Engdes
Engdes
A 190-m² dwelling unit has typical household loads including one 3phase 3-TR ACU, one 2-HP ACU, two 1.5-Hp ACU, one 1-Hp ACU,
three 3.5-kW bathroom shower heater, one 7-kW range, one 2-kW microwave oven, one 2.5 kW air fryer/cooker, one 1.8-kW washing
machine, one 4-kW clothes dryer, one 1.5-Hp submersible pump, and 1-Hp booster pump. If the service is 3-phase 230 V 3-wire 60
Hz, determine the following:
a) total net computed load
b) minimum size of service entrance conductor (THW) and its conduit (RMC)
c) maximum size of service equipment
d) minimum grounding conductor
Air Conditioning Load
One 3phase 3-TR ACU
1TR=1.5kVA
3TR = 3(1500) = 4500VA
Sub-Total =13700VA
Cooking Loads
2-kW microwave oven =2000VA
2.5 kW air fryer/cooker =2500VA
Sub-total =4500VA
Application of Demand Factor
4500VA(0.75) =3375VA
SERVICE EQUIPMENT
36011+150%(4500)
𝐼𝑊 = √3×230
= 107𝐴 Use 110A, 3P, 240V, MCCB ………………………………..c.
GROUND
Use 1-40 mm2 Cu Ground Wire ………………………………..d.
2. Prepare a schedule of load for a sub-panel board consisting of two 1φ 1.5-Hp water pumps and two 1φ 1-Hp booster pumps if the
available line is 3φ 3-wire 220 V 60 Hz service. Use THHN concentric stranded conductors and Rigid PVC Conduit Sched 40.
PANEL BOARD --------------- LOCATION ----------------
FROM ----------------- SYSTEM VOLTAGE 3-phase, 3 Wire, 230V
CIRCUIT CIRCUIT BREAKER
DESCRIPTION AB BC CA ABC
NUMBER VOLT-AMPERE AT AF POLE CONDUCTOR TYPE OF WIRE GROUND CONDUIT
1 1.5Hp Water Pump 504 10 30 100 2 2-3.5 mm² THWN/THHN 1-5.5 mm² 1/2" ϕ PVC
2 1.5Hp Water Pump 2340 10 30 100 2 2-3.5 mm² THWN/THHN 1-5.5 mm² 1/2" ϕ PVC
3 1Hp Booster Pump 1840 8 20 100 2 2-3.5 mm² THWN/THHN 1-3.5 mm² 1/2" ϕ PVC
4 1Hp Booster Pump 1500 8 20 100 2 2-3.5 mm² THWN/THHN 1-3.5 mm² 1/2" ϕ PVC