Measurement of Winding Resistance, Voltage Ratio Test, Polarity Test
Measurement of Winding Resistance, Voltage Ratio Test, Polarity Test
Measurement of Winding Resistance, Voltage Ratio Test, Polarity Test
In addition some other tests are also carried out by the consumer at site before commissioning
basis throughout its life
and also periodically in regular and emergency
Transformer Tests done by Manufacturer
(a) Routine Tests
(b) Type Tests
(c) Special Tests
Transformer Tests done at Site
(d) Pre Commissioning Tests
(e) Periodic/Condition Monitoring Tests
(D Emergency Test
(a) Routine Tests:
A Routine tests of transformer is mainly for confirming operational performance of individual
unit in a production lot. Routine tests are carried out on every unit manufactured.
c) Special Tests
Special tests are tests, other than routine or type tests, agreed between manufacturer and
purchaser.
on three-phase transformers.
(1) Zero-sequence impedance
(2) Short-circuit test.
current
(3) Harmonics on the no-load
fan and oil-pump motors.
(4) Power taken by
(5) Determination of sound levels.
Determination of capacitances between windings and earth, and between windings.
(6)
Determination of transient voltage transfer between windings.
(7)
3.6
MEASUREMENT OF wINDING RESISTANCE:
The following methods can be used to measure resistance of the transformer winding
1. Wheatstone bridge
2. Kelvin's double bridge
3. Voltmeter-ammeter method
voitmeter-ammeter method, direct current is passed through the winding from the suitable
Source.
Low voltage
D.C. Supply
(a)
Low voltage
D.C. Supply
o
(b) Rp
Rp
Low voltage
D.C. Supply
RpA
2 (c)
FIG. 3.7 DC/AC RESISTANCE
MEASUREMENT
The test current should be less than tne rared Current of the
the winding and the current flowing through it are
winding. Voltage dron across
measured.
and current is found,
Ratio of the voltage drop
The arrangement is shown in Fig. 3.7 the ammeter, voltmeter and variable resistance
are
connected as shown.
The value of mcasured resistance changes due to increase in temperature. For copper
conductors therefore, the resistance at required temperature is found as follows
R 2 2 + 234.5
R, + 234.5
where, 2 =
Temperature (°C) of the winding at the end of test.
Temperature (°C) of the winding (cold) at the beginning of test.
Resistance of the winding at the end of test.
R =
220V or
3.7 VOLTAGE RATIOTEST. 400V AC
1. Using voltmeter
2. Using ratio meter
help of voltmeter
v
1. Voltage ratio test with the (v
For this the HT winding
is connected to 220 V or
400 V. a.c. supply. Its secondary
winding is kept
open circuited.
the HT side and LLT
Readings of the voltages
on
LT side is calculated.
FIG. 3.8 VOLTAGE RATIO TEST
meter USING VOLTMETER
2. Voltage ratio test using ratio
windings in it. One is the HT winding
transformer. There ae two
Ratio meter is a portable
which is connected to
the supply.
Some tapings are coarse while some are
Transfomer
under test
LT HT
HT LT
Ratio
Meter
Current will circulate when the values of the two voltages are not equal. This current is
indicated by ammeter. The reading of the ammeter is brought to zero value by adjusting
the coarse and fine tappings
Value of the secondary voltage can be found from the tapings. The primary voltage is
measured with the help of voltmeter. This way the voltage ratio is measured.
Error of +0.5% in the declared ratio and the actual ratio is acceptable
Note: Voltage ratio test is done for each tap. Starting is done from the lowest tap and
then further readings are taken. Tap chaning is done manually.
LV sides.
(a) Voltage of 415 V 3-phase a.c. is applied to the HV winding. The secondary side is
kept open circuited.
Y Volts R phase A
Y - B Volts Y phase A
B R Volts B phase
(b) Voltage of 415 V, 3-phase is applied to the LV winding. The HV winding is kept
open circuited.
r -y Volts r phase
A
y b Voltsy phase A
b r Volts| b phase. _A
For single phase transformer, the LV winding is kept open circuited and 230 V a.c. single
phase supply is given to the HV winding. The magnetizing current is measured.
2. Connect one terminal of the secondary winding of one transformer to any one terminal
of the secondary winding of another transformer.
115 115
10 10
A.C. A.C.
COM COM
115
115
230V
oV
COM
COM
(a) (b)
FIG. 3.10 POLARITY TEST (a) CORRECT POLARITY (b) WRONG POLARITY
3. Connect a voltmeter with voltage rating double the voltage rating of the secondary
winding across the remaining two terminals.
Apply rated voltage to the primary winding.
5. If the voltmeter shows the zero reading, the polarity of the connected terminals is
correct.
6. If the reading of the voltmeter is double the rating of the secondary winding, the polarity
is not correct. In this case, the polarity will becomne correct by reversing the connections
of the secondary.