Csu-01 800 8RD
Csu-01 800 8RD
0 ev - build 201014|S
Citizen Industries Limited.
Citizen Arena, Opp. Nidhi Hospital
Navrangpura, Ahmedabad - 380009, India.
Phone No.+ 91 79 - 2643 1869 / 2644 5155
E-mail: [email protected]
Customer M/s. Apex HVAC Date 20.04.2021
To the k. a. of Mr. Karan Our Offer -
Your Reference Kerala Hospital Project Description CSU-01
COOLING COIL - CITIZEN-0.5 12T 8NR 390.144A 2.11P 12NC
Geometry CITIZEN-0.5 Coil Length 15.4 in
Nr of Tubes per Row 12 Fin Pitch 2.11 mm
Nr of Rows 8 Nr of Circuits 12 Tube Shape Circular
Capacity 5.494 ton(ref.)
Sensible Capacity 2.461 ton(ref.)
Latent Capacity 3.032 ton(ref.)
Sensible/Total Capacity Ratio 0.4480
Quantity of Produced Water 15.24 kg/h
Exchange Surface 27.99 m²
Global Exchange Coefficient 23 W kg/(m² kJ)
DHML 29.95 kJ / kg
Fins Material / Tubes Material Aluminium / Copper
Fin Thickness 0.1300 mm
Coil Internal Volume 4.0 l
Tubes External Diameter 12.7 mm
Tubes Internal Diameter 11.7 mm
Number of skipped tube 0
AIR SIDE
Atmospheric Pressure / Altitude 1.01 / 0.00 bar A / m
Volumetric Air Flow 800.0 cft/min
Mass Air Flow 1547 kg/h
Face Velocity on the Coil 500 ft/min
Inlet Air Density 1.14 kg/m³
Inlet Air Temperature 33.3 °C
Inlet Wet Bulb Temperature 26.70 °C
Inlet Air Specific Humidity 19.60 g/kg DA
Inlet Air Enthalpy 83.62 kJ / kg
Outlet Air Temperature 14.0 °C
Outlet Air Relative Humidity 97.68 %
Outlet Air Specific Humidity 9.70 g/kg DA
Outlet Air Enthalpy 38.64 kJ / kg
Pressure Drop 1.8071 inH2O
Partial Exchange Coefficient 58 W/(m² K)
Fouling Factor 0.000000 (m² K)/W
Frost thickness 0.00 mm
FLUID SIDE
Fluid WATER (1 bar A)
Volumetric Fluid Flow 13.3 Gal/min
Mass Fluid Flow 3012 kg/h
Fluid Velocity 2.13 ft/s
Inlet Fluid Temperature 6.7 °C
Outlet Fluid Temperature 12.2 °C
Total Pressure Drop Fluid Side 1.868 ftH2O
Partial Exchange Coefficient 2592 W/(m² K)
Fouling Factor 0.0000 (ftq h °F)/Btu