SIEMENS TEST CERTIFICATE

Product Code: 7SJ82DAAAAA00AAAA0AA041112111BBAA000000AB0HB1BD4JA0


Serial No. : BM1804007032 test date : 2018-04-25
TNS : P1J39525 test equip.: V5 UPS 3.1
Order No. : 0038465524 / 000040 tested by : 1271
Firmware : OvercurrentProt_V07.53 test prg. : 2.6.2.1817

Personalizing of Crypto Controller


Test step Passed.

Upload Firmware to the device


Test step Passed.

Device USB Check


Test step Passed.

Upload configuration files to the device


Test step Passed.

Update COM Firmware


Test step Passed.

Compare Product Code with HW configuration


Product code explanation:
Type of device: 7SJ82
Special approvals: without (idx 7, val AA)
Extended Tests: without (idx 9, val A)
Customer-specific Parameterization: without (idx 10, val AA)
Encryption for communication modules: Normal (idx 19, val A)
Functional class: Basic (idx 20, val A)
Significant Feature: not relevant (idx 21, val 0)
Power Supply (Voltage variant): DC 110 V-250 V, AC 115 V-230 V (idx 22, val 4)
Housing Construction: Flush Mounting (idx 23, val 1)
Key Switch: without (idx 24, val 1)
LEDs: 16 (idx 25, val 1)
Display: Small (idx 26, val 2)
Operation Panel: Integrated (idx 27, val 1)
Front Design: Standard (idx 28, val 1)
Port J: DIGSI via Ethernet, RJ45 (idx 29, val 1)
Port E: ETH-BB-2FO (idx 30, val BB)
Mounting position 0 (in the 1/3 housing) CPU: CP100 (idx 40, val AB0)
Mounting position 1 (in the 1/3 housing) IO: IO102, TerminalA = 4xI (idx 43, val HB1)
Mounting position 2 (in the 1/3 housing) PS: PS101, DC 110 V-250 V, AC 115 V-230 V (idx
46, val BD4)
Mounting position 3 (in the 1/3 housing) Exp. Board: IO110 (idx 49, val JA0)
MAC mainboard to DB: MAC B4:B1:5A:05:9C:77, PCB BF1803061268, Device BM1804007032
MAC Port E to DB: MAC B4:B1:5A:05:87:F1, PCB BF1803067560, Device BM1804007032
Test step Passed.

Human Machine Interface Check


Test step Passed.

Power Consumption
───────────────────────────────────────────────────────────────────────────
│ voltage [V] │ current [A] │ power [W] │ min. [W] │ max. [W] │ state │
───────────────────────────────────────────────────────────────────────────
│ 81.99 │ 0.098 │ 8.04 │ 6.52 │ 9.78 │ PASS │
│ 250.03 │ 0.034 │ 8.50 │ 6.52 │ 9.78 │ PASS │
│ 179.99 │ 0.045 │ 8.10 │ 6.52 │ 9.78 │ PASS │
Test step Passed.

Onboard Communication interfaces


Test step Passed.

Page 1 of 6
SIEMENS TEST CERTIFICATE

Product Code: 7SJ82DAAAAA00AAAA0AA041112111BBAA000000AB0HB1BD4JA0


Serial No. : BM1804007032 test date : 2018-04-25
TNS : P1J39525 test equip.: V5 UPS 3.1
Order No. : 0038465524 / 000040 tested by : 1271
Firmware : OvercurrentProt_V07.53 test prg. : 2.6.2.1817

Binary Inputs at IO102 in Slot1


Applied 300 V to 8 binary inputs. Measured current: 13.771 mA. Average: 1.721 mA
──────────────────────────────────────────────────────────────────────────────────────────
│ no. │ BI │input │unit │ nom.value │ meas.value │ comment │state│
│of BI│ threshold │ [V] │ │ MSB LSB │ MSB LSB │ │ │
──────────────────────────────────────────────────────────────────────────────────────────
│ 8 │ HIGH │ 170 │bits │ 11111111 │ 11111111 │ All BIs │PASS │
│ 8 │ HIGH │ 130 │bits │ 00000000 │ 00000000 │ All BIs │PASS │
│ 8 │ HIGH │ 170 │bits │ 11111111 │ 11111111 │ All BIs Reverse │PASS │
│ 8 │ HIGH │ 130 │bits │ 00000000 │ 00000000 │ All BIs Reverse │PASS │
│ 8 │ MEDIUM │ 80 │bits │ 11111111 │ 11111111 │ All BIs │PASS │
│ 8 │ LOW │ 18 │bits │ 11111111 │ 11111111 │ All BIs │PASS │
Test step Passed.

