Electrical Drawings

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

LEGEND

MARK DESCRIPTION

A B C D E F G A B C D E F G LF-(A) 50W LIGHTING OUTLET (LO)

1S-(A) SWITCH, ONE GANG

2S-(AB) SWITCH, TWO GANG

3S-(ABC) SWITCH, THREE GANG


1 1

LF-H LF-H
S3W-(A) SWITCH, THREE WAY

DUPLEX CONVENIENCE
CO
OUTLET, GROUNDING TYPE
2 2
DUPLEX CONVENIENCE OUTLET,
1S-EH 1S-EH WP GROUNDING TYPE, WEATHER
PROOF
LF-F 1S-G 1S-G LF-F
LF-G LF-E LF-E LF-G DUPLEX CONVENIENCE OUTLET,
LF-O LF-O C
GROUNDING TYPE, AT COUNTER
3 1S-F 1S-F 3
1S-O LF-P LF-P 1S-O DUPLEX CONVENIENCE OUTLET,
LF-N LF-N REF
GROUNDING TYPE, FOR REF.
LF-D LF-D
1S-P 1S-P DUPLEX CONVENIENCE OUTLET,
3SW-J 3SW-J R
1S-I 1S-I GROUNDING TYPE, FOR RANGE
4 4 LF-L
1S-N 1S-N
DUPLEX CONVENIENCE OUTLET,
ACU
3SW-JL 3SW-J GROUNDING TYPE, FOR AIRCON
LF-D LF-D
2S-LM 2S-LM

5 5 M KWHR SERVICE METER


LF-J LF-J

CIRCUIT BREAKER, PLUG-IN TYPE


6 6 LF-L
LF-L

LF-C STAIRS STAIRS


LF-C LIGHTING & POWER PANELBOARD,
1S-K 1S-K
NEMA1 ENCLOSURE, FLUSH TYPE,
LPP DEADFRONT, 250V, 1PHASE
LF-K LF-K
2S-AB 2S-CD 2S-CD 2S-AB RJ11 TELEPHONE OUTLET
7 M M 7 TEL
LF-A LF-B LF-B LF-M LF-M
LF-A
STANDARD CATV OUTLET
CATV

SERVICE ENTRANCE SERVICE ENTRANCE

8 8

NOTE: ARCHITECTURAL PLANS SHALL


PREVAIL OVERALL ENGINEERING
PLANS W/ REGARDS TO DIMENSION
AND SIZES. ANY DISCREPANCIES
A GROUND FLOOR LIGHTING LAYOUT B SECOND FLOOR LIGHTING LAYOUT FOUND HEREIN, SHALL VERIFY W/
THE ARCHITECT.
E1 01 SCALE 1:60 MTS E1 02 SCALE 1:60 MTS
PROJECT TITLE : OWNER : SHEET CONTENTS : RA 545 ART. 2 SEC. 25 (4) SHEET NUMBER
A GROUND FLOOR LIGHTING LAYOUT G ALL DESIGN, DRAWINGS, SPECIFICATIONS, AND COPIES
ARTHURO C. SECUYA CHARITO OLMOGUEZ-CLARO THEREOF, PREPARED AND FURNISHED BY THE ARCHITECT IN
A R C H I T E C T E N G I N E E R B SECOND FLOOR LIGHTING LAYOUT H CONNECTION WITH THE PROJECT, ARE INSTRUMENTS OF

E-1
PROFESSIONAL SERVICE. AS INSTRUMENTS OF
PRC REG. NO.:
12151 PRC REG. NO.:
4024 PROPOSED TOWNHOUSE DEVELOPMENT MARIA AURORA TANJANGCO JAUCIAN C I PROFESSIONAL SERVICE, THEY ARE THE PROPERTY OF THE
PTR NO. : PTR NO. : ARCHITECT WHETHER THE WORK FOR WHICH THEY ARE
1748048C 1762323
D J MADE MAY BE EXECUTED OR NOT, AND ARE NOT TO BE
DATE :
01/15/19 DATE :
01/09/19 REPRODUCED OR USED ON OTHER WORK EXCEPT BY THE
LOCATION : ADDRESS : E K WRITTEN AGREEMENT WITH THE ARCHITECT.
PLACE :
DAVAO CITY PLACE :
DAVAO CITY BLOCK 2, LOT 5, DAPDAP STREET, PALMERA HOMES, 2 SUNRISE HILL ST., NEW MANILA ROLLING HILLS,
T.I.N. :
168-290-455 T.I.N. :
415-046-432-000 BRGY. STA MONICA,NOVALICHES, QUEZON CITY BARANGAY DAMAYAN LAGI, QUEZON CITY F L
LEGEND
MARK DESCRIPTION

