Down) buttons to select the parameter to view/change within the currently selected section.
• To edit the parameter, press the (Tick) button to enter edit mode. The parameter begins to flash to indicate editing.
• Press the (Up) or (Down) buttons to change the parameter to the required value.
• Press the (Tick) button to save the value. The parameter ceases flashing to indicate that it has been saved.
NOTE: Terminals 38, 39, 40 & 41 are not fitted to the DSE7310 MKII. • To exit the editor and save the changes, press and hold the (Tick) button.
NOTE: A larger version of the Typical Wiring Diagram is available in the product’s operator manual, refer to • To exit the editor and not save the changes, press and hold the (Stop/Reset) button.
DSE Publication: 057-253 DSE7310 MKII & DSE7320 MKII Operator Manual available from www.deepseaelectronics.com for
more information.
NOTE: If the editor is left inactive for the duration of the LCD Page Timer, it is automatically exited to ensure security.
Deep Sea Electronics Ltd. Deep Sea Electronics Inc.
NOTE: The PIN number is automatically reset when the editor is exited (manually or automatically) to ensure security.
Tel:+44 (0)1723 890099 Tel: +1 (815) 316 8706
Email: [email protected] Fax: +1 (815) 316 8708
NOTE: Comprehensive module configuration is possible using the DSE Configuration Suite PC Software, refer to DSE
Web: www.deepseaelectronics.com Email: [email protected]
publication 057-243 DSE7310 MKII & DSE7320 MKII Configuraiton Suite PC Software Manual available from
Web: www.deepseausa.com www.deepseaelectronics.com.
MAIN CONFIGURATION EDITOR PARAMETERS MAIN CONFIGURATION EDITOR PARAMETERS (CONTINUED) ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
Section Parameter As Shown On Display Value • The ‘running’ editor can be entered while the engine is running. All protections remain
NOTE: Depending upon module configuration, some values in the Main & Running Generator Nominal Frequency 0.0 Hz active if the engine is running while the running editor is entered.
Configuration Editors may not be available. For more information refer to DSE (Continued) Over Frequency Pre Alarm 0.0 Hz
publication 057-243 DSE7310 MKII & DSE7320 MKII Configuraiton Suite PC Software Over Frequency Shutdown 0.0 Hz
Manual available from www.deepseaelectronics.com Over Frequency Delay 0.0 s • Press and hold the (Tick) button to enter the running editor.
Frequency Overshoot 0%
Section Parameter As Shown On Display Value Frequency Overshoot Delay 0.0 s
Display Contrast 0% CT Primary 0A RUNNING CONFIGURATION EDITOR PARAMETERS
Language English CT Secondary 0A
Current Date and Time dd:mm:yyyy, hh:mm:ss Earth CT Primary 0A Section Parameter As Shown On Display Values
Set Priority / Run Time / Full Load Rating 0A Display Contrast 0%
Dual Mutual Mode Delayed Over Current Active / Inactive
Engine Hours Language English
Dual Mutual Priority 0 Delayed Over Current 0% Dual Mutual Dual Mutual Status Set Priority (1 to 8)
Dual Mutual Duty Time 0h0m 0s Earth Fault Trip Active / Inactive Engine Manual Frequency Trim 0.0 Hz
Alt Config Main Configuration / Alt Earth Fault Trip 0% Speed Bias 0.0
Config To Edit
Config 1,2,3,4 or 5 kW Overload Trip 0% Governor Gain 0
Main Configuration / Alt Mains AC System 3 Phase, 4 Wire Frequency Adjust 0.0 %
Default Configuration
Config 1,2,3,4 or 5 DSE7320 MKII Under Voltage Trip 0V DPF Auto Regen Inhibit Active / Inactive
