Influence of Tertiary Stabilizing Windings On Zero-Sequence
Influence of Tertiary Stabilizing Windings On Zero-Sequence
Influence of Tertiary Stabilizing Windings On Zero-Sequence
a r t i c l e i n f o a b s t r a c t
Article history: The presence of a stabilizing winding (or tertiary stabilizing winding when is used to for auxiliary
Received 4 October 2015 applications) in three-phase three-legged YNynd transformers remarkably affects the zero-sequence
Received in revised form 27 July 2016 performance of both the transformer and the network. This paper presents a detailed analysis of the
Accepted 29 October 2016
influence of the stabilizing winding on the zero-sequence behavior of three-phase three-legged YNynd
Available online 23 November 2016
transformers. Based on a complete set of onsite zero-sequence measurements taken in three power
transformers, transformer zero-sequence performance is analyzed in relation to internal design features
Keywords:
such as stabilizing winding position relative to high-voltage and low-voltage windings or the presence
Three-winding transformers
Tertiary stabilizing windings
of magnetic shunts in the tank. Based on these measurements, this paper assesses the ability of various
Transformer zero-sequence performance equivalent circuit models to reproduce zero-sequence performance accurately. A companion paper that
Onsite zero-sequence impedance complements this study evaluates the influence of stabilizing windings on tank overheating hazard and
measurements short-circuit duty in the event of asymmetrical faults.
Transformer equivalent circuits © 2016 Elsevier B.V. All rights reserved.
http://dx.doi.org/10.1016/j.epsr.2016.10.065
0378-7796/© 2016 Elsevier B.V. All rights reserved.
A. Ramos, J.C. Burgos / Electric Power Systems Research 144 (2017) 32–40 33
Fig. 1. Schematic description of the internal construction design of the transformers measured.
Table 1 Table 4
Characteristics of transformers subject to zero-sequence measurements. Results and calculations of zero-sequence measurements taken in transformer #2.
Test number Test code HV winding LV winding Stabilizing winding HOO (In Table 6) (In Table 6) – – 87.98
HOC 0.045 0.265 – 0.257 16.85
1 HOO Energized Open circuit Delta open HSO 0.109 0.896 0.782 – 12.17
2 HOC Energized Open circuit Delta close HSC 0.062 0.897 0.487 0.396 6.90
3 HSO Energized Short circuit Delta open LOO (In Table 6) – (In Table 6) – 104.27
4 HSC Energized Short circuit Delta close LOC 0.123 – 0.359 0.324 34.20
5 LOO Open circuit Energized Delta open LSO 0.053 0.366 0.375 – 14.06
6 LOC Open circuit Energized Delta close LSC 0.065 0.502 0.470 0.061 13.88
7 LSO Short circuit Energized Delta open
8 LSC Short circuit Energized Delta close
(I3 ). Voltage and current values are shown in percentage of base
quantities (rated voltage and rated apparent power). Calculation of
Table 3
Results and calculations of zero-sequence measurements taken in transformer #1.
zero-sequence impedance is indicated in Eq. (1),
V
Test code V (%) I1 (%) I2 (%) I3 (%) Z0 (%) Z0(ABC) = (1)
I/3
HOO (In Table 6) (In Table 6) – – 80.14
HOC 0.249 1.581 – 1.243 15.76 where (ABC) is the test code (e.g., HOO in test 1 in Table 2) and V
HSO 0.150 1.590 1.386 – 9.43 and I are the measurements taken in the energized winding.
HSC 0.145 1.555 1.659 0.387 9.35
Zero-sequence impedance modules are presented in percent-
LOO (In Table 6) – (In Table 6) – 86.09
LOC 0.033 – 0.599 0.545 5.58 ages in Tables 3–5, calculated as indicated in Eq. (2),
LSO 0.054 0.503 0.507 – 10.76 Z0(ABC) V (%)
LSC 0.019 0.225 0.587 0.360 3.29 Z0(ABC) (%) = = (2)
Zbase I (%)
Relation between Eqs. (1) and (2) could be easily derived from
The internal design of transformer #1 (with inner stabilizing well-known relations between rated and base quantities.
winding and no magnetic shunts) is typically employed in low- and As illustrated in Ref. [16], non-linear behavior of HOO and
medium-power YNynd transformers. When rated power is above LOO measurements does not produce a major problem of model
30–40 MVA, transformer designers include magnetic shields, as in accuracy when predicting short-circuit currents. Consequently, to
transformer #2. For high-power transformers (above 100 MVA), facilitate understanding of Tables 3–5 these tests consider average
three-winding YNynd transformers may include outer stabilizing impedance values. All values measured in these tests are shown in
windings, as in transformer #3 (with or without magnetic shields). Table 6. Some additional considerations about “no-load” tests (i.e.
