700 MK3 Data
700 MK3 Data
700 MK3 Data
FEATURES
• Diesel and gas genset support • DC genset functionality • Multiple load management
• 400Hz operation support • DPF regeneration functionality • Current unbalance protection
• 400 event logs, full snapshot • Peak Lopping / peak shaving • Voltage unbalance protection
• All parameters front panel • Mains de-coupling protection • Fuel filling & fuel theft alarms
editable • R.O.C.O.F protection • Contactor & MCB drive
• 3 level configuration password • Vector shift protection • Battery back-up real time clock
• 4.3” 480x272pixels color LCD • Reverse power protection • Idle speed control
• Downloadable languages • Over/under freq. Protection • Battery charge run enabled
• Waveform display of V & I • Over/under voltage protection • Combat mode support
• Harmonic analysis of V & I • Smart load management • Multiple nominal conditions
• Synchroscope & check synch • Smart genset sequencing • 4 quadrant genset power
• Allows closed transfers • Run/stop priority support counters
• 12 configurable digital inputs • Equal aging of gensets • Mains power counters
• Inputs expandable to 44 • Base load (power export) • Fuel filling counter
• 8 configurable digital outputs • Unmanaged distributed power • Fuel consumption counter
• Outputs expandable to 40 export support • Modem & ethernet diagnostics
• 7 configurable analog inputs • AVR & GOV droop support • Configurable through USB,
• 2 configurable analog outputs • Dead bus sensing RS-485, Ethernet and GPRS
• Both CANBUS-J1939 & MPU • Multiple automatic exerciser • Free configuration program
• 3 configurable service alarms • Weekly operation schedule • Allows SMS controls
• Multiple topologies • Dual mutual standby with • Ready for central monitoring
• 6xCT, true mains metering equal aging of gensets ethernet & GPRS
• Supports up to 48 gensets • Manual “speed fine adjust” on • SNMP v1 v2c v3 support
• Automatic learning/self adjust selected ECUs • Mobile genset support
• Direct governor & AVR control • Automatic fuel pump control • Automatic GSM geo-location
• Voltage and phase matching • Disable protections feature • GPS connectivity (USB&RS232)
• kW & kVAr load sharing • Excess power protection • Dynamic DNS support
• True soft transfer in both ways • Reverse power protection • Easy USB firmware upgrade
• PLC functions • Overload IDMT protection • IP65 rating with standard gasket
• Load shedding, dummy load
PLUG-IN MODULES FUNCTIONALITIES COMMUNICATIONS
▪ 2G GSM Modem ▪ Multi genset synch & load share ▪ Central Monitoring
▪ 3G-2G GSM Modem ▪ Mains synchronization ▪ Embedded Web Server
▪ 4G-3G-2G (CAT-4) Modem ▪ Single genset parallel with mains ▪ USB
▪ NB/IOT,CAT-M1,2G Modem ▪ DC genset controller ▪ GPS (geo-location)
▪ Wi-Fi (802.11 b/g/n) ▪ AMF unit (uninterrupted transfer) ▪ SMS
▪ Ethernet 100 Mbps ▪ ATS unit (uninterrupted transfer) ▪ E-mail
▪ USB Host ▪ Remote start controller ▪ Modbus
▪ RS-232 (isolated) ▪ Manual start controller ▪ Modbus TCP/IP
▪ RS-485 (isolated) ▪ Engine controller ▪ SNMP v1 v2c v3
▪ Synchro/LoadShare Module ▪ Remote display panel ▪ HTML
▪ 3x AC Current Inputs ▪ UDP
▪ 3x Analog Inputs & 2x Analog ▪ SNTP
Outputs
▪ DC Voltage and Current Inputs
▪ Tilt Detector
Backpanel view
Plug-in modules
LOAD
Datalink
DATALINK
Bus To mains GENSET
BUS
controller BUSBAR
s TO GENSET
CONTROLLERS
SCOPEMETER & HARMONICS RAINBOW SCADA CENTRAL MONITORING
TECHNICAL SPECIFICATIONS
Alternator voltage: 0 to 300 V-AC (Ph-N) RS-232 Port: selectable baud rate (2400-115200baud)
Alternator frequency: 0-600 Hz. Operating temperature: -20°C to 70°C (-4 to +158 °F)
Mains voltage: 0 to 300 V-AC (Ph-N) Storage temperature: -40°C to 80°C (-40 to +176°F)
Mains frequency: 0-600 Hz. Maximum humidity: 95% non-condensing.
Topology: 1-2-3 phases, with or without neutral IP Protection: IP65 from front panel, IP30 from the rear (with
DC Supply Range: 8.0 to 36.0 V-DC. gasket)
V-A-cos Accuracy: 0.5% + 1 digit Dimensions: 245 x 188 x 36mm (WxHxD)
kW-kVA-kVAr Accuracy: 1.0% + 1 digit Panel Cut-out Dimensions: 216 x 156 mm minimum.
Current consumption: 500 mA-DC max. Weight: 800 g (approx.)
Current Inputs: from current transformers. ../5A or ../1A. Case Material: High Temperature, non-flammable ABS/PC
Digital inputs: input voltage 0 to 36 V-DC. Installation: Flat surface mounting on a Type 1 enclosure. Rear
Analog input range: 0-5000 ohms. retaining plastic brackets.
Mains and genset contactor outputs: 16Amps@250V
DC Outputs: Protected mosfet semiconductor outputs,
CONFORMITY
rated 1Amp@28V-DC
Cranking dropouts: survives 0V for 100ms.
Magnetic pickup voltage: 0.5 to 50Vpk. EU Directives Conformity
Magnetic pickup frequency: 0 to 20000 Hz. -2014/35/EC (low voltage)
Charge Alternator Excitation: 2W. -2014/30/EC (electro-magnetic compatibility)
Display Screen: 4.3”, 480x272 pixels, color Norms of reference:
Ethernet Port: 10/100 Mbits EN 61010 (safety requirements)
USB Device: USB 2.0 Full speed EN 61326 (EMC requirements)
USB Host: USB 2.0 Full speed UL & CSA Compatibility:
RS-485 Port: selectable baud rate (2400-115200baud) • UL 6200, Controls for Stationary Engine Driven Assemblies
(File# - 20140725-E314374)
• CAN/CSA C22.2 No. 14-13 – Industrial Control Equipment
TYPICAL CONNECTIONS