Digital outputs at IO102 in Slot1


Test Relay activation:
───────────────────────────────────────────────────────────────────────────────
│ rel.no. │ switch │ nom.val │ nom.val │ meas.val. │ meas.val. │ state │
│ │ state │ COM -> NO │ COM -> NC │ COM -> NO │ COM -> NC │ │
───────────────────────────────────────────────────────────────────────────────
│ 1 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 1 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
│ 2 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 2 │ inactive │ LOW │ HIGH │ LOW │ HIGH │ PASS │
│ 3 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 3 │ inactive │ LOW │ HIGH │ LOW │ HIGH │ PASS │
│ 4 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 4 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
│ 5 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 5 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
│ 6 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 6 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
Test step Passed.

Check of Clamp Compensation for Delivery at IO102 in Slot1


Test step Passed.

Compensation of Current Transformers (Board) at IO102 in Slot1


Test step Passed.

Compensation of Voltage Transformers at IO102 in Slot1


Test step Passed.

Page 2 of 6
SIEMENS TEST CERTIFICATE

Product Code: 7SJ82DAAAAA00AAAA0AA041112111BBAA000000AB0HB1BD4JA0


Serial No. : BM1804007032 test date : 2018-04-25
TNS : P1J39525 test equip.: V5 UPS 3.1
Order No. : 0038465524 / 000040 tested by : 1271
Firmware : OvercurrentProt_V07.53 test prg. : 2.6.2.1817

Check Voltage Amplitude at IO102 in Slot1


──────────────────────────────────────────────────────────────────────────────────────────
│channel│freq.[Hz]│amp.range[V]│setpoint[V]│meas.value[V]│deviation[%]│max.dev. [%]│state│
──────────────────────────────────────────────────────────────────────────────────────────
│ 5 │ 50.00 │ 200 │ 57.75 │ 57.762 │ +0.021 │ 0.20 │PASS │
│ 6 │ 50.00 │ 200 │ 57.75 │ 57.762 │ +0.020 │ 0.20 │PASS │
│ 7 │ 50.00 │ 200 │ 57.75 │ 57.758 │ +0.014 │ 0.20 │PASS │
│ 8 │ 50.00 │ 200 │ 57.75 │ 57.758 │ +0.015 │ 0.20 │PASS │
│ 5 │ 50.00 │ 200 │ 100.00 │ 100.023 │ +0.023 │ 0.20 │PASS │
│ 6 │ 50.00 │ 200 │ 100.00 │ 100.031 │ +0.031 │ 0.20 │PASS │
│ 7 │ 50.00 │ 200 │ 100.00 │ 100.034 │ +0.034 │ 0.20 │PASS │
│ 8 │ 50.00 │ 200 │ 100.00 │ 100.023 │ +0.023 │ 0.20 │PASS │
│ 5 │ 60.00 │ 200 │ 57.75 │ 57.747 │ -0.005 │ 0.20 │PASS │
│ 6 │ 60.00 │ 200 │ 57.75 │ 57.746 │ -0.007 │ 0.20 │PASS │
│ 7 │ 60.00 │ 200 │ 57.75 │ 57.747 │ -0.005 │ 0.20 │PASS │
│ 8 │ 60.00 │ 200 │ 57.75 │ 57.750 │ -0.001 │ 0.20 │PASS │
│ 5 │ 60.00 │ 200 │ 100.00 │ 100.007 │ +0.007 │ 0.20 │PASS │
│ 6 │ 60.00 │ 200 │ 100.00 │ 100.016 │ +0.016 │ 0.20 │PASS │
│ 7 │ 60.00 │ 200 │ 100.00 │ 100.020 │ +0.020 │ 0.20 │PASS │
│ 8 │ 60.00 │ 200 │ 100.00 │ 100.011 │ +0.011 │ 0.20 │PASS │
Test step Passed.