A B C D E F G A B C D E F G LF-(A) 50W LIGHTING OUTLET (LO)

1S-(A) SWITCH, ONE GANG

2S-(AB) SWITCH, TWO GANG

1 1 3S-(ABC) SWITCH, THREE GANG

WM WM S3W-(A) SWITCH, THREE WAY


PB-A PB-B
7 7

DUPLEX CONVENIENCE
CO
WP WP OUTLET, GROUNDING TYPE
2 2
WH WH CO
WH
CO CO
WH
CO DUPLEX CONVENIENCE OUTLET,
RO RO
PB-A PB-B PB-A PB-B
WP GROUNDING TYPE, WEATHER
5 5 9 9
PB-A
11
PB-B
11
PB-A
10 PB-A
12
PB-B
12
PB-B
10 PROOF
CO CO
DUPLEX CONVENIENCE OUTLET,
C
3 3 GROUNDING TYPE, AT COUNTER
CHO CHO

CO DUPLEX CONVENIENCE OUTLET,


CO REF
REF REF
CO CO GROUNDING TYPE, FOR REF.
PB-A PB-B
6 6

DUPLEX CONVENIENCE OUTLET,


CO CO R
4 4 GROUNDING TYPE, FOR RANGE
DN DN
PB-A
3
PB-B
3 DUPLEX CONVENIENCE OUTLET,
CO CO
ACU
GROUNDING TYPE, FOR AIRCON

CO CO
5 5 M KWHR SERVICE METER
CO CO PB-A
4
PB-B
4

6 6 CO CO CIRCUIT BREAKER, PLUG-IN TYPE

LIGHTING & POWER PANELBOARD,


WP WP NEMA1 ENCLOSURE, FLUSH TYPE,
CO CO LPP DEADFRONT, 250V, 1PHASE
CO CO
PB-A PB-B
8 8

RJ11 TELEPHONE OUTLET


7 M M 7 TEL
PB-A PB-B
ACU 13

WH
13
ACU
WH STANDARD CATV OUTLET
CATV

SERVICE ENTRANCE SERVICE ENTRANCE

8 8

NOTE: ARCHITECTURAL PLANS SHALL


PREVAIL OVERALL ENGINEERING
PLANS W/ REGARDS TO DIMENSION
AND SIZES. ANY DISCREPANCIES
A GROUND FLOOR POWER LAYOUT B SECOND FLOOR POWER LAYOUT FOUND HEREIN, SHALL VERIFY W/
THE ARCHITECT.
E2 01 SCALE 1:60 MTS E2 02 SCALE 1:60 MTS
PROJECT TITLE : OWNER : SHEET CONTENTS : RA 545 ART. 2 SEC. 25 (4) SHEET NUMBER
A GROUND FLOOR POWER LAYOUT G ALL DESIGN, DRAWINGS, SPECIFICATIONS, AND COPIES
ARTHURO C. SECUYA CHARITO OLMOGUEZ-CLARO THEREOF, PREPARED AND FURNISHED BY THE ARCHITECT IN
A R C H I T E C T E N G I N E E R B SECOND FLOOR POWER LAYOUT H CONNECTION WITH THE PROJECT, ARE INSTRUMENTS OF

E-2
PROFESSIONAL SERVICE. AS INSTRUMENTS OF
PRC REG. NO.:
12151 PRC REG. NO.:
4024 PROPOSED TOWNHOUSE DEVELOPMENT MARIA AURORA TANJANGCO JAUCIAN C I PROFESSIONAL SERVICE, THEY ARE THE PROPERTY OF THE
PTR NO. : PTR NO. : ARCHITECT WHETHER THE WORK FOR WHICH THEY ARE
1748048C 1762323
D J MADE MAY BE EXECUTED OR NOT, AND ARE NOT TO BE
DATE :
01/15/19 DATE :
01/09/19 REPRODUCED OR USED ON OTHER WORK EXCEPT BY THE
LOCATION : ADDRESS : E K WRITTEN AGREEMENT WITH THE ARCHITECT.
PLACE :
DAVAO CITY PLACE :
DAVAO CITY BLOCK 2, LOT 5, DAPDAP STREET, PALMERA HOMES, 2 SUNRISE HILL ST., NEW MANILA ROLLING HILLS,
T.I.N. :
168-290-455 T.I.N. :
415-046-432-000 BRGY. STA MONICA,NOVALICHES, QUEZON CITY BARANGAY DAMAYAN LAGI, QUEZON CITY F L
LEGEND

