Ti094den 0809
Ti094den 0809
TI094D/06/en/08.09
71101431
Proline Promag 10 P
Table of contents
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Human interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Signal on alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operating elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Low flow cut off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Galvanic isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Certificates and approvals . . . . . . . . . . . . . . . . . . . . . 27
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
C-tick mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Electrical connection, measuring unit . . . . . . . . . . . . . . . . . . . . . 4
Ex approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Electrical connection, terminal assignment . . . . . . . . . . . . . . . . . 5
Other standards and guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Electrical connection, remote version . . . . . . . . . . . . . . . . . . . . . 5
Pressure measuring device approval . . . . . . . . . . . . . . . . . . . . . . 27
Supply voltage (power supply) . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ordering information. . . . . . . . . . . . . . . . . . . . . . . . . 28
Remote version cable specifications . . . . . . . . . . . . . . . . . . . . . . . 6
Power consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Power supply failure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Potential equalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Performance characteristics. . . . . . . . . . . . . . . . . . . . . 9
Reference operating conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . 28
Maximum measured error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Repeatability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 Endress + Hauser
Proline Promag 10 P
Ue
V
B
I
L
a0003191
Ue = B · L · v
Q=A·v
Ue Induced voltage
B Magnetic induction (magnetic field)
L Electrode spacing
v Flow velocity
Q Volume flow
A Pipe cross-section
I Current strength
Input
Measured variable Flow velocity (proportional to induced voltage)
Endress + Hauser 3
Proline Promag 10 P
Output
Output signal Current output
• Galvanically isolated
• Active: 4...20 mA, RL < 700 Ω (for HART: RL ≥ 250 Ω)
• Full scale value adjustable
• Temperature coefficient: typ. 2 μA/°C, resolution: 1.5 μA
Pulse/status output
• Galvanically isolated
• Passive: 30 V DC / 250 mA
• Open collector
• Can be configured as:
– Pulse output: Pulse value and pulse polarity can be selected, max. pulse width adjustable (5...2000 ms),
pulse frequency max. 100 Hz
– Status output: for example, can be configured for error messages, empty pipe detection, flow recognition,
limit value
Low flow cut off Low flow cut off →Switch-on point can be selected as required.
Galvanic isolation All circuits for inputs, outputs and power supply are galvanically isolated from each other
Power supply
Electrical connection,
measuring unit
e b
e b e b
f c
a
g d
i
h 24 25 26 27 1 2
+ – + – L1 N
(L+) (L-)
a0003192
Connecting the transmitter (aluminum field housing), cable cross-section max. 2.5 mm2
a Electronics compartment cover
b Power supply cable
c Ground terminal for power supply cable
d Terminal connector for power supply cable
e Signal cable
f Ground terminal for signal cable
g Terminal connector for signal cable
h Service connector
i Ground terminal for potential equalization
4 Endress + Hauser
Proline Promag 10 P
Electrical connection,
terminal assignment Order version Terminal No.
GND
S1
E1
E2
S2
E
S
d
a
c 6 5 7 8 4 37 36 42 41
2 1
5 7 4 37 42 41
E1
E2
GND
E
a0003193-en
Endress + Hauser 5
Proline Promag 10 P
Coil cable
Remote version cable • 2 x 0.75 mm2 PVC cable with common, braided copper shield (∅ ∼ 7 mm)
specifications • Conductor resistance: ≤ 37 Ω/km
• Capacitance core/core, shield grounded: ≤ 120 pF/m
• Operating temperature: –20...+8o °C
• Cable cross-section: max. 2.5 mm2
Signal cable
• 3 x 0.38 mm2 PVC cable with common, braided copper shield (∅ ∼ 7 mm)
and individual shielded cores
• With empty pipe detection (EPD): 4 x 0.38 mm2 PVC cable with common, braided copper shield (∅ ∼ 7
mm) and individual shielded cores
• Conductor resistance: ≤ 50 Ω/km
• Capacitance core/shield: ≤ 420 pF/m
• Operating temperature: –20...+8o °C
• Cable cross-section: max. 2.5 mm2
1
2
3
4
5
6
7
a b
a0003194
a Signal cable
b Coil current cable
1 Core
2 Core insulation
3 Core shield
4 Core jacket
5 Core reinforcement
6 Cable shield
7 Outer jacket
Power supply failure Lasting min. ½ cycle frequency: EEPROM saves measuring system data
6 Endress + Hauser
Proline Promag 10 P
a0003195
Caution!