Check Current Amplitude at IO102 in Slot1


──────────────────────────────────────────────────────────────────────────────────────────
│channel│freq.[Hz]│amp.range[A]│setpoint[A]│meas.value[A]│deviation[%]│max.dev. [%]│state│
──────────────────────────────────────────────────────────────────────────────────────────
│ 1 │ 50.00 │ 50.0 │ 1.0 │ 0.9999 │ -0.014 │ 0.10 │PASS │
│ 2 │ 50.00 │ 50.0 │ 1.0 │ 1.0002 │ +0.021 │ 0.10 │PASS │
│ 3 │ 50.00 │ 50.0 │ 1.0 │ 1.0000 │ +0.002 │ 0.10 │PASS │
│ 4 │ 50.00 │ 50.0 │ 1.0 │ 0.9999 │ -0.008 │ 0.10 │PASS │
│ 1 │ 50.00 │ 250.0 │ 5.0 │ 4.9994 │ -0.012 │ 0.10 │PASS │
│ 2 │ 50.00 │ 250.0 │ 5.0 │ 4.9996 │ -0.007 │ 0.10 │PASS │
│ 3 │ 50.00 │ 250.0 │ 5.0 │ 5.0005 │ +0.010 │ 0.10 │PASS │
│ 4 │ 50.00 │ 250.0 │ 5.0 │ 4.9994 │ -0.013 │ 0.10 │PASS │
│ 1 │ 60.00 │ 50.0 │ 1.0 │ 1.0001 │ +0.011 │ 0.10 │PASS │
│ 2 │ 60.00 │ 50.0 │ 1.0 │ 1.0001 │ +0.011 │ 0.10 │PASS │
│ 3 │ 60.00 │ 50.0 │ 1.0 │ 0.9999 │ -0.005 │ 0.10 │PASS │
│ 4 │ 60.00 │ 50.0 │ 1.0 │ 1.0001 │ +0.009 │ 0.10 │PASS │
│ 1 │ 60.00 │ 250.0 │ 5.0 │ 5.0006 │ +0.013 │ 0.10 │PASS │
│ 2 │ 60.00 │ 250.0 │ 5.0 │ 5.0000 │ -0.001 │ 0.10 │PASS │
│ 3 │ 60.00 │ 250.0 │ 5.0 │ 5.0010 │ +0.020 │ 0.10 │PASS │
│ 4 │ 60.00 │ 250.0 │ 5.0 │ 5.0007 │ +0.015 │ 0.10 │PASS │
Test step Passed.

Page 3 of 6
SIEMENS TEST CERTIFICATE

Product Code: 7SJ82DAAAAA00AAAA0AA041112111BBAA000000AB0HB1BD4JA0


Serial No. : BM1804007032 test date : 2018-04-25
TNS : P1J39525 test equip.: V5 UPS 3.1
Order No. : 0038465524 / 000040 tested by : 1271
Firmware : OvercurrentProt_V07.53 test prg. : 2.6.2.1817