Engine Oil Pressure Low Shutdown 0.00 bar 0 psi 0 kPa Only Over Voltage Trip 0V DPF Manual Regeneration Request Active / Inactive
Oil Pressure Low Pre Alarm 0.00 bar 0 psi 0 kPa Under Frequency Trip 0.0 Hz ECU Service Mode Active / Inactive
Coolant Temperature Low Warning 0 ºC 0 ºF Over Frequency Trip 0.0 Hz AVR Droop (% of Set Point) 0.0
Coolant Temperature High Pre Alarm 0 ºC 0 ºF Timers Start Delay Off Load 0h0m 0s Proportional Set Point 0.0
Coolant Temperature High Electrical Trip 0 ºC 0 ºF Start Delay On Load 0h0m 0s Integral Set Point 0.0
Coolant Temperature High Shutdown 0 ºC 0 ºF Start Delay Mains Fail 0h0m 0s Derivative Set Point 0.0
Fuel Usage Running Rate 0% Start Delay Telemetry 0h0m 0s Off Load Duty Cycle 0.0
Fuel Usage Stopped Rate 0% Mains Transient Delay 0m 0s Maximum Duty Cycle 0.0
Specific Gravity 0.00 Engine Cranking 0m 0s Soft Start Ramp Start Point 0.0
Pre Heat Temp 0 ºC 0 ºF Engine Cranking Rest 0m 0s Soft Start Ramp Rate (%/Hz) 0.0
Pre Heat Timer 0h0m 0s Engine Smoke Limiting 0m 0s Alternative Configuration 0
Post Heat Temp 0 ºC 0 ºF Engine Smoke Limiting Off 0m 0s Stability Selection 0
Post Heat Timer 0h0m 0s Engine Safety On Delay 0m 0s
Droop Control Active / Inactive Engine Warming 0h0m 0s
Droop Control 0.0 % ECU Override 0m 0s REQUIREMENTS FOR UL CERTIFICATION
Crank Disconnect Oil Pressure Delay 0.0 s Mains Transfer Time 0 m 0.0 s
Crank Disconnect 0V Return Delay 0h0m 0s
Under Speed Shutdown Active / Inactive Engine Cooling 0h0m 0s
Engine Fail To Stop Delay 0m 0s WARNING!: More than one live circuit exists, see diagram overleaf for further
Under Speed Shutdown 0 RPM
LCD Page Delay 0h0m 0s information.
Under Speed Warning Active / Inactive
Under Speed Warning 0 RPM LCD Scroll Delay 0h0m 0s
Under Speed Delay 0.0 s Sleep Timer 0h0m 0s Specification Description
Over Speed Warning Active / Inactive Backlight Timer 0h0m 0s Screw Terminal
Over Speed Warning 0 RPM Schedule Schedule Active / Inactive Tightening • 4.5 lb-in (0.5 Nm)
Over Speed Shutdown 0 RPM Schedule Bank 1 Period Weekly / Monthly, Torque
Over Speed Delay 0.0 s Conductors • Terminals suitable for connection of conductor size 13 AWG to 20 AWG
On Load / Off Load / Auto Start Inhibit, Press Tick to begin editing (0.5 mm² to 2.5 mm²).
Overspeed Overshoot 0%
Week, Start Time, Run Time and Day then up or down when selecting • Conductor protection must be provided in accordance with NFPA 70,
Overspeed Overshoot Delay 0 m 0.0 s
Selection (1 to 8) the different parameters in the Article 240
Battery Under Voltage Warning Active / Inactive scheduler.
Battery Under Voltage Warning 0.0 V • Low voltage circuits (35 V or less) must be supplied from the engine
Schedule Bank 2 Period Weekly / Monthly, starting battery or an isolated secondary circuit.
Battery Under Voltage Warning Delay 0h0m 0s
• The communication, sensor, and/or battery derived circuit conductors
Battery Over Voltage Warning Active / Inactive On Load / Off Load / Auto Start Inhibit, Press Tick to begin editing shall be separated and secured to maintain at least ¼” (6 mm)
Battery Over Voltage Warning 0.0 V Week, Start Time, Run Time and Day then up or down when selecting separation from the generator and mains connected circuit conductors
Battery Over Voltage Warning Delay 0h0m 0s Selection (1 to 8) the different parameters in the unless all conductors are rated 600 V or greater.