For sensors without reference electrodes or without metallic process connections, potential equalization must
be carried out as described in the following special cases. These special measures apply especially where normal
grounding cannot be guaranteed or excessively strong equalizing currents are expected.
DN 300 DN 350
6 mm² Cu
a0003201
Potential equalization in the case of equalization currents in metallic, not grounded piping
Endress + Hauser 7
Proline Promag 10 P
Caution!
• Risk of damage by electrochemical corrosion. Please note the electrochemical series if ground disks and
measuring electrodes are made of different material.
• Also, observe company-internal grounding guidelines.
6 mm² Cu
a0003197
2 2
6 mm² Cu
a0003198
8 Endress + Hauser
Proline Promag 10 P
Performance characteristics
Reference operating As per DIN EN 29104 and VDI/VDE 2641:
conditions • Fluid temperature: +28 C ± 2 K
• Ambient temperature: +22 C ± 2 K
• Warm-up period: 30 minutes
Installation:
• Inlet run >10 x DN
• Outlet run > 5 x DN
• Sensor and transmitter grounded.
• The sensor is centered in the pipe.
[%]
2.5
2.0
0.5 %
1.5
1.0
0.5
0 v [m/s]
0 1 2 4 6 8 10
a0003200
Endress + Hauser 9
Proline Promag 10 P
h ³ 2 x DN
a0003202
Mounting location
Installation of pumps
Sensors may not be installed on the pump suction side. This precaution is to avoid low pressure and the
consequent risk of damage to the lining of the measuring tube.
Information on the pressure tightness of the measuring tube lining can be found in the “Pressure tightness”
section in the “Operating conditions: Process” chapter.
Pulsation dampers may be needed when using piston pumps, piston diaphragm pumps or hose pumps.
Information on the shock and vibration resistance of the measuring system can be found in the “Shock and
vibration resistance” section in the “Operating conditions: Environment” chapter.
a0003203
Installation of pumps
³ 2 x DN
³ 5 x DN
a0003204
10 Endress + Hauser
Proline Promag 10 P
Down pipes
Install a siphon or a vent valve downstream of the sensor in down pipes longer than 5 meters. This precaution
is to avoid low pressure and the consequent risk of damage to the lining of the measuring tube. This measure
also prevents the liquid current stopping in the pipe which could cause air locks. Information on the pressure
tightness of the measuring tube lining can be found in the “Pressure tightness” section in the “Operating
conditions: Process” chapter.
>5m
a0003205
Orientation
An optimum orientation helps avoid gas and air accumulations and deposits in the measuring tube. However,
the measuring device also offers the additional function of empty pipe detection (EPD) for detecting partially
filled measuring tubes or if outgassing fluids or fluctuating operating pressures are present.
Vertical orientation
This is the ideal orientation for self-emptying piping systems and for use in conjunction with empty pipe
detection.
a0003206
Vertical orientation
Horizontal orientation
The measuring electrode axis should be horizontal. This prevents brief insulation of the two measuring
electrodes by entrained air bubbles.
Caution!
Empty pipe detection only works correctly with horizontal orientation if the transmitter housing is facing
upwards. Otherwise there is no guarantee that empty pipe detection will respond if the measuring tube is only
partially filled or empty.
Endress + Hauser 11
Proline Promag 10 P
A
1
2 2
A
3
a0003207
Horizontal orientation
1 EPD electrode for empty pipe detection
2 Measuring electrodes for signal detection
3 Reference electrode for potential equalization
Vibrations
Secure the piping and the sensor if vibration is severe.
Caution!
If vibrations are too severe, we recommend the sensor and transmitter be mounted separately. Information on
the permitted shock and vibration resistance can be found in the
“Shock and vibration resistance” section in the “Operating conditions: Environment” chapter.
> 10 m
a0003208
12 Endress + Hauser
Proline Promag 10 P
Inlet and outlet run If possible, install the sensor well clear of assemblies such as valves, T-pieces, elbows, etc.
Note the following inlet and outlet runs to comply with measuring accuracy specifications:
• Inlet run: ≥ 5 x DN
• Outlet run: ≥ 2 x DN
5 x DN 2 x DN
a0003210
Adapters Suitable adapters to DIN EN 545 (double-flange reducers) can be used to install the sensor in larger-diameter
pipes. The resultant increase in the rate of flow improves measuring accuracy with very slow-moving fluids.
The nomogram shown here can be used to calculate the pressure loss caused by reducers and expanders.
Note!
The nomogram only applies to liquids of viscosity similar to water.
1. Calculate the ratio of the diameters d/D.
2. From the nomogram read off the pressure loss as a function of flow velocity (downstream from the
reduction)
and the d/D ratio.
