Fujian LEAD Automatic Equipment Co., LTD
Fujian LEAD Automatic Equipment Co., LTD
Fujian LEAD Automatic Equipment Co., LTD
The thermostat monitors dangerous electrical transformers. It may cause serious damage to
property or personal injury or even death if you fail to operate the machine according to
regulations in this manual.
Only qualified technician should be allowed to operate the thermostat. The technician
should be familiar with all the safety instructions, installation, operation and maintenance
procedures before operation. The normal operation of the thermostat depends on the proper
transportation, installation, operation and maintenance.
1. Power voltage of the thermostat is 220VAC~240VAC, 50Hz/60Hz;
2. Please make sure all wires are correctly secure;
3. Please do not contact exposed live parts after power on;
4. Terminals L, N, 1, 2, 3, 4, 5, 6, 7 carry dangerous voltages;
5. It cannot be short-circuited between terminals of fan output 1, 2, 3, 4, 5, 6 and terminal 7;
6. Before the high-voltage test of dry transformer is in progress, the sensor cable must be
removed from the thermostat to avoid damaging this equipment!
Attention
1. Please read the instructions carefully before using it;
2. The thermostat shall be used for purposes specified by our company only. The thermostat
may suffer a fault and even failure if it is changed without approval;
3. Please avoid using this thermostat in the atmosphere containing SO2, H2S or other
corrosive gases. Otherwise, contacts of the thermostat relay will lose efficacy;
4. Connect electrical wiring after installation. Make sure all the connection is correct before
power on;
5. Do not grill sensor probes with a lighter (Flame temperature is about 800℃);
6. Do not apply voltage and current that is greater than the maximum ratings in the relay
output contacts;
7. When the actual product is the custom special models, if the specification content is
conflict to the manual content, '9 special models attached' shall prevail.
8. Keep the instructions in easy reach, and send it to all users.
Contents
1. Introduction .................................................................................................... 1
4. Features .......................................................................................................... 2
8. Installation ..................................................................................................... 9
2. Product Type
Type Function
3. Technical Indicators
3.1 Range of measurement: -30.0℃~240.0℃
3.2 Grade of accuracy: Grade 1 (Grade 0.5 for thermostat, Grade B for sensor)
3.3 Resolution : 0.1℃
3.4 Room temperature: -40℃~+60℃
3.5 Power voltage: AC220V±10% ( 50Hz/60Hz )
3.6 Power consumption: 8W
3.7 Sensor: Three (Four) Pt100 platinum thermo-resistors, three PTC Thermistor
3.8 Control of output capacity: 10A/220VAC (Resistance)
3.9 Weight: <3Kg
3.10 Overall dimension of thermostat: 260mm×200mm×85mm (High×Width×Deep)
3.11 Analogue output: 4~20mA current
3.12 Digital output: RS485 serial communication interface
1
4. Features
4.1 Three-phase winding (and iron core temperature) circular display or maximum value display
function.
4.2 Fan control function. Auto start and stop fan according to the set value so that dry-type transformers
could work safely at normal temperatures. Fan will start when the highest temperature among any three
phases exceeds the set value of fan-start, or start the fan manually. At the same time, the panel 'fan'
indicator light.
4.2.1 Thermostat can connect 1~6 fans or do not connect any. If there are fans, when fans start, the
corresponding led indicator turn green.
4.2.2 If fan phase failure occurs, the corresponding led indicator turn red with alarm. If the number of
connected fans is less than 6, the LED for the unconnected fans will not be on. If the number of external
fans is less than 6, set the number of fans to be the actual number of fans, and the fan must be connected
from No.1.
4.3 Over temperature alarm function. When the highest temperature among any three phases exceeds the
set value of over-temp alarm, the led indicator 'Over-temp' turn light with alarm and the
terminal(14, 15, 16) outputs a switch signal.
4.4 Over temperature trip function. When the highest temperature among any three phases exceeds the set
value of over-temp trip, the led indicator 'Trip' turn light with alarm and the terminal(11, 12, 13)
outputs a switch signal. When the highest coil temp has increased the preset limit for 6 seconds, it will send
an alarm signal.
4.4.1 If the PTC sensor has been used, the Auto-Power-Cut output terminals will not activate unless both
kinds of sensors, the PT100 and PTC, have detected the coils’ temperature meets the preset limit, thus
increasing the reliability of Power-Cut function.
4.5 Thermostat fault alarm function. When there is fault in thermostat, the led indicator 'Fault' turn light
with alarm and the terminal (17, 18, 19) outputs a switch signal.
4.5.1 Different colors represent different phase thermostat fault: Yellow represents phase A, green
represents phase B, red represents phase C. If not light, the thermostat works normally.