USE: 1-25 KVA ; 1Ø ; 60HZ ; 7620/230VOLTS


UNIT 1 MARK DESCRIPTION
DISTRIBUTION TRANSFORMER
CT
LF-(A) 50W LIGHTING OUTLET (LO)

USE: 2 - 30.0mm2 & 1 - 14.0mm2 THW COPPER WIRES


SERVICE ENTRANCE
INSIDE 50 mm Ø RSC PIPE SWITCH, ONE GANG
1S-(A)
M

2S-(AB) SWITCH, TWO GANG

PBA
3S-(ABC) SWITCH, THREE GANG
100 AT/2P, 230V

20 A 20 A
LIGHTING OUTLET 1 2 LIGHTING OUTLET S3W-(A) SWITCH, THREE WAY
20 A 20 A
CONVENIENCE OUTLET 3 4 CONVENIENCE OUTLET DUPLEX CONVENIENCE
CO
30 A 30 A OUTLET, GROUNDING TYPE
RANGE 5 6 REF. OUTLET
DUPLEX CONVENIENCE OUTLET,
30 A 30 A WP GROUNDING TYPE, WEATHER
WASHING MACHINE 7 8 ACU 1HP PROOF
30 A 30 A
DUPLEX CONVENIENCE OUTLET,
ACU 1HP 9 10 ACU 1HP C VICINITY MAP C
GROUNDING TYPE, AT COUNTER
30 A
E3 03 NOT TO SCALE
WATER HEATER 11 12 SPARE DUPLEX CONVENIENCE OUTLET,
REF
1. ALL ELECTRICAL WORKS HEREIN SHALL BE EXECUTED IN ACCORDANCE GROUNDING TYPE, FOR REF.
WITH THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC), THE
GROUND NEW ELECTRICAL ENGINEERING LAW (R.A. 7920), LAWS AND ORDINANCES OF DUPLEX CONVENIENCE OUTLET,
THE LOCAL GOVERNMENT UNIT AND RULES AND REGULATIONS OF THE R
LOCAL ELECTRICAL POWER UTILITY COMPANY. GROUNDING TYPE, FOR RANGE
2. ALL WIRING SHALL BE IN INTERMEDIATE METALLIC CONDUIT (IMC) FOR
THE FEEDERLINE, ELECTRICAL METALLIC TUBING (EMT) FOR LOAD SIDE DUPLEX CONVENIENCE OUTLET,
EMBEDDED IN FLOOR AND EXPOSED WIRING AND UNPLASTICIZED
ACU
GROUNDING TYPE, FOR AIRCON
POLYVINYL CHLORIDE (PVC) FOR AUXILLARY CONDUITS. UNLESS
OTHERWISE SPECIFIED.

3. PANELBOARDS AND OVERCURRENT PROTECTION ENCLOSURES SHALL BE M KWHR SERVICE METER


NEMA-1 FOR INDOOR USE AND NEMA-3R FOR OUTDOOR USE. UNLESS
OTHERWISE SPECIFIED.

4. POWER SERVICE ENTRANCE TO THE BUILDING SHALL BE 230V, 60HZ, THREE CIRCUIT BREAKER, PLUG-IN TYPE
PHASE, 3-WIRE + GROUND SYSTEM.

UNIT 2 5. ALL WIRING INSTALLATION SHALL BE CONCEALED FROM VIEW. LIGHTING & POWER PANELBOARD,
NEMA1 ENCLOSURE, FLUSH TYPE,
USE: 1-25 KVA ; 1Ø ; 60HZ ; 7620/230VOLTS 6. UNLESS OTHERWISE INDICATED, BRANCH CIRCUIT CONDUCTORS SHALL NOT
DISTRIBUTION TRANSFORMER BE SMALLER THAN 2.0mm DIAMETER, SOLID COPPER, MEDIUM DRAWN, THHN
LPP DEADFRONT, 250V, 1PHASE
CT TYPE, 600 VOLTS INSULATIONS.