[mbar]
100
8 m/s
7 m/s
6 m/s
10
5 m/s
4 m/s
max. 8°
3 m/s
d D
2 m/s
1
1 m/s
Endress + Hauser 13
Proline Promag 10 P
Length of connecting cable When mounting the remote version, please note the following to achieve correct measuring results:
• Fix cable run or lay in armored conduit. Cable movements can falsify the measuring signal especially in the
case of low fluid conductivities.
• Route the cable well clear of electrical machines and switching elements.
• If necessary, ensure potential equalization between sensor and transmitter.
• The permitted cable length Lmax is determined by the fluid conductivity.
A minimum conductivity of 50 μS/cm is needed for all fluids.
• When the empty pipe detection function is switched on (EPD), the maximum connecting cable length is
10 m.
[mS/cm]
200
L max
100
50
[m]
50 100 200
L max
a0003214
Storage temperature • The temperature range for storing the device corresponds to the permitted ambient temperature range of the
transmitter and the sensor (see “Ambient temperature range”).
• The measuring device must be protected against direct sunlight during storage in order to avoid unacceptably
high surface temperatures.
• A storage location must be selected where moisture does not collect in the measuring device. This will help
prevent fungus and bacteria infestation which can damage the liner.
• If protecting caps or protective covers are mounted, these must not be removed before mounting the device.
14 Endress + Hauser
Proline Promag 10 P
Medium temperature range –40...+130 °C for PTFE (DN 25...300), restrictions→ see diagrams
TA [°C]
60
50
40 -
Esc
+ E
30
PTFE
20
10
0
-10
-40 -20 0 20 40 60 80 100 120 140 160 180 T [°C]
F
a0003449
TA [°C]
60
50
40
30
PTFE
20
10
0
-10
-40 -20 0 20 40 60 80 100 120 140 160 180 T [°C]
F
a0003446
Endress + Hauser 15
Proline Promag 10 P
[mm] [inch] Material Limit values for the absolute pressure [mbar] at fluid temperatures:
32 - PTFE 0 0 0 100
65 - PTFE 0 * 40 130
16 Endress + Hauser
Proline Promag 10 P
Limiting flow The diameter of the pipe and the flow rate determine the nominal diameter of the sensor.
The optimum flow velocity is between 2…3 m/s. The velocity of flow (v), moreover, has to be matched to the
physical properties of the fluid:
• v < 2 m/s: for abrasive fluids such as potter's clay, lime milk, ore slurry, etc.
• v > 2 m/s: for fluids causing build-up such as wastewater sludges, etc.
Min./max. full scale value Full scale value Pulse value Low flow cut off
Current output
[mm] [inch] (v ~ 0.3 or 10 m/s) (v ~ 2.5 m/s) (~ 2 pulses/s) (v ~ 0.04 m/s)
3 3 3
25 1" 9...300 dm /min 75 dm /min 0.50 dm 1 dm3/min
Min./max. full scale value Full scale value Pulse value Low flow cut off
Current output
[inch] [mm] (v ~ 0.3 or 10 m/s) (v ~ 2.5 m/s) (~ 2 pulses/s) (v ~ 0.04 m/s)
Endress + Hauser 17
Proline Promag 10 P
Min./max. full scale value Full scale value Pulse value Low flow cut off
Current output
[inch] [mm] (v ~ 0.3 or 10 m/s) (v ~ 2.5 m/s) (~ 2 pulses/s) (v ~ 0.04 m/s)
24" 600 1400...44000 gal/min 10500 gal/min 100 gal 180 gal/min
Pressure loss • No pressure loss if the sensor is installed in a pipe with the same nominal diameter.
• Pressure losses for configurations incorporating adapters according to DIN EN 545
(→ “Operating conditions: Installation” → “Adapters”)
Mechanical construction
Measuring tube specifications Diameter Pressure rating Internal diameter
32 – PN 40 Table E – – 20K 32 35
65 – PN 16 – – – 10K 63 67
18 Endress + Hauser
Proline Promag 10 P
161...181
178
20...30 121
150
Esc
- + E
327.5
177.5
Ø 8.6 (M8)
100
133
ANSCHLUSSKLEMMEN - FIELD TERMINALS
25
123
a0003215
A B
248 ±2 238
Esc
Esc - + E
- + E
a0003216
Endress + Hauser 19
Proline Promag 10 P
Compact version
161...181
178 20...30 121
150
Esc
- + E
B
A
C
E
K L (DVGW)
a0003217
DN L A B C K E
The length (L) is always the same regardless of the pressure rating selected.
