Protection Q&A (Ch.1 To Ch.5)
Protection Q&A (Ch.1 To Ch.5)
Protection Q&A (Ch.1 To Ch.5)
Type.
Rating of the protected equipment.
Importance.
Location.
Probable abnormal condition.
Cost
7. What are the results of fault and what are the faults caused by?
Defect in the electric circuit, so:
o The flow of current is diverted from intended path.
o The potential drops to zero at the location of fault.
The nearest generation station could go out of synchronism.
Transient stability will determine whether the different station will remain synchronized
or not.
Faults should be cleared quickly to prevent cascaded failures (BLACKOUTS)
o Current will be thousands of amperes.
o High current will lead to increase heat.
o Short Circuit is associated with arcs.
Caused by breaking of conductors or insulation failure.
Sensitivity( 𝐾 )=
17. Define Reliability.
Measure the degree of certainty that a piece of equipment will perform
.
% Reliability = × 100
. .
5. How can we obtain slow operating and resetting times and what are
their values?
By fitting copper ring around the magnet, and by means of bellows
Operating time = 0.1 sec , resetting time = 0.5 Slow
Operating time = 0.5 milli-second Fast
6. Draw Plunger type electromagnetic attraction relay and mention its
operating principle
13. What are the causes of frequency varying? And what is the
frequency relay used for?
Causes of frequency varying:
o Over-speeding: due to loss of load
o Under-speeding: due to increase in load
Frequency relay is used in generator protection and generator control, they can be under-
frequency or over-frequency relays
16. What is the difference between under voltage relay and normal
induction relay
The construction of instantaneous under-voltage relays is similar to usual induction relay or
attracted armature relay. But the directions of torque/forces on the movable element of relay are
different.
1. What is overcurrent protection? What are its types?
Protection in which the relay picks up when the magnitude of current exceeds the pickup level.
Has the following types:
o High speed overcurrent protection.
o Definite time overcurrent protection.
o Inverse minimum time overcurrent protection.
o Directional overcurrent protection (of above types).
2. What is overloading? What are its causes? How can we protect the
circuit from overcurrent?
Taking more current than rated current, cat be short circuit current
Overloading causes rise in temperature.
Using thermal relays.
22. What is the plug setting? What is the function of time multiplier
(TMS)?
Refers to the magnitude of current at which the relay starts to operate.
(TMS) decides the arc-length through which the disc travels, by reducing the length of travel, the
time is reduced.
23. IDMT Relay Characteristics (IEC 60255)
24. What is the data required for determination of actual operating time
of a relay?
Time-PSM curve
Current setting
Time setting
Fault current
CT ratio
29. Draw Residually connected Earth Fault Relay and mention its theory.
In absence of earth-fault:
o the vector sum of the three line currents is zero.
o The vector sum of the three secondary currents is also zero. ( 𝐼 + 𝐼 + 𝐼 = 0)
The sum (𝐼 + 𝐼 + 𝐼 ) is called residual current (Iresidual). Therefore, the residually connected
earth-fault relay does not operate.
However, in presence of earth fault the conditions is disturbed and (𝐼 + 𝐼 + 𝐼 ≠ 0)
Hence (Iresidual ) flows through the earth-fault relay. If the residual current is above the pick-up
value, the earth-fault relay operates.
30. Draw Earth-fault Relay Connected in Neutral to Earth Circuit?
The increase in current of phase causes corresponding increase in respective secondary currents.
The secondary current flows through respective relay-units.
Very often only two-phase relays are provided instead of three, because in case of phase faults
current in any at least two phases must increase.
Hence two relay-units are enough.
32. Draw Earth-fault Protection with Core Balance Current Transformer
and mention its theory.
𝐼 + 𝐼 + 𝐼 = 3𝐼 = 𝐼 ___ where, 𝐼 is zero sequence current and 𝐼 is current in neutral to ground circuit.
During earth fault, the earth fault current flows through return neutral path. For example for single line
ground fault, 𝐼 = 3𝐼 = 𝐼
Hence the zero-sequence component of 𝐼 produces the resultant flux in the core. Hence core balance
current transformer is also called as zero sequence current transformer (ZSCT).
As it measures resistance and reactances, it is affected by resistance of arc, and results in under-
reach.
It is affected by power swings (fluctuation of reactive power) (changes in voltage and current due
to switching) as the circular characteristic covers a large area on every side of center. Swing
point comes within circle.
Reach Point = Furthest point at which relay can operate = 𝑍
o Over-Reach: Relay operates if 𝑍 > 𝑍
Where:
o 𝑅 = 𝑅𝑒𝑠𝑖𝑠𝑡𝑎𝑛𝑐𝑒 𝑜𝑓 𝑎𝑟𝑐 𝑖𝑛 𝑂ℎ𝑚𝑠.
o L= Length of arc in meters in open standstill air.
o I = Fault current in Amperes.
Shot Transmission line:
o 𝑅 ≫≫ 𝑍
o Under-Reach √
Long Transmission line:
o 𝑅 ≪≪ 𝑍
o Under-Reach ×
10. Briefly discuss the Reactance Type Distance Relay, mention its
advantages and draw characteristics
The main advantage of reactance relay is that it is not affected by fault resistance. The
characteristic of plain reactance relay is a line parallel to R-axis in R-X plane.
The reactance relay is not used by itself. It is generally used along with Mho Relay.
Hence such relays are used for protection of short lines having fault currents less than 20 kA, In
such lines the effect of fault resistance is predominant.
11. Draw Ideal characteristics of Plain Reactance Type Distance Relay.
5. Write the principle of Biased or Percent Differential Relay and draw the
circuit.
6. Show the operation characteristic of Biased or Percent Differential
Relay.
7. Write the principle of Balanced Voltage Differential Protection and
draw the circuit.