Fahu Datasheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

Saved date 18-10-2024 Printed out by MSD_21

Offer nr. 6895-24


Revision
OC nr.
Serial nr.
EUROVENT ENERGY LABELS
WINTER SUMMER
Customer BLUEGATE
Project reference Habib Beirut @ Abu Dhabi
Unit reference FAHU-01 OP2
Quantity 1
Packing type With protective film
Altitude mamsl 0
Outdoor design temperature -5.0°C/80%U.R. / +46.0°C/50%U.R
Temp. MIN/MAX unit -40.0°C/100%U.R. / +50.0°C/80%U.R. DUBAI INTL (United Arab Emirates)

UNIT SIZE: 23MK-60-029039 Applications Standard


SUPPLY AIR FLOW 15377 m³/h RETURN AIR FLOW 0 m³/h
SUPPLY EXTERNAL STATIC PRESSURE 500 Pa RETURN EXTERNAL STATIC PRESSURE // Pa
AIR VELOCITY ACROSS SUPPLY 1.94 m/s AIR VELOCITY ACROSS EXHAUST // m/s
Length 2835 mm
Width 1845 mm
Height 1395 + 135 mm
Inspection side Right
Connection side Right
Drain side Right
Gross dry weight 1143.2 kg
SFPv (clean filters) 1.42 W/l/s
SFPe (mean filters) 1.52 W/l/s
fs-Pref 0.92/0.88
Tot. electrical power 7.50 kW

STRUCTURAL FEATURES ACCESSORIES


Profile 60 mm Al. Anod. Profile insulated No
Corners Nylon black, glass fiber 30% Drainable floor No
Panel 60 mm Sloped drain pan Yes
Insulation Polyurethane foam. 45 kg/mc B2 class Roof material Galv. prepainted RC3 RAL
Internal paneling Galvanized steel 10/10 mm Roof type 9010
Flat roof
External paneling Prepainted sheet RC3 10/10 mm Technical space No
Internal screw material Galvanized steel Control equipment No
External screw material Standard galvanized Feet No -
Internal guides and supports Galvanized steel Providing feet -
Drain pan recessed drain pan SS AISI 304 Handles with key No
Drain Type Frontal with internal tubes not isolated
Baseframe Galvanized steel H 135 mm
CLASSIFICATION ACCORDING TO EN1886 (MB) PV10-ZN10-PU-60
Mechanical resist. Leakage -400/+700Pa (M) Thermal transmittance Thermal bridging Filters by-pass
-400/+700Pa (M) -400/+400Pa (R)
D1(M) L1(M) / L1(M) L2(R) - L2(R)
T2 TB3 F9(M)

PANELS ACOUSTIC ATTENUATION - FREQUENCY ANALYSIS


F [Hz] 63 125 250 500 1000 2000 4000 8000
[dB] 9 11 12 13 14 17 29 34

Fri Oct 18 11:47:01 2024 MEKAR srl - Via Caduti sul Lavoro, 25, 37063 Isola della Scala (VR) Off. N° 6895-24/2
FAHU-01 OP2 Tel. +39 045 663 0536 - Fax +39 045 6630513 Saved date 18-10-2024
Page 10 of 42 www.mekar.it - [email protected] Pro Air Evolution Rel. 1.0.3.2 10-06-2024
Saved date 18-10-2024 Printed out by MSD_21
Offer nr. 6895-24
Revision
OC nr.
Serial nr.

SUPPLY SIDE

1 RIGID BAG FILTER


G4 synthetic EN779:2012 / ISO Coarse 55% ISO16890 Tot. P. 184.0 Pa
4 592 x 592 x 48mm 1.00-4.00 m² 1.80-7.20 kg
2 490 x 592 x 48mm 0.83-1.66 m² 1.50-3.00 kg
Clean filter pressure drop 49 Pa-Calculated filter pressure drop 74 Pa-Dirty filter pressure drop 99 Pa
F7 EN779:2012 / ePM1 50% ISO16890
4 592 x 592 x 292mm 14.00-56.00 m² 3.80-15.20 kg Class:B
2 490 x 592 x 292mm 11.00-22.00 m² 3.60-7.20 kg Class:B
Clean filter pressure drop 60 Pa-Calculated filter pressure drop 110 Pa-Dirty filter pressure drop 160 Pa
COMPONENT NOISE REDUCTION NOTES
Hz 63 125 250 500 1000 2000 4000 8000 Air speed 2.16 m/s
dB 2 2 3 4 5 6 11 11 Glass fiber
ACCESSORIES
Filters side removal
Handles and hinges inspection

