Paper On Galv Vs Plain Rebar
Paper On Galv Vs Plain Rebar
Paper On Galv Vs Plain Rebar
International Journal of
ELECTROCHEMICAL
SCIENCE
www.electrochemsci.org
The aim of this paper is to study the effects of carbonation on the electrochemical properties of carbon
steel and galvanized steel, immersed into cubic prisms of concrete elaborated with Portland pozzolanic
cement. Reinforced concrete specimens using these two metallic materials were exposed in a
carbonation chamber. In a short time period changes in carbon steel and galvanized steel potentials and
in concrete resistivity indicated an increase in carbonation of steel rebar. During the test period it was
observed that zinc, instead to be in active conditions, attains lower corrosion rate than carbon steel.
This behavior allows to assume the use of galvanized steel as an option to enlarge useful life of
reinforced concrete structures in carbonated environments.
1. INTRODUCTION
In the recent decades several research work have been performed concerning the durability of
reinforced concrete structures used in highly aggressive environments such as marine or industrial
areas in which ordinary steel rebars show high levels of deterioration due to electrochemical corrosion
[1-4].
In marine environments ordinary steel suffers pitting corrosion due to the presence of chloride
ions from airborne salinity. These ions diffuse through pores in the concrete, and become inserted in
Int. J. Electrochem. Sci., Vol. 7, 2012 10723
the crystalline network of the oxide layer responsible for the passivation of the steel, thus initiating a
process of autocatalytic oxidation [5-8].
Furthermore, in industrial or urban areas where CO2 emissions have considerably increased
over time, carbonation in concrete structures has also risen. As it is well known, when this gas diffuses
through the pores in the concrete it reacts with the alkaline ions dissolved in the pores of solution,
initiating carbonation as described in equations 1, 2 and 3, and leading to a decrease in pH on the steel-
concrete interface, reaching values lower than 9.5, and causing de-passivation of the steel structure [9-
11].
One way to maintain the expected durability of the structure and diminish carbonation rate is
the use of galvanized steel. Zinc is stable in the pH range of 6 to 12.5, even more than carbon steel, the
stability of the last is observed for pH values between 10 and 12.5. Under these conditions, the
corrosion products formed on the surface of the galvanized steel, mainly CaHZn (calcium hydroxy-
zincate, Ca(Zn(OH)3)2 x 2H2O), are more compact, homogenous, adherent and less voluminous than
the oxides formed on carbon steel [12-17].
Sosa-Baz et al. report the presence of simonkolleite (Zn5(OH)8Cl2.H2O), zincite (ZnO),
wulfingite (Zn(OH)2), calcite (CaCO3), portlandite (Ca(OH)2) and calcium and aluminum oxides
(Ca5Al6O14 and Ca12Al12O19) on the zinc-concrete interface from a film of thermal zinc spray in a
system of cathodic protection via galvanic anode. It is argued that the compounds formed are greater in
volume and therefore block the pores, increasing resistivity and reducing the efficiency of cathodic
protection. Similarly, the pores on the galvanized steel-concrete interface can be obstructed with
products of zinc corrosion, thus decreasing the rate of corrosion of the embedded rebar [18-19].
The sequence of reactions that best represents the Zn corrosion process in alkaline media is the
following [20]:
However, a disadvantage to the use of galvanized steel is that the corrosion rate increases
greatly in media with pH above 12.5, enabling the evolution of hydrogen, the main consequence of
Int. J. Electrochem. Sci., Vol. 7, 2012 10724
which would be the formation of hollows over the rebar-concrete interface, reducing the area of
contact between the galvanized steel and the hydrated phases of the cement, with possible loss of
metal-steel adhesion [21].
This highlights the importance of studying the behavior of galvanized steel in concretes made
using pure Portland cement mixed with pozzolana, produced in Chile, as the reaction of the different
cements with water generates a pH that depends on the alkaline content of the given cement amount of
sodium and potassium ions.
The present paper analyses the effects of carbonation on the electrochemical properties of
carbon steel and galvanized steel in the concrete mix as a consequence of exposure of reinforced
concrete specimens in an accelerated carbonation chamber.
Cubic specimens, 15 cm along each edge, were fabricated of reinforced concrete using Portland
Pozzolanic cement of standard quality. Cement composition is shown in Table 1. Concrete samples
were elaborated with a water/cement ratio (w/c) of 0.55, dosage was in accordance with the amounts
shown on Table 2. The design of the reinforced concrete test-probe used in the study contains a total of
2 carbon steel and 2 galvanized steel rebars located 3.5 cm from the perimeter of the cube; the bars
have a diameter of 3/8” and a length of 16 cm.