Check Angles at IO102 in Slot1


Range 500 is equal to (I_rated x 100); I_rated = 5 A
Range 8 is equal to (I_rated x 1.6); I_rated = 5 A
──────────────────────────────────────────────────────────────────────────────────────────
│channel │ freq. │ range │amplitude│ref.│ ref. │ ref. │ meas.value │ max.dev. │ state │
│ │ [Hz] │ │ │PCB │ chann │range │ [°] │ [°] │ │
──────────────────────────────────────────────────────────────────────────────────────────
│ CH1_AC │ 50.00 │ 50.0 A │ 1.0 A │ 1 │ CH4_AC │ 50.0 │ -0.0181 │ 0.15 │ PASS │
│ CH2_AC │ 50.00 │ 50.0 A │ 1.0 A │ 1 │ CH4_AC │ 50.0 │ -0.0149 │ 0.15 │ PASS │
│ CH3_AC │ 50.00 │ 50.0 A │ 1.0 A │ 1 │ CH4_AC │ 50.0 │ 0.0038 │ 0.15 │ PASS │
│ CH1_AC │ 50.00 │250.0 A │ 5.0 A │ 1 │ CH4_AC │250.0 │ -0.0083 │ 0.15 │ PASS │
│ CH2_AC │ 50.00 │250.0 A │ 5.0 A │ 1 │ CH4_AC │250.0 │ -0.0083 │ 0.15 │ PASS │
│ CH3_AC │ 50.00 │250.0 A │ 5.0 A │ 1 │ CH4_AC │250.0 │ 0.0016 │ 0.15 │ PASS │
│ CH5_AV │ 50.00 │200.0 V │ 57.8 V │ 1 │ CH4_AC │ 50.0 │ -0.0096 │ 0.20 │ PASS │
│ CH6_AV │ 50.00 │200.0 V │ 57.8 V │ 1 │ CH4_AC │ 50.0 │ -0.0099 │ 0.20 │ PASS │
│ CH7_AV │ 50.00 │200.0 V │ 57.8 V │ 1 │ CH4_AC │ 50.0 │ -0.0146 │ 0.20 │ PASS │
│ CH8_AV │ 50.00 │200.0 V │ 57.8 V │ 1 │ CH4_AC │ 50.0 │ -0.0045 │ 0.20 │ PASS │
│ CH1_AC │ 60.00 │ 50.0 A │ 1.0 A │ 1 │ CH4_AC │ 50.0 │ -0.0113 │ 0.15 │ PASS │
│ CH2_AC │ 60.00 │ 50.0 A │ 1.0 A │ 1 │ CH4_AC │ 50.0 │ -0.0133 │ 0.15 │ PASS │
│ CH3_AC │ 60.00 │ 50.0 A │ 1.0 A │ 1 │ CH4_AC │ 50.0 │ -0.0015 │ 0.15 │ PASS │
│ CH1_AC │ 60.00 │250.0 A │ 5.0 A │ 1 │ CH4_AC │250.0 │ -0.0197 │ 0.15 │ PASS │
│ CH2_AC │ 60.00 │250.0 A │ 5.0 A │ 1 │ CH4_AC │250.0 │ -0.0030 │ 0.15 │ PASS │
│ CH3_AC │ 60.00 │250.0 A │ 5.0 A │ 1 │ CH4_AC │250.0 │ 0.0106 │ 0.15 │ PASS │
│ CH5_AV │ 60.00 │200.0 V │ 57.8 V │ 1 │ CH4_AC │ 50.0 │ -0.0165 │ 0.20 │ PASS │
│ CH6_AV │ 60.00 │200.0 V │ 57.8 V │ 1 │ CH4_AC │ 50.0 │ -0.0155 │ 0.20 │ PASS │
│ CH7_AV │ 60.00 │200.0 V │ 57.8 V │ 1 │ CH4_AC │ 50.0 │ -0.0147 │ 0.20 │ PASS │
│ CH8_AV │ 60.00 │200.0 V │ 57.8 V │ 1 │ CH4_AC │ 50.0 │ -0.0139 │ 0.20 │ PASS │
Test step Passed.

Binary Inputs at PS101 in Slot2


Applied 300 V to 3 binary inputs. Measured current: 5.268 mA. Average: 1.756 mA
──────────────────────────────────────────────────────────────────────────────────────────
│ no. │ BI │input │unit │ nom.value │ meas.value │ comment │state│
│of BI│ threshold │ [V] │ │ MSB LSB │ MSB LSB │ │ │
──────────────────────────────────────────────────────────────────────────────────────────
│ 3 │ HIGH │ 170 │bits │ 111 │ 111 │ All BIs │PASS │
│ 3 │ HIGH │ 130 │bits │ 000 │ 000 │ All BIs │PASS │
│ 3 │ HIGH │ 170 │bits │ 111 │ 111 │ All BIs Reverse │PASS │
│ 3 │ HIGH │ 130 │bits │ 000 │ 000 │ All BIs Reverse │PASS │
│ 3 │ MEDIUM │ 80 │bits │ 111 │ 111 │ All BIs │PASS │
│ 3 │ LOW │ 18 │bits │ 111 │ 111 │ All BIs │PASS │
Test step Passed.

Page 4 of 6
SIEMENS TEST CERTIFICATE

Product Code: 7SJ82DAAAAA00AAAA0AA041112111BBAA000000AB0HB1BD4JA0


Serial No. : BM1804007032 test date : 2018-04-25
TNS : P1J39525 test equip.: V5 UPS 3.1
Order No. : 0038465524 / 000040 tested by : 1271
Firmware : OvercurrentProt_V07.53 test prg. : 2.6.2.1817