Fri Oct 18 11:47:01 2024 MEKAR srl - Via Caduti sul Lavoro, 25, 37063 Isola della Scala (VR) Off. N° 6895-24/2
FAHU-01 OP2 Tel. +39 045 663 0536 - Fax +39 045 6630513 Saved date 18-10-2024
Page 11 of 42 www.mekar.it - [email protected] Pro Air Evolution Rel. 1.0.3.2 10-06-2024
Saved date 18-10-2024 Printed out by MSD_21
Offer nr. 6895-24
Revision
OC nr.
Serial nr.

2 HEAT PIPE
Tot. P. 333.0 Pa
AIR SIDE HEAT PIPE
Air flow 15377 m³/h Calculation mode Rating
Air temp.heat pipe IN 46.00 °C Number of rows 2 nr.
Air temp. wet bulb 29.06 °C Fin per inch 11 nr.
Air relative humidity 29.00 % Fin coating Aluminium
Air temp. cooling IN 36.71 °C Air pressure drop (wet) 143.00 Pa
Air temp. wet bulb 26.97 °C Air pressure drop (dry) 143.00 Pa
Air relative humidity 47.4 % GAS R134A
Air temp. cooling OUT 15 °C Pre cooling capacity 49.57 kW
Air temp. wet bulb 15.00 °C Post heating capacity 49.57 kW
Air relative humidity 100 % Effectiveness 29.98 %
Air temp. heat pipe OUT 24.29 °C Weight empty 125.00 kg
Air temp.wet bulb 18.27 °C Heatpipe Type Horseshoe
Air relative humidity 56.13 % Fin width 1465 mm
COOLING COIL Fin height 1200 mm
Cu-Al-FeZn P40AR 7R-30T-1435A-2.5pa 26C 2 1/2" Width overall 1635 mm
Cooling coil duty 219.6 kW Height overall 1250 mm
Sensible capacity 114.2 kW Area 1.72 m2
Air pressure drop (wet) 190 Pa Face air velocity 2.48 m/s
Air pressure drop (dry) 124 Pa
Condensate 147.25 kg/h
Air velocity 2.48 m/s
Entering temperature 7.2 °C COMPONENT NOISE REDUCTION
Leaving temperature 14.9 °C Hz 63 125 250 500 1000 2000 4000 8000
Fluid flow 24475.54 l/h dB 1 1 2 3 4 5 6 7
Pressure drop 31.31 kPa NOTES
Internal volume 77.0 l. Category PED 2014/68/UE Art. 4.3
Fluid Velocity 1.36 m/s
Weight empty 153 kg
Tubes 16.45 x 0.4 Copper
Fins Aluminium 0.11 mm
Connection 2 1/2"
Frame Galv. 1.5 mm
ACCESSORIES
Sloped drain pan made of SS AISI 304 with Ø 1'' discharge

Fri Oct 18 11:47:01 2024 MEKAR srl - Via Caduti sul Lavoro, 25, 37063 Isola della Scala (VR) Off. N° 6895-24/2
FAHU-01 OP2 Tel. +39 045 663 0536 - Fax +39 045 6630513 Saved date 18-10-2024
Page 12 of 42 www.mekar.it - [email protected] Pro Air Evolution Rel. 1.0.3.2 10-06-2024
Saved date 18-10-2024 Printed out by MSD_21
Offer nr. 6895-24
Revision
OC nr.
Serial nr.

