MT 440 Technical Documentation
MT 440 Technical Documentation
PROPERTIES PROGRAMMING
o Measurements of instantaneous values of more than 50 MT440 multifunction transducer is completely
quantities (V, A, kW, kVA, kvar, kWh, kvarh, PF, Hz, MD programmable. It can be programmed using standard
thermal, THD, etc) RS232/485 communication (if available) or USB
o Power accuracy class 0.5 communication (always present). For more information
o 32 adjustable alarms about connection and programming see MT440 Users
o Input frequency: 50/60 Hz, 400 Hz manual.
o Serial communication (RS232 or RS485 up to Primary-secondary ratio (U, I), alarm limits, energy counter,
115,200 bit/s) and USB 2.0 input and output values are all programmed by setting
o MODBUS RTU communication protocol software MIQen via RS232 or RS485 communication.
o Up to 4 I/O (analogue outputs, alarm outputs, pulse
outputs, general purpose relay output, general purpose It is possible to choose between several standard output
solid-state output) value ranges (- 100 … 0 … 100%):
o Single wide auxiliary power supply range 24 – 300 Vdc, - 10 … 0 … 10 V,
40 – 276 Vac or fixed AC: 110V, 230V, 400V - 1 … 0 … 1 V,
o Automatic range of current and voltage (max. 12.5 A and - 20 … 0 … 20 mA,
600 VL-N) - 10 … 0 … 10 mA,
o Housing for DIN rail mounting - 5 … 0 … 5 mA,
o User-friendly setting software, MiQen - 1 … 0 … 1 mA,.
Within these six ranges it is possible to set any linear or bent
(with maximum 5 break points) output characteristic.
DESCRIPTION
MT440 are intended for measuring and monitoring single- COMPLIANCE WITH STANDARDS:
phase or three-phase electrical power network. They
measure RMS value by means of fast sampling of voltage and Standard EN Description
current signals, which makes instruments suitable for Safety requirements for electrical
acquisition of transient events. A built-in microcontroller 61010 equipment for measurement,
calculates measurands (voltage, current, frequency, energy, control and laboratory use
power, power factor, THD phase angles, etc.) from the Electrical measuring transducers
measured signals. for converting AC electrical
60688
APPLICATION variables into analogue and digital
signals
The MT440 multifunction transducer is used for measuring EMC requirements for electrical
and monitoring of all single-phase or three-phase values. equipment for measurement,
61326-1
Wide range of various I/O modules makes MT440 a perfect control and laboratory use - Part 1:
choice for numerous applications. General requirements
Analogue outputs with fast response. Degrees of protection provided by
60529
Alarm (relay) outputs can be used as a supervisory functions enclosures (IP code)
with user defined limit lines to all measured parameters. Environmental testing (-1 Cold, -2
60 068-2-1/ -2/ -
Precise energy measuring in all 4 quadrants with 4 Dry heat, -30 Damp heat, -6
6/ -27/-30
configurable counters can be used as a secondary energy Vibration, -27 Shock)
metering device. Tests for flammability of plastic
MT440 is delivered un-configured for customer UL 94 materials for parts in devices and
configuration with user friendly setting software MiQen. appliances
MT440 supports standard serial communication RS232 or
RS485 with speed up to 115200 baud, which is perfect for
simple applications and serial bus interfacing.
Additional USB 2.0 interface can only be used for a fast set-
up without need for auxiliary power supply. This interface is
provided with only BASIC insulation and can be used ONLY
unconnected to power inputs.
Special "ship version" is available, certified by Bureau
Veritas.
TECHNICAL DATA
Measurand Accuracy ( % of range)
Measurement input Current Rms 0.3 0.2(1)
Nominal frequency (fN) 50/60 Hz Voltage Rms L-N and L-L 0.3 0.2(1)
Power (P, Q, S) 0.5 0.4(1)
CURRENT MEASUREMENTS: Power factor (PF) 0.5
Nominal values 1, 5, 10 A Frequency (f) 10 mHz
Power and phase angle 0.5°
Nominal current (IN) 5A
THD (U), THD (I) (0 … 400 %) 0.5
Max. measured value 12.5 A sinusoidal Active energy Class 1
Max. allowed value (thermal) 15 A cont. Reactive energy Class 2
(acc. to EN 60 688) 20 × IN ; 5 × 1s
(1) On communication
Consumption < I2 × 0.01Ω per phase
Communication
VOLTAGE MEASUREMENTS: MT440 has one isolated communication port, which can be
Nominal values 62.5, 125, 250, 500 VL-N equipped with RS232 or RS485 or left open (to be specified
Nominal voltage(UN) 500 VL-N with order).