Compound SiO2 Al2O3 Fe2O3 CaO MgO Na2O K2O SO3 Mn2O3 P2O5
Content, % 21.5 4.6 3.3 62.0 2.7 0.2 0.4 2.2 0.08 0.09
Mixture Portland Pozzolana Cement (Kg) Water (L) Gravel (Kg) Sand (Kg)
w/c: 0.55 308 171 1039 959
Int. J. Electrochem. Sci., Vol. 7, 2012 10725
The galvanized steel probes comply with ASTM Standard A767M and are identified with the
letter G, and the carbon steel of type A44-28H of commercial use is identified with the letter C.
The probes were cured in a wet chamber at 25 °C and 90% relative humidity for 28 days. Cubic
concrete probes were also fabricated without steel rebars in order to characterize the concrete mix.
Both, fine and coarse aggregates used were siliceous.
The concrete mix was characterized by testing compressive strength and electrical resistivity
using probes without steel rebars. Compressive strength (ASTM Standard C39) was evaluated from
day 28th of curing in the wet chamber until day 60th. Cylindrical core samples were also taken from
some non-reinforced specimens after the curing period in order to measure the electrical resistivity of
the concrete. Measurements were taken in accordance with the method of Wenner [9].
General conditions in the carbonation chamber were: relative humidity of 60-70% and
temperature of 25 ºC. The purpose of the testing is to cause accelerated diffusion of carbon dioxide
through the pores in the concrete towards the rebars, in order to evaluate the resistance of both types of
steel to carbonation, which leads to corrosion of the steel rebars, and to see how the different degrees
of carbonation affect resistivity of the concrete. The probes were partially removed at 28, 35, 42 and
49 days of exposure in carbonation chamber, which is maintained saturated with CO2 (100% CO2). All
faces of the cubic specimens, except the bottom one, which supports the probe inside the chamber,
were exposed to gas penetration.
Electrical resistivity measurements using the Wenner method were taken throughout the
progress of carbonation of the probes, that is, for each partial removal of the concrete samples, a core
sample was extracted having the same carbonation time as the probe. Thus, by the end of the
accelerated carbonation test, changes in electrical resistivity of concrete were obtained as function of
carbonation time.
Each time the reinforced concrete samples were partially removed from the carbonation
chamber, the status of the embedded rebars was evaluated by measuring corrosion potential and
corrosion current. This was done using a G–Sec potentiostat V2.0, forming an electrochemical cell
with a Cu/CuSO4 reference electrode (CSE +316mV v/s ENH), a copper counter-electrode, and with
the steel rebar as the working electrode.
Int. J. Electrochem. Sci., Vol. 7, 2012 10726
Measurement of corrosion potential (Ecorr) were done for 30 minutes until a stable potential was
reached. Polarization resistance (Rp) was then measured by making a sweep of potential of + 10 mV
over the Ecorr found for the rebars. This value was then used to indirectly calculate the corrosion
current and with that the corrosion rate of the rebar by Stern and Geary ecuation (ec. 8). [22]
(8)
Where Rp is the polarization resistance, and B is a constant value determined from Tafel plot through
non destructive experiments in concrete probes [23], B has two values, 26 mV to active carbon steel
and 56 mV to passive rebars. In the case of galvanized steel this constant value was taken from Farina
studies, it is 26 mV [24]. To convert the corrosion current into corrosion rate, it applies Faraday’s law.
The results obtained were compared with measurements taken on a non exposed probe, denominated
the control probe or “C probe”.
2.6. Qualitative and quantitative analysis of the carbonation level of the specimens
Qualitative analysis was performed by cutting each specimen in two equal parts and exposing
its interior. The two resulting interior faces were then sprayed with a phenolphthalein solution: an acid-
base indicator that in alkaline solution, such as with healthy concrete, turns violet in color, while in
neutral or acidic solution it remains colorless. This method can be used to measure the depth reached
by the entrance of CO2 into the probe. The consequence of the diffusion of the gas is a fall in pH in the
concrete and therefore there will be no coloration when spraying with phenolphthalein.
