Differential Protection N Busbar
Differential Protection N Busbar
•For internal faults I1≠ I2 i.e. i1 ≠ i2, thus the current through relay not equal to zero
and if Relay current exceed the pick-up value, it operate. (i1=I1 /n, i2=I2 /n)
• For internal faults, the voltages of secondaries of CTs are different and thus
current passes through relay coils and operate the relay.
For external faults I1=I2 i.e . i1=i2, thus current through relay is zero. Or the
relay will not operate. (i1=I1 /n, i2=I2 /n)
Zone of Protection of the Differential
Relay
•It comprises everything between two CTs.
Actual Behaviour of a simple Differential
Protection
Through Fault Stability and Stability
Ratio
Equivalent Circuit of CT
Differential Scheme Considering CT
Equivalent Circuit
Difficulties with differential Protection
• Difference in length of Pilot wires difficult to get equipotential point:
CTs for the power system elements under protection are located at
different location and connected through pilot wires. If the length of the
pilot wires are different , it is very difficult to connect the relay at
equipotential point.
– This can be overcome by connecting adjustable resistors in series with
pilot wires.
•From the operating characteristic it can be observed that except for the effect of control spring
at low currents, the ratio of differential operating current to the average restraining current is a
fixed percentage. Thus it is called as percentage differential relay.
•It is also called as biased differential relay as the relay is restrained or biased against operating
inaccuracy under fault condition due to rising operating characteristic.
Induction type Biased Differential Relay
(Shaded ring type)
• The effect of transient current due to dc offset current is more in
balanced beam type relays.
• As in Induction type relay, the disc takes some time to rotate and close the
contact (around 2-3 cycles), thus it is immune to the transient condition.
• Second thing, by adjusting the position of the shading coil (we can move
towards the disc or away from the disc, so with that we can adjust the angle
between the un-shaded portion and shaded portion and so easily we can
adjust the torque produces i.e. operating or restraining torque).
Voltage Balanced Differential Relay
• Current Differential Relays (discussed) are convenient while both ends
of the protected elements are close together.
• e.g. Generator, Motor, Transformers, Bus bars etc.
• Relays are connected series opposition, so the voltages induced in such that
their difference will be zero.
• During internal fault . e1≠ e2 ,thus current flow the relay and relay will
trip.
Advantages and Disadvantages