4.5.2 –oP- represents open circuit of sensor, -oL- represents short circuit of sensor in the temperature
display area.
4.5.3 When there is a phase or two-phase fault in the thermostat, the fan is controlled according to the
temperature signal of the sensor. When the three-phase sensor fails, the fan is turned on immediately.
4.6 Parameter setting function. You can set the stop and start fan value, over-temp alarm value,
over-temp trip value, the timing of fan, communication address, baud rate and the number of fan
control by directly through the key. Those setting value will save when power off.
2
4.7 Manually control the fan function. Start fan manually by pressing the key 'Manual'. This feature is
also available as a fun test function.
4.8 Start the fan with a timer function. 0 to 255 hours can be arbitrarily set (If 0 is set, it means no timer
function). After regular time arrives, the fan will start 1 minute. 24 hours is set by our factory.
4.9 With 'Black box' function. The thermostats automatically record instantaneous temperature of the three
-phase windings before power failure. In order to avoid the power down and change the memory data again,
if the temperature below 80℃ before power down, not to refresh the original record temperature.
4.10 History highest temperature. Recording the highest temperature of each phase since power on, to
prepare query.
5. Operating Instructions
Fan 1 Fan 2 Fan 3 Fan 4 Fan 5 Fan 6 Manual Highest Over-Temp Trip Fault
5.1 First power: The thermostat is displaying temperature of phase A, B, C (d iron core circular
measurement/ambient temperature) circularly when power on and the self-test is completed. If the
thermostat is not connected with the sensor, the fan automatically starts.
5.2 Maximum value and circular value display switching: The thermostat will enter maximum value
state by pressing the key 'Highest/+' under circular displaying status and the indicator 'Highest' lights, then
it displays the highest temperature of the 3 windings; Vice versa.
5.3 Start fan manually: The thermostat will start the fan manually by pressing the key 'Manual' under
normal working mode and the indicator ' Manual' lights ; Vice versa.
5.4 Power-down data query function: Pressing the key 'Inquire/-' continuously, the thermostat is
displaying the temperature of phase A, B, C sequentially (d iron core circular measurement/ambient
3
temperature) before power down and historical maximum temperature of phase A, B, C.
5.5 Inquire control parameters
The
Display The second
Steps first ~ Description Remark
the fifth
Key digital
digital
Temperature value for fan
1 Function 1 80.0 The factory setting is 80.0 ℃
stop
Communication address of
6 Function P 1 The factory setting is 1
the thermostat
Note: When setting parameters, make sure that over-temp trip value> over-temp alarm value> start fan
5
temperature value> stop fan temperature value, and the minimum interval is not less than 5℃.
Inquire/-
D-way highest temp since If there is d-way
8 4. XXX.X
power on measured
电源
AH AL Er 开关
Power
Switch
31 32 33 34 32' 31' 11 12 13 14 15 16 17 18 19 1 2 3 4 5 6 7 N L
C B A G B- A+
NO NC NO NC NO NC
A A A
21 22 23 24 25 26
A: PTC
B: PTC
C: PTC
B: Pt100
C: Pt100
A: Pt100
型号 Model :BWDK-3208BE
21 22 23 24 25 26
15
14
13
12
11
10
9
8
1
3
6
6.1 Power terminals (L&N): The instrument’s main power resource AC220V.
6.2 Fan outputs (1~7): 0-6 fans can be used in the system according to the real application. If one fan is
needed, using terminals 1&7. If two fans are needed, using terminals 1, 2&7. If three fans are needed, using
terminals 1, 2, 3&7. If four fans are needed, using terminals 1, 2, 3, 4&7. If five fans are needed, using
terminals 1, 2, 3, 4, 5&7. If six fans are needed, using terminals 1, 2, 3, 4, 5, 6&7.
Note: If the fans were connected wrongly, the LED indication will not be correct, and the alarming signals
will be activated.
6.3 Fault outputs (17&18&19): When the thermostat fault, they will be activated, thus sending a switch
signal to the remote alarming unit.
6.4 Over temp alarm terminals (14&15&16): When the over temp alarm is needed they will be activated,
thus sending a switch signal to the remote control unit.
6.5 Power cut terminals (11&12&13): When the power cutoff is needed they will be activated, thus
sending a switch signal to cutoff power.