Subsequently, quantitative analysis was performed by taking samples of crushed concrete from
each probe at different depths: 1, 2, 3 and 4 cm from the surface of the probe up to the rebars. These
samples were then submitted to a soluble salt extraction process using deionized water to collect the
ions responsible for the pH in the concrete pore solution. The pH of the resulting solution was
measured with a Corning Scholar 425 pH meter with a glass membrane electrode calibrated between
pH 7 and 10, with a gradient of 92%, obtaining carbonation profiles as function of sample depth.
Figure 1 shows the average variation in compressive strength of the concrete probe over time.
Compressive strength for the cubes used in these tests increases from 25.3 MPa at 28 days wet
chamber curing to a maximum of 30.8 MPa at 49 days curing. This value is concordant with the
literature [9], due it falls between the compressive strength of a cubes with a w/c ratio of 0.45 and with
a ratio of 0.65.
Int. J. Electrochem. Sci., Vol. 7, 2012 10727
Figure 2 shows the average variation in electrical resistivity versus time, for samples with and
without carbonation. A trend to decrease resistivity in the first days of exposure can be seen due to
humectation of the specimens when they are initially placed in the wet chamber, after the initial
behavior, resistivity begins to increase due to the formation of calcium carbonate which, as it is
deposited in the pore, cuts conductivity between the ions occluded in the pore. The calcium carbonate
occupies a larger volume in the pores of the concrete than the calcium hydroxide without carbonation.
It could cause less connectivity between the pores which would help to increase surface
impermeability, and therefore less conductivity inside the concrete, which substantiates the resistivity
values found.
The photographs in Figure 3 show cross-sections of the concrete specimens exposed in the
accelerated carbonation chamber. It can be seen how the degree of carbonation varies depending on the
number of days of exposure in the carbonated environment.
Figure 3. Concrete probes exposed in the carbonation chamber A) 0 days, B) 28 days, C) 35 days,
D) 42 days, E) 49 days.
The penetration of CO2 over time into the samples was confirmed by wet chemistry using
phenolphthalein, and it can be seen in the change in coloration on the surface of the concrete, where
the areas without carbonation are violet in color, corresponding to the interaction between the
phenolphthalein indicator and the ions responsible for the alkaline pH of the concrete. The areas
without color change show the advancement of the gas into concrete and its capacity to combine with
the water in solution in the pores and to react with dissolved alkali, leading to a subsequent drop in
alkalinity due to the neutralization of the pH level [9-11].
The initial state of the probe after 28 days of curing in the wet chamber (Figure 3A) shows
healthy concrete with an alkaline pH, free of contamination. After 28 days of exposure in the
accelerated carbonation chamber, the development of carbonation has reached an average penetration
Int. J. Electrochem. Sci., Vol. 7, 2012 10729
depth of 1.7 cm (Figure 3B), and thus has not yet reached the rebar. At 35 days exposure, diffusion of
CO2 can be seen to an average depth of 2.2 cm; at 42 days it has reached 2.6 cm and at 49 days, 4.18
cm. The average carbonation depths determined by wet chemistry are expressed as a function of time
(Figure 4).
Figure 4. Carbonation depths as a function of exposure time in the accelerated carbonation chamber.
Figure 5. A) pH profile for different CO2 exposure times. B) pH at the steel/concrete interface as a
function of time.
The most common method for predicting the CO2 penetration depth reached in a reinforced
concrete structure at a particular time relates the depth with the root squared of the time in years.
However, in this case, the process is accelerated and obeys a system that does not follow that pattern as
we are working in a saturated CO2 environment. This irregular development is also due to the
Int. J. Electrochem. Sci., Vol. 7, 2012 10730
heterogeneity of the concrete paste. Although it is made using the correct amounts and mixed in
accordance with normal construction standards, non-homogenous zones are formed, in which these
properties are shown [22-23].
In order to quantify the degree of carbonation, profiles were obtained by measuring the pH of
solutions obtained by leeching soluble salts from crushed concrete. As can be seen in Figure 5, before
exposure the pH of the normal concrete is around 12.6 from the perimeter to the area around the rebar,
while after 28 days of exposure, at 1 and 2 cm from the perimeter the pH falls 2 units, in agreement
with the observations carried out on the cross-section of the same specimen, where it was found that
the carbonation depth was around 1.7 cm. At 3 and 4 cm there are also drops in the initial pH value of
12.7 to 11.7, this is because the CO2 diffuses faster through larger pores; however, the fall in pH is not
generalized to all points of the surface because the concentration of the gas at these points is still
insufficient to cause total carbonation at the given depth.