7. MINIMUM SIZE OF CONDUIT SHALL BE 20mm DIA. FOR RSC AND uPVC. 15mm RJ11 TELEPHONE OUTLET
2 2
TEL
USE: 2 - 30.0mm & 1 - 14.0mm THW COPPER WIRES DIA. FOR EMT.
SERVICE ENTRANCE
INSIDE 50 mm Ø RSC PIPE
8. NO BRANCH CIRCUIT CONDUCTORS SHALL BE LOADED MORE THAN 80% OF
M ITS RATED AMPACITY. STANDARD CATV OUTLET
CATV
9. BOXED SHALL BE PRESSED STEEL WITH REQUIRED THICKNESS IN
CONFORMANCE WITH THE LATEST EDITION OF THE PEC.

10.MOUNTING HEIGHT OF PANEL AND DEVICES ARE AS FOLLOWS; (FROM


PBA FLOOR FINISH TO CENTER OF UNIT)

100 AT/2P, 230V A. WALL SWITCHES 1400 mm


B. WALL CONVENIENCE OUTLETS 300 mm
20 A C. COUNTER-TOP OUTLETS VERIFY ARCHITECT
20 A
D. TELEPHONE/CATV OUTLET VERIFY ARCHITECT
LIGHTING OUTLET 1 2 LIGHTING OUTLET E. EMERGENCY LIGHT OUTLET VERIFY ARCHITECT
F. kWHr METER 1830 mm
20 A 20 A
G. PANELBOARD 1830 mm
CONVENIENCE OUTLET 3 4 CONVENIENCE OUTLET
11.GROUND ROD OF 15mm DIA. SHOULD BE CONNECTED BY GROUND
30 A 30 A CONNECTOR 14.0mm2 (MAXIMUM) TO THE NEUTRAL BAR AT THE METER
RANGE 5 6 REF. OUTLET CENTER.

30 A 30 A 12.GROUND WIRE FROM THE NEUTRAL BAR AT THE METER CENTER SHOULD BE
TAP TO THE BUILDING REINFORCING BAR OF NOT LESS THAN 1/2 INCHES
WASHING MACHINE 7 8 ACU 1HP
DIAMETER LENGTH SHOULD BE MORE THAN 20ft. USE SOLDERLESS
30 A 30 A CONNECTOR FOR EXPOSED CONNECTIONS. THEREMOWELD IN CONCEALED
IN CONCRETE OR EMBEDDED IN CONCRETE.
ACU 1HP 9 10 ACU 1HP
30 A 13. CONDUITS/RACEWAYS SHALL BE ADEQUATELY SUPPORTED AS REQUIRED IN
CONFORMANCE WITH THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL
WATER HEATER 11 12 SPARE CODE (PEC).

14. ONLY LISTED TOOLS, APPLIANCES AND EQUIPMENT COVERED BY PEC ART.
2.50.6.5 AND 2.10.1.8 (EXEMPTION-2) SHALL NOT BE REQUIRED TO BE G.F.C.I
GROUND PROTECTED.

15.DISTRIBUTION PANEL SHALL BE READILY ACCESSIBLE, THAT NO OBSTACLE


SHOULD BLOCK ACCESS TO THE PANEL.

16. THE INSTALLATION SHALL BE DIRECTLY SUPERVISED BY A DULY LICENSED


ELECTRICAL PRACTITIONER IN CONFORMANCE WITH R.A.
NOTE: ARCHITECTURAL PLANS SHALL
PREVAIL OVERALL ENGINEERING
PLANS W/ REGARDS TO DIMENSION
AND SIZES. ANY DISCREPANCIES
A LOAD SCHEDULE & COMPUTATION B RISER DIAGRAM D GENERAL NOTES FOUND HEREIN, SHALL VERIFY W/
THE ARCHITECT.
E3 01 NOT TO SCALE E3 02 NOT TO SCALE E3 04 NOT TO SCALE
PROJECT TITLE : OWNER : SHEET CONTENTS : RA 545 ART. 2 SEC. 25 (4) SHEET NUMBER
A LOAD SCHEDULE & COMPUTATION G ALL DESIGN, DRAWINGS, SPECIFICATIONS, AND COPIES
ARTHURO C. SECUYA CHARITO OLMOGUEZ-CLARO THEREOF, PREPARED AND FURNISHED BY THE ARCHITECT IN
A R C H I T E C T E N G I N E E R B RISER DIAGRAM H CONNECTION WITH THE PROJECT, ARE INSTRUMENTS OF