3 SUPPLY FAN
Backward curved blades Tot. P. 0 Pa
NTHZ 500 R MOTOR IE3
Quantity / Behavior 1 x 100.0% Installed power 7.5 kW
Airflow 1 x 15377.0 m³/h Electrical power 400/3/50 V/ph/Hz
External static pressure x 500 Pa Poles 4
Additional external static pressure 0 Pa Motor shaft diameter Ø 38 mm
Internal pressure drops 517 Pa Insulation Class F
Total static pressure 1017 Pa Protection IP 55
Dynamic pressure 66.3 Pa Nominal current each 14.43 A
Total pressure 1083.2 Pa Motor size 132M
Fan speed 1640 rpm Motor efficiency 90 %
Max fan speed 2100 rpm cosφ 0.83
Impeller power input 5.63 kW
Fan system power input 6.49 kW Frequency at the operation point 50 Hz
LwA_in 88.6 dB(A) Maximum frequency allowed 58 Hz
Total impeller efficiency 82.13 % Fan PULLEY SPA 140 x2 Shaft diameter 35 mm
Air speed on fan outlet 10.5 m/s Motor bush 2012 hole 38 mm
Altitude 0 m.slm Fan bush 2012 hole 35 mm
SFP 1.52 kW/(m³/s) Belt SPA-1832 x2
Air density 1.20 Kg/m3 Motor PULLEY SPA 160 x2 Shaft diameter 38 mm
Tmin / Tmax - °C Q=k·√(2/ρ·(ΔP))

Octave bands sound power level


F [Hz] 63 125 250 500 1000 2000 4000 8000
Outlet [dB] 91 88 90 85 85 80 74 66
Inlet [dB] 83 82 92 87 82 79 73 67
NOTES
Safety microswitch and protection carter
Designed for wet conditions
The fan system effect is taken into account in the fan performances, fans calculated at mean filters

ACCESSORIES
1 Belt tightener MOD. 132B GR 90/132 Standard galvanized
Handles and hinges inspection
4 Spring shock absorber

Fri Oct 18 11:47:01 2024 MEKAR srl - Via Caduti sul Lavoro, 25, 37063 Isola della Scala (VR) Off. N° 6895-24/2
FAHU-01 OP2 Tel. +39 045 663 0536 - Fax +39 045 6630513 Saved date 18-10-2024
Page 13 of 42 www.mekar.it - [email protected] Pro Air Evolution Rel. 1.0.3.2 10-06-2024
Saved date 18-10-2024 Printed out by MSD_21
Offer nr. 6895-24
Revision
OC nr.
Serial nr.

Fan diagram
P. Tot. [Pa]

Area 1

75 79
7.5 71 82
1900
81

78Area 2
5.5

72
4

1100 3 62

2.2
46
1.5 2100
1.1 1900
0.8 1700
[kW] 0.8 11
1500 7.5 [dB]
300
1300 5.5
1100 3 4
9001.1 1.5 2.2

3.1 8.4 13.7 18.9 24.2 29.5 34.8


Qx1000 [m3/h]

Fri Oct 18 11:47:01 2024 MEKAR srl - Via Caduti sul Lavoro, 25, 37063 Isola della Scala (VR) Off. N° 6895-24/2
FAHU-01 OP2 Tel. +39 045 663 0536 - Fax +39 045 6630513 Saved date 18-10-2024
Page 14 of 42 www.mekar.it - [email protected] Pro Air Evolution Rel. 1.0.3.2 10-06-2024
Saved date 18-10-2024 Printed out by MSD_21
Offer nr. 6895-24
Revision
OC nr.
Serial nr.

Fri Oct 18 11:47:02 2024 MEKAR srl - Via Caduti sul Lavoro, 25, 37063 Isola della Scala (VR) Off. N° 6895-24/2
FAHU-01 OP2 Tel. +39 045 663 0536 - Fax +39 045 6630513 Saved date 18-10-2024
Page 15 of 42 www.mekar.it - [email protected] Pro Air Evolution Rel. 1.0.3.2 10-06-2024
Saved date 18-10-2024 Printed out by MSD_21
Offer nr. 6895-24
Revision
OC nr.
Serial nr.

