Columns
Columns
AR 3151/D
BUILDING TECHNOLOGY 3
REINFORCED CONCRETE
COLUMNS
• Columns are rigid, relatively slender
structural members designed primarily
to support axial compressive loads
applied to the ends of the members.
• There may be short columns or long
columns.
• Concrete columns are designed to act
together with vertical and lateral
reinforcement in resisting applied forces.
Factors affecting the Structures
• Lateral Loads (Horizontal Load)
• Loads ü Wind Load
• Gravity Loads ü Earthquake
(Vertical Load) ü Tsunami
ü Dead load
ü Live Load
Structural Analysis
• Mathematics, Physics, Materials Engineering
Design equations, Softwares, Models, Analysis, Spreedsheet, Design
table
Load Transfer
q Roof - Column - Footing - Ground
ü Structural Elements
• Columns, Beams, Slab, Roof, Braces, Structural Walls, Shear walls,
Purlins, Girts, Rafters
• How much reinforcements
• Sizes of structural elements
REINFORCED CONCRETE
COLUMNS
1. Tied Columns.
• These are columns with longitudinal bars and lateral
ties.
• The ratio of the effective cross-sectional area of vertical
reinforcement to the gross column area should not be less than 1%
nor more than 8%, and should consist of at least 4 bars of a
minimum size of #5.
TYPES OF RC COLUMNS
Lateral tiles shall be at least 3/8” (10 mm) diameter and shall be
spaced apart not over than 16 bar diameters, 48 tie diameters, or
the least dimension of the column.
Where there are more than four vertical bars, additional ties should
be provided so that every longitudinal bar will be firmly held in its
designed position. The reinforcement for tied columns shall be
protected by a covering of concrete, cast monolithically with the core,
of at least 1-1/2” (38 mm) thickness.
2. Spiral Columns.
• These are columns with
longitudinal bars and closely
spaced continuous spiral
hooping.
• For spiral columns, the ratio of
the area of the vertical
reinforcement to the gross
column area shall not less than
1% nor more than 8%.
• The minimum number of bars
shall 6, and the minimum bar
size shall #5.
• The spiral reinforcement, with min
size of 3/8” shall consist of evenly
spaced continuous spirals held firmly
in place by at least three vertical
spacer bars.
• The center to center spacing of the
spirals shall not exceed 3” (75 mm)
nor be less than 1-3/8” (35 mm) or 1-
1/2 times the maximum size of the
coarse aggregate. Protective covering
for the column reinforcement shall
not be less than 1-1/2” (38 mm).
3. Composite Columns – where
structural steel columns are
embedded into the concrete core of
a spiral column.
Diagram: Centra at
Metropark, Iselin,
New Jersey,
1997–2011, Kohn
Pederson Fox
Associates