Var. I - 2.AXC-EX - 500-6 - 19°-2-PV - (200) - (2.2 - KW) - S - IE3
Var. I - 2.AXC-EX - 500-6 - 19°-2-PV - (200) - (2.2 - KW) - S - IE3
Var. I - 2.AXC-EX - 500-6 - 19°-2-PV - (200) - (2.2 - KW) - S - IE3
Working point
Airflow (Q) 9,646 m³/h
External static pressure (pstat 412 Pa
-p_acc)
Additional pressure drop 0 Pa
(p_acc)
Fan static pressure (pstat) 412 Pa
Dynamic pressure (pd) 112 Pa
Air velocity 13.6 m/s
Total Efficiency (eta) 69 %
Shaft power (P2) 2.03 kW
Max. shaft power (P2max.) 2.46 kW
Impeller angle 19°
FEI (Fan Energy Index, AMCA 1.38
214-21)
Technical Data
Motor form B3
Blades 6 Power diagram
Voltage/frequency 3~400V/50Hz
Nominal motor power 2.20 kW
Poles 2
Nominal motor speed 2,866 rpm
In 4.3 A
Ia/In 8.4
Motor frame size 90L
Protection class motor IP55
ISO-class motor F
Fan weight 95 kg
Fan weight with accessories 114 kg
According to VDE/EN standards, nominal current tolerance can be up to
±10%. For operation with frequency converter use sine filter or EMC-kit.;
The frequency converter must be installed outside of the potentially
explosive atmosphere for operation in hazardous areas!
Documents
Type examination certificate
EU Declaration of conformity (pdf)
Installation and Operating Instructions (Axial fans/Jet fans)
Accessories
311287 MFA-AXC/AM 500 mounting foot 2
308415 EV-EX 500 2
8380 GFL-AR/AXC 500 counter flange 2
36414 REV-3POL/ATEX-11kW R/Y 1
30546 FSD3 AXC spring set 4 ≤168kg 1
AXC-EX 500-6/19°-2-PV
Axial fan of the AXC-EX series suitable for continuous operation in temperatures between -20°C and 60°C. CE mark of
conformity by BSI.
The fans could be used for zones 1 or 2, field of application II, for gases of groups IIA, IIB and H² and temperature classes T1
to T4.
The fans are classified to category 2G. The fans are certified under the no TPS 21 ATEX 085751 0010 X.
Explosion proof marking: II 2G Ex h IIB+H² T4 Gb.
Impeller:
Impellers with profiled blades made of cast aluminum alloy.
Dynamically balanced according to ISO 21940-11 and ISO 14694, balancing quality G6,3
Casing:
Manufactured from hot-dip galvanized sheet steel according to ISO 1461 (or optionally on request in stainless steel 1.4404).
Pre-drilled, rolled Eurovent 1/2 flanges pressed on both sides.
Aluminum anti-spark ring.
Pre-wired terminal box on fan casing IP65 (IEC 60034-5).
PV Version includes bolt-on outlet guide vanes.
Motor:
Ex d three-phase asynchronous motors with squirrel cage rotor.
Protection class IP55 (IEC 60034-5), insulation class F.
The motors are equipped with PTC thermistors for motor protection.
Speed controllable via frequency converter.
Working point
Airflow (Q) 9,646 m³/h
External static pressure (pstat-p_acc) 412 Pa
Additional pressure drop (p_acc) 0 Pa
Fan static pressure (pstat) 412 Pa
Dynamic pressure (pd) 112 Pa
Air velocity 13.6 m/s
Total Efficiency (eta) 69 %
Shaft power (P2) 2.03 kW
Max. shaft power (P2max.) 2.46 kW
Impeller angle 19°
FEI (Fan Energy Index, AMCA 214-21) 1.38
Technical Data
Motor form B3
Blades 6
Voltage/frequency 3~400V/50Hz
Nominal motor power 2.20 kW
Poles 2
Nominal motor speed 2,866 rpm
In 4.3 A
Ia/In 8.4
Motor frame size 90L
Protection class motor IP55
ISO-class motor F
Fan weight 95 kg
Fan weight with accessories 114 kg
Front
Left
Power diagram
Efficiency diagram