IDNetbroS1410 A4
IDNetbroS1410 A4
IDNet� Analogue
Addressable Devices
Features General
• Supported by SIMPLEX 4100U/ES Series CIE IDNet communication is provided by the SIMPLEX
4100U/ES Control and Indicating Equipment (CIE)
• CIE displays device location and status and is the next generation of addressable device
• Individually addressable communications communications, improving upon the original
over a single cable pair MAPNET II communications protocol. The IDNet
protocol and hardware enhancements support
• Zone adaptor modules provide addressable
interface to conventional circuits up to 250 addressable devices on a single cable
pair and can support additional device types and
• IDNet digital protocol communications different operations.
• Convenient DIP switch address selection IDNet communicating devices individually
• Supports up to 250 addressable devices per annunciate identity and accurate status to the
loop 4100U/ES CIE Applications include monitoring of
• Range of enclosures to suit, with a covers sprinkler pressure switches, flow switches and
incorporating an LED viewing window valve monitor devices, interfacing of conventional
detectors and addressable monitoring and control
(voltage free) for AS 1668 applications.
The majority of IDNet devices are loop powered
requiring a single cable pair for operation by the
CIE.
4090-9002 Relay IAM (Individual Addressable Module)
4090-9120 Six Point I/O Module with T-Sense Inputs & Relay Outputs Module
The 4090-9120 allows 4100U/ES IDNet Technical Specification
communication channel to monitor four Comms Power1 24 to 40Vdc w/data
T-sense input circuits and control two Operating Voltage 18 to 32Vdc
output relays from a single module Operating Current 30mA@24Vdc
requiring a single address. Power is Contact Ratings SPDT
supplied by a separate (listed) 24Vdc Non-power limited 0.5A @120VAC2
power supply. The input circuits and 0.25A@120VAC3
output relay operation are controlled Power limited 2A@30Vdc2
independently and may be disabled 1A@30Vdc3
separately. Point association is determined Supervision Resistor 6k8 Ohm 0.5W
at the 4100U/ES host panel. Each of the Current Ltd Operation 1k8/4k7 0.5W
four input circuits are monitored via an Input N/O, dry contacts
end-of-line resistor and can differentiate LED Output 24Vdc (ext. PSU)
between a short circuit contact closure Dimensions (HWD) 105x105x35 mm
and a current limited contact closure. Two Ambient Temperature 0 to +49°C
input supervision resistors are required per Relative Humidity 10% to 90% (n/c)
T-sense input. Part Number 4090-9120
1. IDNet communications with data
2. Resistive Load 3. Inductive Load
Note: 4 wire device; requires separate 24Vdc and IDNet
communication loop