Directions: Solve and show solutions of the given problems.
Submit solution in pdf file.
1. A 3-phase, 16-pole alternator has the following data number
of slots = 192, conductor/slot = 8, number of parallel paths = 2, coil span = 160⁰, speed of alternator = 275 rpm, flux per pole = 55 mWb. Calculate the line voltage. (10 points)
2. The armature of a three-phase eight-pole 900 rpm synchronous
generator is wye-connected, and has 72 slots with 10 conductors per slot. The winding factor is 0.96. if 2400 V is measured across the line, determine the flux per pole. (10 points)
3. A winding is short pitched by 30 electrical degrees. Its pitch
factor is _____.(5 points)
4. A 90-slot stator has a 3-phase, six-pole winding. Each coil
spans from slot 1 to sot 14. Calculate the pitch factor. (5 points)
5. A 90-slot stator has a 3-phase, six-pole winding. Each coil
spans from slot 1 to slot 14. Calculate the distribution factor. (5 points)
6. A wye-connected alternator is rated 1000 kVA, 13.5 kV. The
armature effective resistance and synchronous reactance are 1.5 ohms and 30 ohms respectively per phase. Determine the percentage regulation for a load of 1280 kW at a pf of 0.80 lagging. (10 points)