PB-1106 - 19-09 MX250 Series Microprocessor Controller

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Zenith MX250
Entelli-Switch Microprocessor Controller

Introduction
With more powerful integrated features, the Entelli-Switch 250 microprocessor, standard with the entire ABB Zenith ZTS product
family, offers expanded programmability and field adaptability. This premium controller is designed for use in specification-grade
applications. As an embedded digital controller, the Entelli-Switch 250 seriesoffers high reliability and ease of unattended operation
across a range of applications.

Available in ALL transfer modes:


• Open, Closed, Delayed and Bypas


Features and Benefits
• User-friendly programmable engine exerciser, used for the
engine generator with or without load, at any interval in a one-
year period
• Operating voltages available in a single controller for most
domestic and international applications
• Real-time display of ATS status, including active timer(s)
• Multiple levels of user-defined password protection
• Serial communications allowing connectivity with other ATS’s,
paralleling switchgear and SCADA systems
• Time-tested synchronous logic automatically measures phase
angle and frequency allowing disturbance-free transfer
• Unsurpassed statistical ATS/System monitoring available in
real-time
• T3/W3 elevator pre-signal timer and output contacts.
Automatically bypassed if the selected source fails,
minimizing time an elevator is without power
• Universal Motor Disconnect (UMD) sends a pre-signal, post-
signal or both to any motor control center. Not bypassed in an
outage, the UMD ensures safety in the event of a single phase
loss.
• Voltage unbalance detection standard
• Optically isolated inputs and outputs
• Includes all standard Zenith MX150 microprocessor controller
features


User-Friendly Operation
LEDs are used in a recognizable line configuration for continuous monitoring of switch position. A 4x20 character LCD
display shows source availability, exercise time delay operation and system source condition. A new simplified adjustment is
featured for voltage, frequency and time delay settings.

The control operates off a close differential 3-phase under-voltage sensing of Source 1 (normal), factory standard setting
90% pickup, 80% dropout; underfrequency sensing of Source 1 factory setting 95% pickup; voltage and frequency sensing of
Source 2 (emergency), factory standard setting 90% pickup voltage, 95% pickup frequency. All factory settings are operator
adjustable (see table on reverse side).

A test is standard (fast test/load/no load) to simulate Source 1 failure - automatically bypassed should Source 2 fail.

Fully Approved
• UL and CSA listed
• Ringing wave immunity per IEEE 472 (ANSI C37.90A)
• Conducted and Radiated Emissions per EN55022 Class B (CISPR 22) (Exceeds
EN55011 & MILSTD 461 Class 3)
Source 1 LED (Green)
• ESD Immunity test per EN61000-4-2 Class B (Level 4)
indicates Source 1 is
• Radiated RF, electromagnetic field immunity test per EN61000-4-3
acceptable for use
(ENV50140) 10v/m
• Electrical fast transient/burst immunity test for EN61000-4-4
• Surge immunity test per EN61000-4-5 IEEE C62.41 (1.2 x 50µs, 0.5 to 4 kV)
• Conducted immunity test per EN61000-4-6 (ENV50141)
• Voltage dips and interruption immunity EN61000-4-11
LCD Screen


Control Setting Ranges

MX250 Current Time, Day and


Factory Date of Display
Control Feature Function Range Setting
Fail 75-98% 80%
S1 Line Sensing – Under-voltage Restore 85-100% 90%
Fail 88-98% 90%
S1 Line Sensing – Under-frequency Restore 90-100% 95%
Fail 75-98% 80%
S2 Line Sensing – Under-voltage Restore 85-100% 90% Menus (MORE, CFG, TEST)
Fail 88-98%* 90%
S2 Line Sensing – Under-frequency Restore 90-100% 95%
Time Delay S2 Start P1 Timer 0-10 seconds 3 seconds
S2 Stop Delay U Timer 0-60 minutes 5 minutes
Time Delay S2 Stable Timer W Timer 0-5 minutes 1 second
30
Time Delay S1 Stable Timer T Timer 0-60 minutes minutes
Universal Motor Disconnect** UMD Timer 0-60 seconds 5 seconds
T3/W3 20
Elevator Transfer Presignal** Timers 0-60 seconds seconds
DT, DW 1 second-10
Delay Transition Time Delays Timers minutes 5 seconds #1 or the word on the LCD
above the key.
The word above the key
changes depending on which
screen is being displayed.

Notes
*2 Hz below restore setting
**Form C Double Throw Contact Output
Source 1 Position LED (Green) Source 2 Position LED (Red)
indicates Power Panel (ATS) is indicates Power Panel (ATS) is
closed to Source 1 position closed to Source 2 position
Source 2 (Red)
indicates Source 2 is
acceptable for use

Exercise Event
"Impending"

SET Menu

Keypad

#4 or the word on the LCD


above the key.
The word above the key
changes depending on which
screen is being displayed.

#2 or the word on the LCD #3 or the word on the LCD


above the key. above the key.
The word above the key The word above the key
changes depending on which changes depending on
screen is being displayed. which screen is being
displayed.

ABB Zenith Controls, Inc.


305 Gregson Drive
Cary, NC 27511
24-hour support:
ABB Technical Services
+1 (800) 637-1738

PB-1106, 19-09

© Copyright 2019 ABB. All rights reserved.


Specifications subject to change without notice.