Charge Alternator Failure Warning Active / Inactive scheduler.
Current Inputs • Must be connected through UL Listed or Recognized isolating current
Charge Alternator Failure Warning 0.0 V
transformers with the secondary rating of 5 A max.
Charge Alternator Warning Delay 0h0m 0s
Communication
Charge Alternator Failure Shutdown Active / Inactive DIMENSIONS AND MOUNTING Circuits
• Must be connected to communication circuits of UL Listed equipment
Charge Alternator Failure Shutdown 0.0 V DC Output Pilot
Charge Alternator Shutdown Delay 0h0m 0s Parameter Specification • 0.5 A
Duty
Inlet Temperature Shutdown 0 ºC 0 ºF Dimensions 245 mm x 184 mm x 51 mm (9.6 ” x 7.2 ” x 2.0 ”) Mounting • Suitable for flat surface mounting in Type 1 Enclosure Type rating with
Inlet Temperature Pre-Alarm 0 ºC 0 ºF Panel Cut-out 220 mm x 160 mm (8.7 ” x 6.3 ”) surrounding air temperature -22 ºF to +122 ºF (-30 ºC to +50 ºC)
Generator AC System 3 Phase, 4 Wire Weight 0.98 kg (2.16 lb) • Suitable for pollution degree 3 environments when voltage sensing
Under Voltage Shutdown 0V Operating Temperature inputs do not exceed 300 V. When used to monitor voltages over 300 V
-30 ºC to +70 ºC (-22 ºF to +158 ºF)
Under Voltage Pre Alarm 0V With Standard Display device to be installed in an unventilated or filtered ventilation enclosure
Under Voltage Delay 0.0 s Operating Temperature to maintain a pollution degree 2 environment.
-40 ºC to +70 ºC (-40 ºF to +158 ºF)
Nominal Voltage 0V With Heated Display Operating
Over Voltage Pre Alarm 0V Storage Temperature -40 ºC to +80 ºC (-40 ºF to +176 ºF) • -22 ºF to +122 ºF (-30 ºC to +50 ºC)
Temperature
Over Voltage Shutdown 0V
Over Voltage Delay 0.0 s
Under Frequency Shutdown 0.0 Hz
Under Frequency Pre Alarm 0.0 Hz
Under Frequency Delay 0.0 s
❖ Battery Datasheet
DATA SHEET
HYUNDAI SUNGWOOAUTO BLDG., 609, BONGEUNSA-RO, GANGNAM-GU, SEOUL, KOREA
TEL : +82-2-2189-0955 / FAX : +82-2-2189-0930 / URL : http://www.solite.co.kr
Specification
Self-discharge Characteristic
100
-15
90 15
of Capacity (%)
80
Remainder
25
70
60
50
40
40
0 10 20 30 40 50 60 70 80 90
Time (days)
AC SUPPLY
24 Volt, 10 Amp Battery Charger VOLTAGE RANGE
90 V to 305 V (L to N)
FREQUENCY RANGE
48 Hz to 64 Hz (L to N)
DC OUTPUT
10 A DC at 24 V DC (Configurable)
EFFICIENCY
>86%
REGULATION
LINE
<0.5%
LOAD
2%
PROTECTIONS
Short circuit
DC over voltage
DC over current
Reverse polarity
Over temperature
AC under & over voltage
DIMENSIONS
OVERALL
70 mm x 200 mm x 130 mm
ADVANCED FEATURES Full Protection • Fully configurable via DSE 2.7” x 7.9” x 5.1”
• UL recognised (9470-01 USA / • AC input under voltage Configuration Suite PC Software
9470-A4 USA & Canada) • AC input over voltage • External remote display option - WEIGHT
0.75 kg
• Intelligent three and four stage • Battery charger output over voltage DSE2541
charging profiles • Battery charger output over current OPERATING TEMPERATURE RANGE
• Configurable to suit 12V/24V - • Battery under voltage alarm KEY BENEFITS -30 ºC to +70 ºC
5A/10A applications • Automatic battery detection • Fully flexible to maximise the life of -22 ºF to +158 ºF
• Adjustable current limit • Automatic battery charger self test the battery STORAGE TEMPERATURE RANGE
• Can be used as a battery charger, • Output short circuit and inversion • Suitable for a wide range of battery -30 ºC to +70 ºC
power supply or both at the same polarity with auto recovery types -22 ºF to +158 ºF
time • Max current mode • Minimum 86% efficiency UL VOLTAGE APPROVAL RATINGS
• Automatic or manual boost and • SCADA digital input status throughout full operating range USA ONLY (9470-01)
storage charge functions to help information • No external intervention for boost 110 V - 250 V