As demonstrated in Ref. [16], accurate representation of the HOO and LOO measurements) can be found after Table 6.
zero-sequence performance of three-phase three-legged YNynd As indicated previously, an accurate representation of the
transformers can be achieved by taking onsite low-voltage mea- zero-sequence performance of three-phase three-legged YNynd
surements, requiring 8 tests as indicated in Table 2. transformers can be achieved by means of low-voltage onsite
The results and calculations deriving from the tests performed measurements. With the exception of no-load tests, the rest of zero-
on the three transformers in Table 1 are shown in Tables 3–5, which sequence impedances (i.e. HOC, HSO, HSC, LOC, LSO and LSC) show
present measurements of voltage in the energized winding and of a good consistency between low-voltage onsite measurements and
currents in the HV side (I1 ), LV side (I2 ) and stabilizing winding high-voltage factory tests [16,17]. This is an expected result as these
34 A. Ramos, J.C. Burgos / Electric Power Systems Research 144 (2017) 32–40
Table 7
Zero-sequence impedance (T-type) calculation results for transformer #1.
Zero-sequence equiv. circuit (model A) Zero-sequence equiv. circuit (model B1) Zero-sequence equiv. circuit (model B2)
Table 8
Zero-sequence impedance (T-type) calculation results for transformer #2.
Zero-sequence equiv. circuit (model A) Zero-sequence equiv. circuit (model B1) Zero-sequence equiv. circuit (model B2)
Table 9
Zero-sequence impedance (T-type) calculation results for transformer #3.
Zero-sequence equiv. circuit (model A) Zero-sequence equiv. circuit (model B1) Zero-sequence equiv. circuit (model B2)
Table 12
Comparison of the different models’ impedance prediction.
Table 13 5. Conclusions
Comparison of the different models’ mean errors in primary and secondary current
prediction.
Differences in the zero-sequence performance of three-phase
Model Quadratic mean error (QME) three-legged YNynd power transformers when the stabilizing
Transformer #1 Transformer #2 Transformer #3 winding is closed and when it is open is a key factor in assess-
ing the need for this winding. This performance is determined by
A 7.7% 3.8% 1.2%
B 0.8% 1.3% 0.8% zero-sequence flux circulation inside the transformer under dif-
C 2.3% 1.7% 1.3% ferent network operating conditions, meaning that internal design
features such as the relative position of the windings (HV, LV and
stabilizing) or the presence of magnetic shields in the tank are of
Table 14 great importance.
Comparison of the different models’ mean errors in stabilizing winding current This paper proposed taking a complete set of onsite low-voltage
prediction. zero-sequence measurements to obtain overall information about
Model Quadratic mean error (QME)
the zero-sequence performance of the three most frequent design
types found in core-form power transformers, complementing the
Transformer #1 Transformer #2 Transformer #3
results published by the authors in Ref. [16].
A 29.2% 16.0% 23.0% Based on these measurements, the parameters of different
B 27.0% 9.3% 11.4% equivalent circuits were calculated using a set of equations and an
C 2.3% 2.2% 2.0%
optimization process. These circuit models comprised two T-type
equivalent circuits (the simpler option commonly used in represen-
tation of transformers in power system analysis tools) and a more
complex six-branch equivalent circuit.
current circulation when zero-sequence voltages are applied to the For the T-type models, the model whose parameters are differ-
transformer [10]. For example, in case of zero-sequence voltages ent depending on whether the stabilizing winding is closed or open
applied to HV winding, HV ampere-turns should be balanced with was more accurate than the alternative with common parameters
LV ampere-turns, stabilizing winding ampere-turns and ampere- in all cases. Separate T-type zero-sequence equivalent circuits usu-
turns from tank currents. This last term (ampere-turns from tank ally produce a complete and sufficiently accurate description of the
currents) is not taken into account by model B, as this is a T-type zero-sequence behavior of YNynd transformers for all stabilizing
model (see Fig. 4—B1).
38 A. Ramos, J.C. Burgos / Electric Power Systems Research 144 (2017) 32–40
Table 15
Comparison of the different models’ current prediction for transformer #1.
Table 16
Comparison of the different models’ current prediction for transformer #2.
winding operation options. Nevertheless, in some cases, stabilizing a precise evaluation of internal transformer currents (especially
winding current prediction showed errors, though of slight signif- circulating current inside the delta stabilizing winding) is required.
icance. It should be noted that in case of no load condition and These experimental data and results will be of great use in analy-
stabilizing winding open, non-linearity of magnetizing impedances sis of tank overheating hazard and short-circuit duty in three-phase
can introduce a certain error in the use of the models. three-legged YNynd power transformers, which will be addressed
The six-impedance equivalent circuit supposes greater com- in the companion paper (Part II) to this study.
plexity both in obtaining the parameters and in calculating circuit
currents. Nevertheless, this option offers greater accuracy when
A. Ramos, J.C. Burgos / Electric Power Systems Research 144 (2017) 32–40 39
Table 17
Comparison of the different models’ current prediction for transformer #3.