Digital outputs at PS101 in Slot2


Test Relay activation:
───────────────────────────────────────────────────────────────────────────────
│ rel.no. │ switch │ nom.val │ nom.val │ meas.val. │ meas.val. │ state │
│ │ state │ COM -> NO │ COM -> NC │ COM -> NO │ COM -> NC │ │
───────────────────────────────────────────────────────────────────────────────
│ 1 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 1 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
│ 2 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 2 │ inactive │ LOW │ HIGH │ LOW │ HIGH │ PASS │
│ 3 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 3 │ inactive │ LOW │ HIGH │ LOW │ HIGH │ PASS │
Switch Time of relays:
─────────────────────────────────────────────────────────────────────────────────────
│ no. relay │ nom.maketime │ meas.maketime │ nom.breaktime │ meas.breaktime │ state │
│ │ [ms] │ [ms] │ [ms] │ [ms] │ │
─────────────────────────────────────────────────────────────────────────────────────
│ 1 │ 13.00 │ 12.00 │ 12.00 │ 7.00 │ PASS │
│ 2 │ 13.00 │ 11.00 │ 12.00 │ 7.00 │ PASS │
Test step Passed.

Binary Inputs at IO110 in Slot3


Applied 300 V to 12 binary inputs. Measured current: 21.207 mA. Average: 1.767 mA
──────────────────────────────────────────────────────────────────────────────────────────
│ no. │ BI │input │unit │ nom.value │ meas.value │ comment │state│
│of BI│ threshold │ [V] │ │ MSB LSB │ MSB LSB │ │ │
──────────────────────────────────────────────────────────────────────────────────────────
│ 12 │ HIGH │ 145 │bits │ 111111111111 │ 111111111111 │ All BIs │PASS │
│ 12 │ HIGH │ 88 │bits │ 000000000000 │ 000000000000 │ All BIs │PASS │
│ 12 │ HIGH │ 145 │bits │ 111111111111 │ 111111111111 │ All BIs Reverse │PASS │
│ 12 │ HIGH │ 88 │bits │ 000000000000 │ 000000000000 │ All BIs Reverse │PASS │
│ 12 │ MEDIUM │ 74 │bits │ 111111111111 │ 111111111111 │ All BIs │PASS │
│ 12 │ LOW │ 19 │bits │ 111111111111 │ 111111111111 │ All BIs │PASS │
Test step Passed.

Page 5 of 6
SIEMENS TEST CERTIFICATE

Product Code: 7SJ82DAAAAA00AAAA0AA041112111BBAA000000AB0HB1BD4JA0


Serial No. : BM1804007032 test date : 2018-04-25
TNS : P1J39525 test equip.: V5 UPS 3.1
Order No. : 0038465524 / 000040 tested by : 1271
Firmware : OvercurrentProt_V07.53 test prg. : 2.6.2.1817

Digital outputs at IO110 in Slot3


Test Relay activation:
───────────────────────────────────────────────────────────────────────────────
│ rel.no. │ switch │ nom.val │ nom.val │ meas.val. │ meas.val. │ state │
│ │ state │ COM -> NO │ COM -> NC │ COM -> NO │ COM -> NC │ │
───────────────────────────────────────────────────────────────────────────────
│ 1 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 1 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
│ 2 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 2 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
│ 3 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 3 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
│ 4 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 4 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
│ 5 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 5 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
│ 6 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 6 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
│ 7 │ activated │ HIGH │ LOW │ HIGH │ LOW │ PASS │
│ 7 │ inactive │ LOW │ LOW │ LOW │ LOW │ PASS │
Switch Time of relays:
─────────────────────────────────────────────────────────────────────────────────────
│ no. relay │ nom.maketime │ meas.maketime │ nom.breaktime │ meas.breaktime │ state │
│ │ [ms] │ [ms] │ [ms] │ [ms] │ │
─────────────────────────────────────────────────────────────────────────────────────
│ 1 │ 13.00 │ 11.00 │ 12.00 │ 8.00 │ PASS │
│ 2 │ 13.00 │ 11.00 │ 12.00 │ 8.00 │ PASS │
│ 3 │ 13.00 │ 11.00 │ 12.00 │ 7.00 │ PASS │
│ 4 │ 13.00 │ 12.00 │ 12.00 │ 7.00 │ PASS │
│ 5 │ 13.00 │ 12.00 │ 12.00 │ 7.00 │ PASS │
│ 6 │ 13.00 │ 11.00 │ 12.00 │ 7.00 │ PASS │
│ 7 │ 13.00 │ 11.00 │ 12.00 │ 8.00 │ PASS │
Test step Passed.

Verify the error log file(s)


Test step Passed.

Page 6 of 6