E-3
PROFESSIONAL SERVICE. AS INSTRUMENTS OF
PRC REG. NO.:
12151 PRC REG. NO.:
4024 PROPOSED TOWNHOUSE DEVELOPMENT MARIA AURORA TANJANGCO JAUCIAN C VICINITY MAP PROFESSIONAL SERVICE, THEY ARE THE PROPERTY OF THE
I
ARCHITECT WHETHER THE WORK FOR WHICH THEY ARE
PTR NO. :
1748048C PTR NO. :
1762323
D GENERAL NOTES MADE MAY BE EXECUTED OR NOT, AND ARE NOT TO BE
DATE :
01/15/19 DATE :
01/09/19
J REPRODUCED OR USED ON OTHER WORK EXCEPT BY THE
LOCATION : ADDRESS : E WRITTEN AGREEMENT WITH THE ARCHITECT.
PLACE :
DAVAO CITY PLACE :
DAVAO CITY BLOCK 2, LOT 5, DAPDAP STREET, PALMERA HOMES, 2 SUNRISE HILL ST., NEW MANILA ROLLING HILLS, K
T.I.N. :
168-290-455 T.I.N. :
415-046-432-000 BRGY. STA MONICA,NOVALICHES, QUEZON CITY BARANGAY DAMAYAN LAGI, QUEZON CITY F L
230V Zu Zse

Source
PANEL ACU BLANK PLATE
BOARD
IMPEDANCE DIAGRAM ELECTRIC
METER

UTILITY DISTRIBUTION LINE: SERVICE ENTRANCE: SWITHCES


COUNTER TOP

90.00
89.77
ASSUME SIZE,30.0mm² Copper Wire, 48.20ft. 30.0mm² Copper Wire @ 30.32ft.

15.00
CONVENIENCE OUTLET

80.12

90.00
89.77
Ru = 0.0245Ω/100ft. Rse = 0.0245Ω/100ft.

80.12
65.00
Xu = 0.00305Ω/100ft. Xse = 0.00305Ω/100ft.

WEATHER PROOF CONVENIENCE


RESISTANCE CALCULATION: OUTLET OUTLET

Utility Distribution Line, 48.2 ft. Service Entrance, 30.32 ft.


Ru Rse Rtotal

15.00
Rse = 0.0245 Ω x 30.32 ft. = FFL

25.00
Ru = 0.0245 Ω x 48.20 ft. 100 ft. FINISH
100 ft. 0.01181 Ω 0.0074 Ω 0.0192 Ω GROUND LINE
Rse = 0.0074Ω
Ru = 0.01181 Ω
Total Resistance: RESISTANCE DIAGRAM
Rt = Ru + Rse C MOUNTING HEIGHT DETAILS
Rt = 0.01181 Ω + 0.0074 Ω E4 03 NOT TO SCALE
Rt = 0.0192 Ω

REACTANCE CALCULATION:
Utility Distribution Line, 48.2 ft. Service Entrance, 30.32 ft. Xu Xse Xtotal
Xu = 0.00305 Ω x 48.2 ft. Xse = 0.00305 Ω x 30.32 ft. =
100 ft. 100 ft. 0.00147 Ω 0.00092 Ω 0.0024 Ω SERVICE DROP SERVICE DROP
Xu = 0.00147 Ω Xse = 0.00092 Ω SPOIL INSULATOR

Total Resistance: REACTANCE DIAGRAM


SERVICE
Xt = Xu + Xse ENTRANCE CAP

Xt = 0.00147 Ω + 0.00092 Ω
Xt = 0.0024 Ω

SHOULD BE 6" - 12" FROM SPOOL PACK


PIPE STRAP
COMPUTE FOR SHORT CIRCUIT CURRENT: DRIP LOOP
(at least 1-ft)
IMPEDANCE CALCULATION: Isc = V
Zt = √(Rt)² + (Xt)² Zt PVC CONDUIT
FOR CATV
RIGID STEEL CONDUIT
(3/4" ∅ min.)
(1/2" ∅ min.)
Zt = √(0.0192)² + (0.0024)² Isc = 230 PLAIN SMOOTH FIN.
Zt = 0.0193 Ω 0.0193 PIPE STRAP
RIGID STEEL CONDUIT
Isc = 11,917.10 Amps - Symmetrical Short Circuit Current (3/4" ∅ min.)