6.6 Sensors socket (DB15): Connecting the three coils temperature sensors.
6.7 4~20mA current output: Terminals 31, 32, 33, 34 outputs 4~20mA current corresponding to the
temperature of phase A, B, C. (4mA corresponding to 0.0℃, 20mA corresponding to 200.0℃)
6.8 RS485 communication: Terminals 31’, 32’ is RS485 communication interface.
6.9 Spare terminals are terminal 21~26.
7. Communication Protocol
7.1 Instructions on communication setting: MODBUS RTU communication protocol.
● Using asynchronous communication data transfer format of RS485;
● Baud rate is set 9600bps, 19200bps, 4800bps or 2400bps; No check bit, 8-bit data, 1 stop bit;
● Using CRC16;
● Communication distance<1200m/twisted pair(It is related to the number of thermostat and
communication lines).
7.2 Data Format
a. Master computer transmit data
No. Description Value Remark
1 Address 01H-C7H
2 Function code 03H Fixed format
3 Initial address high 8-bit 00H Definition of Initial
4 Initial address low 8-bit ××H address see as below
5 Data number word high 8-bit 00H
6 Data number word low 8-bit ××H
7 CRC check low 8-bit ××H
8 CRC check high 8-bit ××H
7
2 Function code 03H
3 The number of bytes of returned data ××H Returns the data word×2
4 Status word high 8-bit ××H Definition of status bit see
5 Status word low 8-bit ××H as below
6 Temperature data high 8-bit in phase A 00H
7 Temperature data low 8-bit in phase A ××H Unit: ℃
8 Temperature data high 8-bit in phase B 00H Actual temperature is equal
9 Temperature data low 8-bit in phase B ××H to the temperature data
10 Temperature data high 8-bit in phase C 00H minus 23H
11 Temperature data low 8-bit in phase C ××H
12 Interval fan timing high 8-bit 00H If '0', it indicates the fan has
13 Interval fan timing low 8-bit ××H no timed start function
14 Temperature data high 8-bit in d-way 00H If there is no d-way, the
15 Temperature data low 8-bit in d-way ××H data is invalid
16 CRC check low 8-bit ××H
17 CRC check high 8-bit ××H
8
Bit 5='0', it indicates it has not output trip signal;
Bit 5='1', it indicates it has output trip signal.
Bit 6='0', it indicates sensor of d-way works in normal;
Bit 6='1', it indicates sensor of d-way failed.
Bit 7='0', it indicates the d-way has not over-temperature, if there is no d-way, the data is invalid;
Bit 7='1', it indicates the d-way has over-temperature, if there is no d-way, the data is invalid;
f. Example
When communication address of a thermostat is 1, temperature in phase A is 64.0℃, temperature in
phase B is 54.0℃, temperature in phase C is 68.0℃, timed start time of fan is 24 hours, temperature in
d-way is 65.0℃, sensor Pt100 works in normal, fan has not started, it has not outputs over-temperature
alarm and trip signal.
Master computer transmit data:
01H-03H-00H-00H-00H-06H-C5H-C8H
Slave computer sends back data:
01H-03H-0CH-00H-00H-00H-63H-00H-59H-00H-67H-00H-18H-00H-64H-
52H-A3H
8. Installation
8.1 Refer to figure 2, drill a rectangular hole of 232×182mm in the embedded body and also drill another
four holes of same size as installation B holes.
8.2 Put the thermostat case bottom into the rectangular hole of 232×182mm in the embedded body. The
four ф4.5 holes in the case should be overlapped exactly with the holes in embedded body.
8.3 Put the four provided supporting legs through the four holes in the case bottom and fix the case onto the
embedded body by 4 M4 screws.
9
B B
B B
Figure1 Figure2
9. Common problem
Fault phenomena Analysis Solution
Power failure (such as power loss or
Check the power supply and the power
Black screen or no displays under voltage) ;
switch with a multi-meter.
of temperature control panel Power switch is not turned on.
Controller power circuit failure Manufacturer handling
Sensor plug is unplugged, loose or in Tighten the temperature sensor joint
poor contact. screw or replace
“OP” blinks in X-phase,
Sensor failure or damage; Replacement of temperature sensor
fault light on
The temperature sensor measurement
Replacement of temperature controller
circuit is damaged.
“OL” blinks in X-phase,
Sensor failure or damage Replacement of temperature sensor
fault light on
Loose or poor connection of fan Check whether the terminal connection
terminals of fan is normal
The number of fans set by controller
Temperature controller Set the number of fans in temperature
does not conform to the actual
alarm, showing fan fault control as the actual number in use
connection.
Check if the fan is faulty and replace
Fan fused
the fuse
Fan runs of itself before Manual start-up of fan state Press "manual " to cancel fan start-up
10
starting temperature is Regular start and stop of fan Normal state
reached.
Modification of fan start-stop
View fan start-stop parameters
parameters
11