JUPITER-9000K-H0 / STS-6000K/3000K-H1

Smart Transformer Station Technical Specifications


Model JUPITER-9000K-H0 STS-6000K-H1 STS-3000K-H1
Input
Available Inverters SUN2000-215KTL-H0 / LUNA2000-200KTL
Max. LV AC Inputs 44 34 17
AC Power 9,000 kVA @40°C 1
6,800 kVA @40°C 1
3,400 kVA @40°C 1

Rated Input Voltage 800 V


LV Panel Segregation Form 2b
LV Main Switches ACB (4,000 A, 2 x 1 pcs) ACB (2,900 A, 2 x 1 pcs) ACB (2,900 A, 1 pcs)
LV Main Switches for SUN2000-215KTL-H0 MCCB (400 A, 2 x 22 pcs) MCCB (250 A, 2 x 17 pcs) MCCB (250 A, 17 pcs)
Output
Rated Output Voltage 10~35 kV 2

Frequency 50 Hz / 60 Hz
Transformer Type Oil-immersed, Conservator Type
Transformer Cooling Type ONAN
Transformer Tappings ± 2 x 2.5%
Transformer Oil Type Mineral Oil (PCB Free)
Transformer Vector Group Dy11-y11 Dy11
Transformer Min. Peak Efficiency Index Tier 1 or Tier 2 In Accordance with EN 50588-1
RMU Type SF6 Gas Insulated
RMU Transformer Protection Unit MV Vacuum Circuit Breaker Unit
Simple Efficient
Prefabricated and pre-tested, High efficiency transformer for higher yields RMU Cable Incoming / Outgoing Unit Direct Cable Unit or Cable Load Break Switch Unit
no Internal cabling needed onsite Lower self-consumption for higher yields Dry Type Transformer, Dry Type Transformer,
Auxiliary Transformer
Compact 20’ HC container design for easy transportation 5 kVA, Single-phase, li0 5 kVA, Three-phase, Dyn11
Output Voltage of Auxiliary Transformer 230 / 127 Vac 400 / 230 Vac or 220 / 127 Vac
Protection
Transformer Detection & Protection Oil Level, Oil Temperature, Oil Pressure and Buchholz

Smart Reliable Protection Degree of MV & LV Room IP 54


Real-time detection of transformer, Robust design against harsh environments optimal cooling Internal Arcing Fault of STS IAC A 20 kA 1s
LV panel and RMU high precision sensor Design for high availability and easy O&M MV Relay Protection 50/51, 50N/51N
of LV electricity parameters Comprehensive tests from components, device to solution
Remote control of ACB and MV circuit breaker LV Overvoltage Protection Type I+II
Anti-rodent Protection C5-Medium
Features
Schematic Diagram 2 kVA UPS Optional 3

MV Surge Arrester for MV VCB Optional 3

General
Dimensions (W x H x D) 6,058 x 2,896 x 2,438 mm (20’ HC ISO Container)
Weight < 28 t < 22 t < 15 t
Operating Temperature Range -25°C ~ 60°C 4

Relative Humidity 0% ~ 95% (Non-condensing)


Max. Operating Altitude 1,000 m 5

MV-LV AC Connections Prewired and Pretested, No Internal Cabling Onsite


LV & MV Room Cooling Smart Cooling without Air-across for Higher Availability
Modbus TCP, Preconfigured Modbus RTU, Preconfigured
Communication
with SmartACU2000D with SmartACU2000D
Transformer
Standards Compliance
IEC 62271-202, EN 50588-1, IEC 60076, IEC 62271-200, IEC 61439-1
1: More detailed AC power of STS, please refer to the de-rating curve.
2: Rated output voltage from 10 kV to 35 kV, more available upon request
3: Extra expense needed for optional features which standard product doesn’t contain, more options upon request.
LV Panel RMU 4: When ambient temperature ≥55 , awning shall be equipped for STS on site by customer.
5: For higher operating altitude, pls consult with Huawei.