Max. measured value (cont.) 600 VL-N ; 1000 VL-L Different configurations are possible (to be specified with
Max. allowed value 2 × UN; 10 s order):
(acc. to EN 60 688) Configuration COM
Consumption < U2 / 3.3 MΩ per phase WO USB (2)
Input impedance 3.3 MΩ per phase RS232 RS232 + USB (2)
RS485 RS485 + USB (2)
FREQUENCY MEASUREMENT: (2) Read WARNING below
16 … 400 Hz (on comm.)
Frequency measuring range
fN ± 30 Hz (on analogue SERIAL
(Only for frequency meas.) RS232 RS485
out) COMMUNICATION:
Connection type Direct Network
SYSTEM:
screw
Voltage inputs can be connected either directly to low- Connection terminals screw terminals
terminals
voltage network or via a high-voltage transformer to high- Settings, measurements and
voltage network. Function
firmware upgrade
Current inputs can be connected either directly to low- Protection class II, 3.3 kVACRMS
voltage network or shall be connected to network via a Insulation
1 min
corresponding current transformer (with standard 1 A or 5 A
Max. connection length 3m 1000 m
outputs).
For more information about different system connections Transfer mode Asynchronous
see CONNECTION on page 6. Protocol MODBUS RTU
Transfer rate 2.4 kBaud to 115.2 kBaud
Basic accuracy under reference conditions Number of bus stations / 32
Total accuracy (measurements and analogue output)
according to EN 60 688 Additionally, MT440 has a USB communication port, located
Accuracy is presented as percentage of measurands nominal on the bottom under small circular plastic cover. It is
value except when it is stated as an absolute value. intended for settings ONLY and requires NO auxiliary power
Presented accuracy is valid only for a full output range. In supply. When connected to this communication port MT440
case if used output range is less than full output range is powered by USB.
(zoom-characteristics) see INTRINSIC ERROR on page 5.
Defined accuracy of analogue output is valid only after 45
minutes after power up, due to self-heating.
SAFETY:
Protection: protection class II
Pollution degree 2
Installation category CAT III; 600 V meas. inputs
CAT III; 300 V aux. uni.supply
CAT III; 600 V aux. AC supply
Acc. to EN 61010-1
Test voltages UAUXI/O, COM: 5000 VDC
UAUXU, I inputs: 5000 VDC
U, I inI/O,COM: 3320 VACrms
U inI in: 3320 VACrms
Enclosure material PC/ABS
Acc. to UL 94 V-0
yb yb1 xe
c or c 1
xb xb1 ye
Three-phase four
wire connection DIMENSIONAL DRAWING
with balanced load
4b (1W4)
Three-phase four
wire connection
with unbalanced
load
4u (3W4)
Dimensions for MT440
Output
Communication
Power supply
(COM1)
Finish
Class
Type
Out. 1
Out. 2
Out. 3
Out. 4
MT440 X X X X X X X X X
| | | | | | | | |
| | | | | | | | A Standard *
| | | | | | | | H HVE (Tropical Seal)
| | | | | | | | S Ship version**
| | | | A Analogue output *
| | | | H Analogue output (Fast)
| | | | S Pulse output (SO)
| | | | M Relay output
| | | | N Without
| | | S RS232
| | | D RS485
| | | N without
| | U 20...300 V DC, 48...276 V AC *
| | B 63,5 V AC***
| | D 110 V AC***
| | E 230 V AC***
| | I 240 V AC***
| | F 400 V AC***
| S 50, 60 Hz *
| A 400 Hz
S 0.5
* - standard
** - For this option, the universal power supply should be chosen
*** - With fixed AC supply only one I/O module (OUT1) is available