maintain battery condition • Automatic power de-rating at high mode USA & CANADA (9470-A4)
110 V - 150 V
• Digital microprocessor technology ambient temperatures. • Multiple chargers can be linked
• Temperature compensation for • Optional battery temperature together to provide larger current
battery charging compensation using PT1000 outputs
• Low output ripple and superb line temperature sensor with over • Can be permanently connected
regulation temperature protection to a battery and AC supply. No
• Three LED indicators Automatic Boost Mode need to disconnect through high
• Switched mode design • Boosts and equalises cell charge, load conditions such as cranking
• Fully customisable battery charging improving battery performance or when the engine is running.
curves Power Save Mode
• Battery health check • Once the battery is fully charged,
• Battery voltage sensing the chargers switch to eco-power
• Deep sleep mode to save energy
• PSU only mode Communication
• Automatic voltage detection • Can be integrated into external
• Wide output current range systems through MODBUS RTU
using RS485
RELATED MATERIALS
TITLE PART NO.
DSE9400 Series Configuration Suite PC Software Manual 057-159
DSE Configuration Suite Installation & Operators Manual 057-151
DSE9000 Series Installation Instructions 053-049
DSE9000 Series Operators Manual 057-085
ELECTRO-MAGNETIC COMPATIBILITY
24 Volt, 10 Amp Battery Charger BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
The DSE9470 MKII is a UL recognised The charger can be DIN rail PART NUMBERS EMC Generic Emission Standard for
intelligent battery charger fully or chassis mounted, using the 9470-01 the Industrial Environment
configurable for 12 Volt/ 24 Volt & 5 fixing holes that are built into the 24 V 10 A Battery Charger
OPERATING TEMPERATURE RANGE
Amp / 10 Amp applications. case. The charger includes three (110 V - 250 V UL Recognised - USA) BS EN 60068-2-1
coloured LEDs to indicate charging Ab/Ae Cold Test -30 ºC
There are two different UL recognised status and fault conditions. 9470-A4 BS EN 60068-2-2
Bb/Be Dry Heat +80 ºC
variants. The 9470-01 is recognised 24 V 10 A Battery Charger
* Refer to de-rating curve in the DSE9000
for USA only (110 V - 250 V) and the The chargers do not include any (110 V - 150 V UL Recognised - USA & Operator Manual
9470-A4 is recognised for USA & moving parts for additional Canada)
VIBRATION
Canada (110 V - 150 V). durability and reliability. Each charger
BS EN 60068-2-6
will continue to operate during Ten sweeps in each of three
The charger features automatic engine running. major axes
voltage detection and battery voltage 5 Hz to 8 Hz @ +/-7.5 mm,
8 Hz to 500 Hz @ 2 gn
sensing down to 1 volt and has an Multiple chargers can be linked
output current range that can go together to provide a larger current HUMIDITY
down to 1 amp. The charger can output where required. BS EN 60068-2-30
Db Damp Heat Cyclic 20/55 oC
be easily programmed for different @ 95% RH 48 Hours
charging curves, to maximise battery The battery chargers are programmed BS EN 60068-2-78
life. using the user-friendly DSE Cab Damp Heat Static 40 oC
Configuration Suite PC software. @ 93% RH 48 Hours
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS
1ph
N
DSE9470 MKII
7
OTHER
PT1000 ONLY
1 1
NFPA 20
(QWIR2) 055-158/11/21 (6)
TYPICAL WIRING DIAGRAM DEEP SEA ELECTRONICS 053-277
ISSUE 1
NOTE: A larger version of the Typical Wiring Diagram is available in the product’s operator DSE 9470 MKII Installation Instructions
manual, refer to DSE Publication: 057-277 DSE9470 MKII Operator Manual available from
www.deepseaelectronics.com for more information. INSTALLATION
NOTE: Please refer to DSE Publication: 057-291 DSE9470 MKII Intelligent Battery Charger
Operator Manual for further details.