1)
For flanges to AS, only the nominal diameters DN 80, 100 and 150...300 are available
20 Endress + Hauser
Proline Promag 10 P
Remote version
129 163
143
102
B
A
C
E
K L (DVGW)
a0003219
DN L A B C K E
The length (L) is always the same regardless of the pressure rating selected.
1)
For flanges to AS, only the nominal diameters DN 80, 100 and 150...300 are available.
Endress + Hauser 21
Proline Promag 10 P
ØB
6.5
Ø
15
Ø di
10
ØD
2
a0003221
DN 1) di B D H
32 - 35 80 87.5 94.5
22 Endress + Hauser
Proline Promag 10 P
PN 40
PN 40
40 1 ½" 9.4 8.3 9.4 7.4 6.3 7.4 6.0
10K
10K
PN 16
PN 16
100 4" 16.0 14.7 16.0 14.0 12.7 14.0 6.0
Class 150
Class 150
150 6" 25.5 24.5 25.5 23.5 22.5 23.5 6.0
PN 10
400 16" 135 205 133 203 6.0
Endress + Hauser 23
Proline Promag 10 P
[bar]
40
PN 40
35
30
25
PN 25
20
15
PN 16
10
PN 10
5 PN 6
0
-60 -40 -20 0 20 40 60 80 100 120 140 160 180 [°C]
F06-xxFxxxxx-05-xx-xx-xx-000
[bar]
40
PN 40
35
30
25
PN 25
20
15 PN 16
10
PN 10
5 PN 6
0
-60 -40 -20 0 20 40 60 80 100 120 140 160 180 [°C]
A0005304-en
24 Endress + Hauser
Proline Promag 10 P
[bar] [psi]
60 870
50 725
Class 300
40 580
30 435
20 290
Class 150
10 145
0 0
-60 -40 -20 0 20 40 60 80 100 120 140 160 180 [°C]
a0003226
[bar]
60
50
40 Class 300
30
20
Class 150
10
0
-40 -20 0 20 40 60 80 100 120 140 160 180 [°C]
A0005307-en
[bar]
30
20K
20
10K
10
0
-60 -40 -20 0 20 40 60 80 100 120 140 160 180 [°C]
a0003228
Endress + Hauser 25
Proline Promag 10 P
[bar]
25
20
15
10
0
-60 -40 -20 0 20 40 60 80 100 120 140 160 [°C]
F06-xxFxxxxx-05-xx-xx-xx-010
Fitted electrodes Measuring electrodes, reference electrodes and empty pipe detection electrodes available as standard with:
• 1.4435
• Alloy C-22
Surface roughness Electrodes with 1.4435 (AISI 316L), Alloy C-22: ≤ 0.3...0.5 μm
(All data refer to parts in contact with medium)
Human interface
Display elements • Liquid crystal display: unilluminated, two-line, 16 characters per line
• Display (operating mode) preconfigured: volume flow and totalizer status
• 1 totalizer
Remote operation Operation via HART protocol and ToF Tool - Fieldtool Package
26 Endress + Hauser
Proline Promag 10 P
C-tick mark The measuring system meets the EMC requirements of the Australian Communications Authority
(ACA)
Ex approval Information about currently available Ex versions (ATEX, FM, CSA, etc.) can be supplied by your Endress
+Hauser Sales Center on request. All explosion protection data are given in a separate documentation which
is available upon request.
Pressure measuring device Measuring devices with a nominal diameter smaller than or equal to DN 25 correspond to Article 3(3)
approval of the EC Directive 97/23/EC (Pressure Equipment Directive) and have been designed and manufactured
according to good engineering practice. Where necessary (depending on the medium and process pressure),
there are additional optional approvals to Category II/III for larger nominal diameters.
Endress + Hauser 27
Proline Promag 10 P
Ordering information
Your Endress+Hauser service organization can provide detailed ordering information and information on the
order codes on request.
Accessories
Various accessories, which can be ordered separately from Endress
+Hauser, are available for the transmitter and the sensor. Your Endress+Hauser service organization can
provide detailed information on the order codes in question
Documentation
• System Information Promag 10 (SI042D/06/en)
• Operating Instructions Promag 10 (BA082D/06/en)
Registered trademarks
HART®
Registered trademark of the HART Communication Foundation, Austin, USA
ToF Tool - Fieldtool® Package
Registered or registration-pending trademarks of Endress+Hauser Flowtec AG, Reinach, CH
Instruments International
Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland
TI094D/06/en/08.09
71101431
FM+SGML6.0 ProMoDo