CB 1
CB 1
380 KV CB Page 1 of 1
Panel No: AA05 Equip. No.: GENERATOR TRF 07AT Dwg. Ref.:
2. Timing Test
Test equipment: PME – 500 – TR
R (msec) Y (msec) B (msec) ACCEPTANCE
CLOSING TIME 51.0 50.7 50.6 Yes No
OPEINING TIME COIL 1 17 16.9 16.8 Yes No
OPEINING TIME COIL 2 16.9 16.7 16.5 Yes No
4. Equipment Used
DATE: 12/11/2024
TESTING ENGINEER SEC- Engineer