HEIGHT DEPENDS ON STANDARD VERTICAL CLEARANCE


PVC CONDUIT
USE: 15,000Amps / 15KAIC, Minimum Interrupting FOR TEL.
(1/2" ∅ min.)
Molded Case Circuit Breaker BUSHING REDUCER
W/ LOCK NUT

A SHORT CIRCUIT CURRENT CALCULATION


E4 01 NOT TO SCALE

METER BASE
SERVICE ENTRANCE
SANDBLAST FINISH
230V, 2-WIRE, 60HZ
VOLTAGE DROP CALCULATION

2ND FLOOR LEVEL


MDP CO

PHASE WIRE

CONCRETE PEDESTAL, 0.2 m x 0.2 m

CONCRETE PEDESTAL, 0.2 m x 0.2 m


CKT. NO. DESCRIPTION K L I VD %VD

5ft - 6ft
1Ø 3Ø CM SET

1 SERVICE ENTRANCE 1 12 30.32 86.78 66,360 1 0.476 0.21


30.32 ft. 45.17 ft. AREA 0.04 SQ. M.
2 CONVENIENCE OUTLET 1 12 45.17 4.70 6,530 1 0.39 0.17
0.20
0.866 0.38

COMPUTATION: WIRE SIZE: 3.5 mm² THHN Copper Wire COMPUTATION:

0.20
WIRE SIZE: 30.0 mm² THW Copper Wire
K: 12 (Copper Wire) K: 12 (Copper Wire) VD = KxIxL
VD = KxIxL This computed Voltage Drop of Proposed Retail
L: 60.32 ft. L: 45.17 ft. CM
CM Commercial with Warehouse Building with total of
I: 86.78 Amps I: 4.70 Amps
0.38 percentage (%) of Voltage drop meet the
CM: 6,530 CROSS SECTIONAL VIEW
CM: 66,360
VD = (12) (30.32) (86.78) VD = (12) (45.17) (4.70) required allowable VD of Philippine Electrical Code
66,360 6,530 (PEC).

VD = 0.476V VD = 0.39 V

B VOLTAGE DROP CALCULATION D SERVICE DETAIL


E4 02 NOT TO SCALE E4 04 SCALE 1:10 MTS
PROJECT TITLE : OWNER : SHEET CONTENTS : RA 545 ART. 2 SEC. 25 (4) SHEET NUMBER
SHORT CIRCUIT CURRENT
A G ALL DESIGN, DRAWINGS, SPECIFICATIONS, AND COPIES
ARTHURO C. SECUYA CHARITO OLMOGUEZ-CLARO CALCULATION
THEREOF, PREPARED AND FURNISHED BY THE ARCHITECT IN
A R C H I T E C T E N G I N E E R B VOLTAGE DROP CALCULATION H CONNECTION WITH THE PROJECT, ARE INSTRUMENTS OF

E-4
PROFESSIONAL SERVICE. AS INSTRUMENTS OF
PRC REG. NO.:
12151 PRC REG. NO.:
4024 PROPOSED TOWNHOUSE DEVELOPMENT MARIA AURORA TANJANGCO JAUCIAN C SERVICE DETAIL PROFESSIONAL SERVICE, THEY ARE THE PROPERTY OF THE
I
ARCHITECT WHETHER THE WORK FOR WHICH THEY ARE
PTR NO. :
1748048C PTR NO. :
1762323
D MADE MAY BE EXECUTED OR NOT, AND ARE NOT TO BE
DATE :
01/15/19 DATE :
01/09/19
J REPRODUCED OR USED ON OTHER WORK EXCEPT BY THE
LOCATION : ADDRESS : E WRITTEN AGREEMENT WITH THE ARCHITECT.
PLACE :
DAVAO CITY PLACE :
DAVAO CITY BLOCK 2, LOT 5, DAPDAP STREET, PALMERA HOMES, 2 SUNRISE HILL ST., NEW MANILA ROLLING HILLS, K
T.I.N. :
168-290-455 T.I.N. :
415-046-432-000 BRGY. STA MONICA,NOVALICHES, QUEZON CITY BARANGAY DAMAYAN LAGI, QUEZON CITY F L