PCS-902 Line Distance Protection
PCS-902 Line Distance Protection
PCS-902
Line Distance Protection
Integrated Secondary
System
The PCS-902 provides comprehensive protection and control The PCS-902 is compatible with IEC 61850 station bus and
solutions for transmission lines with high-speed sub-cycle process bus applications. It supports IEC 61850-8-1 MMS,
distance element. The PCS-902 is intended for application GOOSE and IEC 61850-9-2 Sampling Value. The RJ-45
on overhead lines and underground cables with diverse faceplate port is provided for testing and setting, allowing for
voltage levels. These include series compensated, double- smoother commissioning and maintenance.
circuit, heavily loaded, weak in feed (WI), short and long
lines. It can meet the requirements of single-pole or three-
pole tripping; it also provides single and/or three-pole auto-
reclosing functions. The PCS-902 is suitable for single and dual-
breaker applications, providing optional dual CT inputs, dual
Functions
breaker failure protections, dual breaker auto-reclosing and dual Protection and Control
synchro-checks. Additionally, the relay integrates the remote/ • Five zone phase-to-phase distance protection (21P)
local control of circuit breaker, disconnector and earth switch. Directional, load encroachment, power swing blocking and
unique low-voltage elements are provided for phase-to-
The PCS-902 employs a wide range of innovative patented phase distance protection.
technologies, such as DPFC (Deviation Power Frequency
Component) distance protection and unique power swing • One zone phase-to-phase distance protection for pilot
blocking logic. Thus, guaranteeing accurate and reliable scheme (85/21P)
operations. The relay provides an independent zone for pilot scheme of
PUTT, POTT, Blocking, Unblocking, DTT & Zone Extension.
The scheme integrates current reversal logic, weak-infeed
echo and open breaker echo.
• Four stage neutral overcurrent protection (67N, 50/51N) • Thermal overload protection (49)
Selectable time characteristics (definite-time or inverse-time) Thermal accumulation using thermal models is implemented
and directional elements (forward, reverse or non-directional) for overload protection. Two stages for alarm and two stages
are provided. A harmonic blocking function is integrated to for tripping are provided.
restrain each stage independently.
• Pole discrepancy protection
• Breaker failure protection for one or two breakers (50BF) It is used to prevent overheating of generators/motors due to
Breaker failure protection can be applied to single-breaker pole discrepancy.
and dual-breaker applications.
• Single and/or three-pole auto-reclosing (single-breaker or
• Stub overcurrent protection (50S) dual-breaker ). (79)
Stub protection is introduced to protect the T-zone in one- Single/three pole auto-reclosing is provided for single- and
and-a-half breaker and ring breaker arrangements. dual-breaker applications. Priority logic is integrated for the
applications of one-and-a-half breaker and ring breaker
• Two sta ge u nder v olt age pr otec tion and tw o s t a g e arrangements.
overvoltage protection (27/59)
Phase under/over voltage protection and negative/zero • Remote/local control
sequence overvoltage protection are provided. The control of circuit breaker, disconnector and earth switch
can be implemented via communication, LCD menu and
• Four stage underfrequency protection and four stage binary inputs. User programmable interlocking logics are
overfrequency protection (81) available by PCS-Explorer.
Frequency is calculated by using the positive sequence
voltage. The df/dt element is provided for the supervision of • Synchronism check (25)
underfrequency protection. Synchro-check can be used for auto-reclosing and manual
closing for single-breaker and dual-breaker.
• Phase overcurrent protection during VT failure (51P VT)
Independent phase overcurrent protection is automatically • Voltage and current drift auto adjustment.
enabled to substitute the phase-to-phase distance protection, The relay continually and automatically traces the voltage
which is blocked during VT failure. and current drifts and adjusts the zero point to acquire
accurate measurements.
• Neutral overcurrent protection during VT failure (51N VT)
Independent neutral overcurrent protection is automatically • Frequency tracking.
enabled to substitute the phase-to-ground distance Frequency tracking is provided to accommodate the
protection, which is blocked during VT failure. frequency shifts in power system.
Integrated Secondary
component failure. One works as a fault detector and the
• Disturbance recorder including 32 disturbance records with
other is designed for protection logic. Tripping outputs are
waveforms (The format is compatible with COMTRADE.)
System
supervised by both data acquisition paths.
• Pilot communication channel supervision
• System frequency supervision • Self-adaptive floating threshold which only reflects deviation
• Clock synchronization using IRIG-B, SNTP, PPS (Pulse-Per- of power frequency components improves the sensitivity and
Second) and PPM (Pulse-Per-Minute) reliability during load fluctuation and system disturbance.