WARNING!: For safe operation, the charger MUST be installed in an enclosure which
prevents accidental contact with Hazardous Voltages.
The DSE9470 MKII Intelligent Battery Charger is designed for convenient installation within a control
panel, either on the panel DIN rail using the integral mounts or on a chassis using the mounting holes. It
can be constantly connected to both the power source and the load, eliminating the need to disable the
charger during periods of high load (e.g., engine cranking) or when the generator is operational (even if
equipped with a DC charging alternator).
BATTERY SUITABILITY
The default charger is pre-configured by DSE to accommodate Lead Acid batteries, but it can be
customized upon request to support other battery types. It is important to verify that the batteries
connected to the charger are compatible with its specific settings.
BOOST MODE
The boost feature is controlled automatically without requiring an external connection. Manual boost can
be initiated by connecting the boost terminals (triggered manually through a Digital Input) together, such
as with an external switch or timer circuit. This will increase the battery charger floating voltage by 0.8V
DC. The feature can be configured using the Digital Input feature in the Configuration Suite.
USER CONNECTIONS
NOTE: Where the current rating has been user configured below the rated maximum
current, an appropriate fuse size must be selected to match the lower maximum output current.
Parameter Comment
Connection Type Screw terminal, rising clamp, no internal spring
Min Cable Size 0.5 mm² (AWG 20)
WARNING: Live parts exist within the enclosure. The enclosure cover must not be removed Max Cable Size 2.5 mm² (AWG 10)
when connected to an AC supply. Recommended AC fuse 230 V AC Input 110 V AC Input
DSE9470 24 V / 12 V 10 A charger 3.5 A anti-surge 6.3 A anti-surge
LED Designation
Condition
FAULT 1 FAULT 2
High Output Voltage (DC) Red Constant Off
High / Low Input Voltage (AC) or High Output Current (DC) Red Flashing Off
High Ambient / Charger Temp, High Battery Temp (if enabled) Off Red Constant
Short Circuit/ Reverse Polarity (DC Output Connection) Off Red Flashing
LED Designation
Status
OPE FAULT 1 FAULT 2
Charger Off Off Off Off
Battery Not Detected (Battery Detection Mode) Green Flashing Red Flashing Red Flashing
Battery Connected (Battery Detection Mode) Green Constant Red Constant Red Constant
Not Charging
(Charger is operating correctly but the output Off Red Constant Red Constant
has been disconnected from the battery)
ALT
AS BUILT CONTROL
DAIGRAM
AS BUILT CONTROL
DAIGRAM
❖ FAT & SAT
FAT PROCEDURE
FACTORY ACCEPTANCE TEST Procedure
FACTORY ACCEPTANCE TEST (FAT) FORGENSET
FAT-REPORT AS PER REQUIERMENTS OF ISO8528-6
DATE: 25.06.2023 JOB NO.: 021-0224 CUSTOMER: TECHNOPOWER FZC
PROTECTIONS
ENGINE INSTRUMENTS Available Check ALTERNATOR CONTROLS Available Check
High Coolant Temperature Emergency Stop
LOAD TEST
Test Starting Time & Date
LOAD TIME Freq (HZ) Volt (V) Ampere (A) P.F Power (KW) Coolant Temp Oil Pressure
15% 15 MINS 60 HZ L-L 380 L-N 220 113 1 75kw 78 4.67
50% 30 MINS 60 HZ L-L 380 L-N 220 376 1 248kw 82 4.56
75% 45 MINS 60 HZ L-L 380 L-N 220 565 1 372 kw 86 4.44
100% 60 MINS 60 HZ L-L 380 L-N 220 756 1 498 kw 88 4.24
110% 10 MINS 60 HZ L-L 380 L-N 220 818 1 539kw 88 4.22
OPTIONS
WJ Heater
BC 24V 5A
Remarks:
SAT
Site Acceptance Test Procedure
GENSETS
CONTRLLED BY DSE7320
SUPPLIER
TECHNOPOWER GENERATORS.
