Max. bending moment assumed simply supported from one side and continous from other side
M= UT*L2/10 = 3328.66 Kg.cm/m
As per 5.10.3.1 .stress should not exceed limitations specified in AISC
Fa =0.75 Fy = 1843.1367 Kg/cm2
Req.Plate thickness of Roof , tr =(6*M /(B*Fb))0.5 = 3.2917857 mm
where
* Plate width B = 100 cm
* Corrosion allowance ca = 0 mm
Min.thickness including corrosion allowance tmin. = 4.0 mm
Provided thickness of Roof Plates t = 6.0 mm
(iv) ROOF PLATES JOINTS& WIGHT
DR =Ring Rafter
13.5 m
Center Col. UPN 180
Pipe 14"Ø STD 23 nos.
No. of Rafters
Diameter of the tank, in m (D) = 27.00 m
Diameter of the ring, in m (DR) = 13.50 m
Total no. of rafters on the circumference of the shell, (nM+nS) = 46.00 Nos
Provided rafter center line spacing, in m = 1.844 m <= 1.885 m O.K.
Span L = 6.77 m
Spacing at shell = Л *D/(ns+nM) S = 1.844 m
Spacing at ring Sr = 0.922 m
Average uniform distributed load = wunif. * (S+Sr)*UT/2 = 230 kg/m
Using 16 Nos IPE270
Self weight = 36.1 kg/m
Beam flange Depth = 200 mm
Total uniform load acting on the beam including self weight, ws
ws = 266 kg/m
Sectional modulus Z = 407.76 cm³
Moment of Inertia Ix = 5504.75 cm4
Sizing of Col.Cap
Cap Diameter 2m
Stiffeners of Cap 713 mm X 356.5 x 15 mm
Top Beams w,t = 7.968 kg
Weight of Cap = 1078.103 kg
(v) Sizing of Center Column Base Plate
Maximum load on the column = 61545 kgs
Considering center column is resting on concrete foundation
Ultimate strength of concrete (28 day) = 300 kg/cm²
Allowable compressive strength, fc = 90 kg/cm²
Using base plate 455 X 455 X 16 mm
Actual bearing perssure on concrete = Load / base plate area
= 37.87 kg/cm² < 90 Safe
Outside diameter of the column = 355.6 mm
Overhanging of the base plate, L = 4.97 cm
Considering section of unit width, b = 1 cm
Maximum bending moment , M =b.w.L2 / 2 = 467.72 kg.cm
Cap = 1,078.1 kg
Col. = 903.1 kg
BasePlate+Guide angles = 47.8 kg
Rafters = 25,924.8 kg
Connections = 653.6 kg
Bracing = 1,155.6 kg
Total w,t = 34,852.3 kg