At 35 days it can be seen that the pH continues to drop, the first point has reached pH 9 and the
deepest point, around the rebar, remains at 11; at 42 and 49 days exposure, the pH of the first two
points (or of the perimeter of the probe) reached a value of 9, while inside the specimen, the pH
reached approximately 9.9 because the carbonation rate is slower due to the fact that carbon dioxide
takes longer to diffuse to the rebar due to the thickness of the concrete and a layer rich in Ca(OH) 2
around the bar.
The corrosion potentials of the carbon steel and the galvanized steel shown in Table 3 are the
averages of the measurements taken at different exposure times in the accelerated carbonation
chamber. The measurements at the start of the experiment for the steel in the C specimen, the control
that was not summited to carbonation, were -45.5 mV vs (Cu/CuSO4) for carbon steel indicating low
probability of corrosion [9-24] and -425 mV for galvanized steel vs (Cu/CuSO4) . These values will be
used as reference for comparing the change in potential during the experiment.
Table 3. Corrosion potential for carbon steel and galvanized steel, carbonation depth and pH in the
area around the rebars as a function of exposure time in the carbonation chamber.
The carbonation front reaches the rebar at some time between 42 and 49 days. The progressive
activation of the steel and galvanized rebars can be seen during the period studied. Ijes [25] mentions
the evolution in corrosion potential as the carbonation depth closes in on the concrete-steel interface.
Monitoring the potentials allows confirmation of this trend, as the Ecorr decreases even before the
carbonation reaches the metals. The pH of the concrete at 49 days shows it is in the region of zinc
oxide stability, in accordance with the Pourbaix diagram [26]; this reduces the corrosion rate even
when the corrosion potential is more negative and is located in the active region.
The change in corrosion potential as a function of exposure time is more notable for galvanized
steel, for which at 49 days the potential decreases by 551.5 mV vs (Cu/CuSO 4), while for the normal
steel it only decreases by 271.8 mV vs (Cu/CuSO4), in comparison to the initial value. Similar results
were obtained by Moreno et al. [19].
Though it is true that potentials are an indication of the probability of corrosion, the dominant
factor to corroborate the active or passive state of a metal or alloy is corrosion current (Ic). Figure 6
shows two completely opposite trends, while the current density of the carbon steel increases almost
linearly with exposure time in the accelerated carbonation chamber, the current determined for
galvanized steel increases up to 35 days of exposure, the increment then becomes slight and remains
constant after 49 days of exposure.
Figure 6. Variation in corrosion current for carbon steel and galvanized steel as a function of exposure
time.
Int. J. Electrochem. Sci., Vol. 7, 2012 10732
The behavior shown by the galvanized steel, as seen in Figure 6, suggests two stages with
regard to the formation of corrosion products:
a) Initial exposure:
When setting, the concrete has only the alkalinity given to it by the alkaline metal oxides and
alkaline earth metal oxides, where calcium plays a fundamental role as it stabilizes the hydroxy-zincate
ions and makes them precipitate; the nucleation of this compound at pH lower than 13.3 (the pH of
concrete is below this value) generates very fine and compact crystals that are then deposited and
adhere to the surface of the galvanized steel, finally carrying the material to the passive state.
Therefore, the corrosion product formed under these conditions is calcium hydroxy-zincate [HZC]
(Ca(Zn(OH)3)2×2H2O) (18), with the following reaction sequence:
b) Presence of carbonation: As the carbonation front advances into the concrete, it leads to a
new corrosion product as the carbon dioxide becomes soluble and neutralizes the alkaline pH and
forms carbonate and bicarbonate ions, causing the following reaction:
with a certain degree of compactness can be observed, thus acting as a barrier to the corrosion of the
bar. If the short-term trend continued, the corrosion rate of the galvanized steel rebar would be lower,
and therefore the durability of a structure using this material would be longer respecting a structure
using carbon steel in the same conditions of manufacture and exposure. This result is concordant with
results reported by Andrade et al. [28].
Figure 7. Surface appearance of the carbon steel at the beginning of the experiment and after 49 days.
Figure 8. Surface appearance of the galvanized steel at the beginning of the experiment and after 49
days.
4. CONCLUSIONS
Galvanized and carbon steel bars are susceptible to corrosion by carbonation of concrete when
they are used as reinforced. It is confirmed by changes toward more negative potential values during
the test and incremented corrosion rates in both cases.
Under accelerated conditions in a carbonation chamber, corrosion rate is lower for galvanized
steel. It tends to reduce at increasing exposure time, which would imply an increased durability of a
concrete structure using this material rather than conventional carbon steel under conditions of
advanced carbonation of the concrete.