[2] J.F. Peters, Harmonics in transformer magnetizing currents, AIEE Trans. 34 [15] T. Ngnegueu, M. Mailhot, A. Munar, Zero-phase impedance and tank heating
(September) (1915) 2157–2182. model for three-phase three-leg core type transformers coupling magnetic
[3] L.N. Robinson, Phenomena accompanying transmission with some types of field and electric circuit equations in a finite element software, IEEE Trans.
star transformer connections, AIEE Trans. 34 (September) (1915) 2183–2195. Magn. 31 (May (3)) (1995) 2068–2071.
[4] J.F. Peters, M.E. Skinner, Transformers for interconnecting high-voltage [16] A. Ramos, J.C. Burgos, et al., Determination of parameters of zero-sequence
transmission systems for feeding synchronous condensers from a tertiary equivalent circuits for three-phase three-legged YNynd transformers based
winding, AIEE Trans. 40 (June) (1921) 1181–1199. on onsite low-voltage tests, IEEE Trans. Power Deliv. 28 (July (3)) (2013)
[5] J. Mini Jr, L.J. Moore, R. Wilkins, Performance of auto transformers with 1618–1625.
tertiaries under short-circuit conditions, AIEE Trans. 42 (October) (1923) [17] A. Ramos, Consideraciones acerca de la Utilización de Arrollamientos de
1060–1068. Estabilización en Transformadores Estrella-Estrella (in Spanish). Pd. D.
[6] R.O. Kapp, A.R. Pearson, The performance of star–star transformers, J. Inst. Dissertation, Universidad Carlos III de Madrid, 2016.
Electr. Eng. 1 (January (6)) (1955) 9–12. [18] M.F. Lachman, Y.N. Shafir, Influence of single-phase excitation and
[7] B.A. Cogbill, Are stabilizing windings necessary in all Y-connected magnetizing reactance on transformer leakage reactance measurement, IEEE
transformers? AIEE Trans. Power Appar. Syst. 78 (October (3)) (1959) Trans. Power Deliv. 12 (October (4)) (1997) 1538–1546.
963–970. [19] S.V. Kulkarni, S.A. Khaparde, Transformer engineering, in: Design and Practice,
[8] O.T. Farry, Tertiary windings in autotransformers, AIEE Trans. Power Appar. Marcel Dekker, 2004.
Syst. 80 (April (3)) (1961) 78–82. [20] A. Ramos, J.C. Burgos, Influence of stabilizing windings on zero-sequence
[9] A.N. Garin, Zero-phase sequence characteristics of transformers. Part I: performance of three-phase three-legged YNynd transformers. Part II: tank
sequence impedances of a static symmetrical three-phase circuit and of overheating hazard and short-circuit duty, Electr. Power Syst. Res. XXXX. (in
transformers, Gen. Electr. Rev. 43 (March (3)) (1940) 131–136. revision).
[10] A.N. Garin, Zero-phase sequence characteristics of transformers. Part II: [21] N. Chiesa, B.A. Mork, H.K. Høidalen, Transformer model for inrush current
equivalent circuits for transformers, Gen. Electr. Rev. 43 (April (4)) (1940) calculations: simulations, measurements and sensitivity analysis, IEEE Trans.
174–179. Power Deliv. 25 (October (4)) (2010) 2599–2608.
[11] K. Schlosser, Die Nullimpedanzen des Voll- und des Spartransformatoren [22] IEC Std. 60076-8, Power Transformers, Part 8: Application Guide. 1997.
(Zero-sequence impedance in transformers and autotransformers), [23] IEEE Std. C57.12.90, IEEE Standard Test Code for Liquid-Immersed
Brown-Boveri-Nachr. 44 (February) (1962) 78–83 (in German). Distribution, Power and Regulating Transformers, 2010.
[12] M. Christoffel, Zero-sequence reactances of transformers and reactors, Brown [24] D. Marquardt, An algorithm for least-squares estimation of nonlinear
Boveri Rev. 52 (November/December (11/12)) (1965) 837–842. parameters, J. Soc. Ind. Appl. Math. 11 (2) (1963) 431–441.
[13] K.P. Oels, Ersatzschaltungen des Transformators für das Nullsystem
(Zero-Sequence Equivalent Circuits for Transformers) ETZ-A Bd, 89, 1968, pp.
59–62 (in German).
[14] R. Allcock, S. Holland, L. Haydock, Calculation of zero-phase sequence
impedance for power transformers using numerical methods, IEEE Trans.
Magn. 31 (May (3)) (1995) 2048–2051.