E560 Cmu01 DS
E560 Cmu01 DS
E560 Cmu01 DS
Data Sheet
Communication Unit 560CMU01
Characteristics
The two microprocessors are the essential
hardware parts of the board, which share
themselves in the tasks:
MPU: 32 Bit Main Processing Unit
SLC: 8 Bit Serial Line Controller
The SLC works as master for the RTU560 serial
Application I/O bus (local I/O-Interface/Wired-OR-Bus).
The MPU is responsible for the other tasks. The
The 560CMU01 is the Communication Unit (CMU) MPU handles the absolute time and date for the
of the remote terminal unit RTU511 for DIN rail RTU. The time can be set and synchronized from
mounting. It is designed to be used together with the central system via the serial lines or via the
DIN rail I/O devices (e.g. 23BI61, 23BO62 or Ethernet LAN interface.
23AI60).
The essential tasks of the 560CMU01 are:
Managing and controlling of the I/O
boards via the interface to the RTU560
serial I/O bus (local I/O-Interface/Wired-
OR-Bus).
Reading Process events from the input
boards.
Writing commands to the output boards.
Communicating with control centers and
local HMI systems via the integrated
serial line interfaces and the implemented
Ethernet 10/100BaseT LAN interface.
Managing the time base for the RTU560
station and synchronizing the I/O boards.
Handling the dialogue between RTU560
and Web-Browser via LAN interface.
The Communication Unit 560CMU01 will be
Figure 1: Function block diagram 560CMU01
mounted in a DIN rail housing, together with the
Power Module 560PSU10, and the DIN rail I/O
modules.
The control unit stores configuration files power 560CMU01 indicates operational and error states
fail save in a removable Compact Flash memory by light emitting diodes on the front plate. The
card. That allows the RTU560 to have valid exact definition for the LED has to be taken from
configuration data after power on and RTU560 will the functional description of the RTU560 releases.
be available again after a short initialization.
The serial communication interfaces ERR (1x) red Error / Warning
Communication Port ‘1’ Tx (3x) green Transmit data,
Communication Port ‘2’ communication
ports 1, 2, A
are based on a USART (universal
synchronous/asynchronous receiver/transmitter) Rx (3x) green Receive data,
and designed for RS232C standard. communication
ports 1, 2, A
The serial communication interface CPA is
designed for RS485 standard. A (1x) green Ethernet
activity
The interface ‘E’ is based for the Ethernet
standard 10BaseT/100BaseT. L (1x) green Ethernet link
The connectors of the serial and Ethernet WOR (2x) green Wired-OR-Bus
communication interfaces are provided as RJ45 activity
jacks.
The RTU560 serial I/O bus (local I/O-Interface
/Wired-OR-Bus) is connected via two 20-pole
pluggable connectors (X31 and X32).
Interface to
Interface to
560PSU10
PSU 10
Technical Data
In addition to the RTU500 series general technical
data, the following applies:
Note:
We reserve the right to make technical changes or modify the contents
of this document without prior notice. With regard to purchase orders,
the agreed particulars shall prevail. ABB AG does not accept any
responsibility whatsoever for potential errors or possible lack of
information in this document.
We reserve all rights in this document and in the subject matter and
illustrations contained therein. Any reproduction, disclosure to third
parties or utilization of its contents - in whole or in parts –is forbidden
without prior written consent of ABB AG.