Tel: 971 6 532 9794 | 971 50 766 7479
Fax: 971 6 5579792 | 971 50 895 3798
www.technopowergroup.com
[email protected]
TESTED BY
TECHNOPOWER GENERATORS
JAN-2023
2
TABLE OF CONTENTS
TITLE PAGE
2- Operation
A. Manual 4
B. Auto 4
6-DSE7320 layout 6
3
A. Mechanical aspects:
B Electrical aspects:
C Verification:
C.1 The serial numbers of all genset parts are picked up by barcode scanner. The
values are transferred automatically to a dedicated testing system.
C.2 The types and serial numbers are visually checked.
C.3 All electrical and mechanical components are verified to be congruent with the
internal order.
2. Operation
A. Manual operation
· Press gently on the Manual button to get the manual mode, and then
press start button; the generating set shall start.
· Press gently on the Stop button to stop the generating set instantly
(without cooling).
B. Automatic operation
· Press gently on the Auto button to select the Automatic mode of
operation.
· Link between the remote start terminals to initiate a start order for
generating set.
· Remove the link to stop the genset automatically (after cooling period).
3. Protection and alarms
The operation of following protections (if needed) is simulated.
A. High engine temperature.
B. Low oil pressure.
C. Low coolant level.
D. Low battery voltage
E. High battery voltage
F. U/O generator voltage.
G. U/O frequency.
H. Over-load.
I. Un-balanced load
J. Failure to start.
K. Fait to stop
5
CUSTOMER COMMENTS
License Members ÿ
- ,
ÿ
4-3-2-1 - /2 -
0508953798 :
82928 :
www.sedd.ae 80080000
Trading Register Certificate
License Details
Capital 0 ÿ
- , ÿ
4-3-2-1 - /2 -
www.sedd.ae 80080000
Main Board Permit
Sign Board No. 250993
Advertising details
Advertisement Content
Size 0 0
Machine Type
Trade Mark
:
.1
.2
þ .3
www.sedd.ae 80080000
Additional Sign Board Permit
Sign Board No. 305978
Advertising details 2
Advertisement Content
Size 14.7*7.5
Machine Type
Trade Mark
:
.1
.2
þ .3
www.sedd.ae 80080000
Additional Sign Board Permit
Sign Board No. 305979
Advertising details 1-
Advertisement Content
Size 25.5*7.5
Machine Type
Trade Mark
:
.1
.2
þ .3
www.sedd.ae 80080000
Main Board Permit
Sign Board No. 305977
Advertising details 1- - 4
Advertisement Content
Size 51.5*7.5
Machine Type
Trade Mark
:
.1
.2
þ .3
www.sedd.ae 80080000
Real Beneficiary
Real Beneficiary For Investor Inside License
Arabic Name
English Name
Emirates Id 784197980876854
Civic ID
Passport No PU310166
Address - -
Work Address
Mobile 0508953798
www.sedd.ae 80080000
7N. / 'G6
License Certificate
TechnoPower FZC
Is an authorised gold distributor
of Deep Sea Electronics Ltd, entitled to promote,
sell and support Deep Sea Electronics Ltd products
Craig Lysons
Director – Sales & Marketing
Valid to 31st December 2025
TECHNOPOWER GENERATOR
Badr Al Sayegh Bldg. Shop 1,2,3,4
Ind.Area 2, Sharjah, UAE.
Tel:+971 6532 9794, Mob: +971 507667479
www.technopowergroup.com