ACKNOWLEDGEMENTS
The authors gratefully acknowledge financing of this project from the Department of Research at the
Pontificia Universidad Católica de Valparaíso and the galvanization company, B. Bosch, Chile.
Int. J. Electrochem. Sci., Vol. 7, 2012 10734
References
1. O. Trocónis de Rincón and Duracon Collaboration, Building and Environment 41 (2006) 952.
2. O. Trocónis de Rincón and Duracon Collaboration, Corros. Sci. 49 (2007) 2832.
3. R. Vera, M. Villarroel, A. M. Carvajal, E. Vera, C. Ortiz, Mater. Chem. Phys. 114 (2009) 467.
4. R. Vera, M. Villarroel, D. Delgado, A. M. Carvajal, F. De Barbieri, O. Troconis de
Rincón, Revista de la Construcción 8 (2009) 13.
5. Y. Choi, J. Kim, K. Lee, Corros. Sci. 48 (2006) 1733.
6. G. S. Duffo, W. Morris, I. Raspini, C. Saragovi, Corros. Sci. 46 (2004) 2143.
7. K. Yong Ann, Song Ha-Won, Corros. Sci. 49 (2007) 4113.
8. A. Lindvall, Cement Concrete Comp. 29 (2007) 88.
9. C. Andrade, I. Díaz, P. Helene, A. Romero de Carruyo, O. Trocónis de Rincón: Manual de
inspección, evaluación y diagnóstico de corrosión en estructuras de hormigón armado, 2ª edición,
CYTED, Venezuela, 1998, 17-44. In Spanish.
10. M. Fernández, S. Simons, C. Hills, P. Carey, J. Hazard. Mater.B 112 (2004) 193.
11. D. Anstice, C. Page, M. Page, Cement and Concrete Research 35 (2005) 377.
12. T. Belleze, M. Malavolta, A. Quaranta, N. Ruffini, G. Roventi, Cement Concrete Comp. 28 (2006)
246.
13. F. Belaid, G. Arliguie, R. Francois, Cement and Concrete Research 31 (2001) 1561.
14. R. Ghosh, D. Singh, Surface & Coatings Technology 201 (2007) 7346.
15. M. Carbucicchio, R. Ciprian, F. Ospitali, G. Palombarini, Corros. Sci. 50 (2008) 2605.
16. E. Sistonen, A. Cwirzen, J. Puttonen, Corros. Sci. 50 (2008) 3416.
17. R. Vera, A. M. Carvajal, M. Villarroel, M. Cortés, Revista de la Construcción 3 (2004) 83.
18. M. R. Sosa, J. Genescá, T. Pérez López, J. Reyes, R. de J. Camacho Chab, J. T. Pérez Quiroz,
Afinidad 68 (2011) 137.
19. E. Moreno, D. Ixtepan, E. Cob, Ingeniería, 9-2 (2005) 17.
20. A. Macías, C. Andrade, British Corrosion Journal 22 (1987) 119.
21. C. Andrade, A. Arteaga, C. López-Hombrados, A. Vásquez, Intergalva 2000, 2000.
22. B. Elsener, Corros. Sci. 47 (2005) 3019.
23. P. Garcés, P. Saura, A. Méndez, E. Zornoza, C. Andrade, Corrosion Science 50 (2008) 498.
24. S. Farina, G. Duffó, British Corrosion Journal 22 (1987) 162.
25. X. Urtubey, R. Lorefice, Mecánica Computacional, XXIII (2004) 1.
26. E. Chávez, Análisis del proceso de corrosión del concreto reforzado elaborado
con agregados calizos expuestos en un medio natural y cámara de carbonatación acelerada”, Tesis
Facultad de Ingeniería, UAC, 3 de septiembre de 2010. In Spanish.
27. ASTM C876 - 09 Standard test method for half-cell potential of uncoated reinforcing
steel in concrete, 2009.
28. R. Rizwan, T. Ishida, Int. J. Electrochem. Sci., 4 (2009) 1178.
29. M. Pourbaix, “Atlas d’Equilibries Electrochimiques a 25 ºC“. Edit. Gauthiers-Villars, Paris 1963,
406-413.
30. S. B. Farina, G. S. Duffo, Electrochimica Acta 52 (2007) 5131.
31. C. Andrade, C. Alonso, Galvanized steel reinforcement in concrete, edt. S.R. Yeomans, Elsevier,
(Chp. 5), 2004, 111-144.