SOUND POWER LEVEL


Octave band (Hz) 63 125 250 500 1000 2000 4000 8000 Tot.dB(A)
Lw at fresh air inlet [dB] 80 79 87 80 73 68 56 49 81
Lw at supply air outlet [dB] 91 88 90 85 85 80 74 66 89
Lw to enviroment [dB] 82 77 78 72 71 63 45 32 75
Sound pressure measured at 1 m distance in free field condition (Q=2) 61 dB(A)
Tolerance on radiated sound power level Lw: +3 dB / Tolerance on level openings Lw: +5 dB @125 Hz, +3 dB @250 - 8000 Hz

EUROVENT

SUMMER WINTER
Design dry-bulb temperature °C 43.1 14.2 °C
Design dew-point temperature 15.8 - °C
°C
Design wet bulb temperature °C 24.2 °C
-
DUBAI INTL (United Arab Emirates)
The manufacturer participates in the ECP programme for AHU. Check ongoing validity of certificate: www.eurovent-certification.com

EN13053
Supply Power Class P1
Supply Velocity Class V3
Return Power Class -
Return Velocity Class -
Heat Recovery Efficiency Class -
Mixing Box Efficiency Class -

TOLERANCES ON DECLARED DATA


COILS HUMIDIFICATION
Tolerance on air pressure drop: 10% or 10 Pa Tolerances on nominal value +5%/-10% in accordance with
Tolerance on capacity: 5% EN 60335-1
Tolerance on water pressure drop: 10% o 5 kPa
ROTARY HEAT EXCHANGER PLATE HEAT EXCHANGER
Tolerance on temperature efficiency: 3% Tolerance on temperature efficiency wet: 3%
Tolerance on humidity efficiency: 5% Tolerance on temperature efficiency dry: 5%
Tolerance on pressure drop: 10% or 15 Pa Tolerance on pressure drop: 10% o 15 Pa
FILTERS FANS
Tolerances in accordance with ISO 16890 and EN 1822 Tolerances according to DIN 24166 Class 1 & ISO 13348 Cl
DIMENSIONS WEIGHTS
Tolerance on dim. according to UNI EN ISO 22081:2021 I Tolerance on weights: 5%
All air flow and pressure losses are based on the density calculated for a given altitude and temperature.

Applications Standard

Fri Oct 18 11:47:02 2024 MEKAR srl - Via Caduti sul Lavoro, 25, 37063 Isola della Scala (VR) Off. N° 6895-24/2
FAHU-01 OP2 Tel. +39 045 663 0536 - Fax +39 045 6630513 Saved date 18-10-2024
Page 16 of 42 www.mekar.it - [email protected] Pro Air Evolution Rel. 1.0.3.2 10-06-2024
Saved date 18-10-2024 Printed out by MSD_21
Offer nr. 6895-24
Revision
OC nr.
Serial nr.

Ecodesign
Manufacturer MEKAR LLC
Unit model 23MK-60-029039
Typology NRVU;UVU
SFPint / SFPint limit 2018 [W/(m³/s)] 90 / 230
Type of HRS -
Thermal efficiency of heat recovery [%] -
Nominal flow rate 4.27
Maximum external leakage rate (RU) +400Pa / -400Pa [%] L2(R) - L2(R)
Maximum internal leakage rate [%] -
Supply
Nominal flow rate 4.27 m³/s
Type of drive Frequency converter is ma
Effective electric power input 6.49 kW
Face velocity 1.94 m/s
Nominal external pressure 500 Pa
Internal pressure drop of ventilation components 60 Pa
Static efficiency of fan 66.9 %
Filter energy performance (ERP designed) B
Sound power level [LWA] see technical schedule
Internet address for disassembly instructions: check in the end of this page
AHU not Ecodesign compliant
-

Fri Oct 18 11:47:02 2024 MEKAR srl - Via Caduti sul Lavoro, 25, 37063 Isola della Scala (VR) Off. N° 6895-24/2
FAHU-01 OP2 Tel. +39 045 663 0536 - Fax +39 045 6630513 Saved date 18-10-2024
Page 17 of 42 www.mekar.it - [email protected] Pro Air Evolution Rel. 1.0.3.2 10-06-2024
G4-F7

15377 [m³/h] 500 [Pa] 0 [m³/h] // [Pa]

Fri Oct 18 11:47:02 2024 MEKAR srl - Via Caduti sul Lavoro, 25, 37063 Isola della Scala (VR) Off. N° 6895-24/2
FAHU-01 OP2 Tel. +39 045 663 0536 - Fax +39 045 6630513 Saved date 18-10-2024
Page 18 of 42 www.mekar.it - [email protected] Pro Air Evolution Rel. 1.0.3.2 10-06-2024