Legend:: This Site
Legend:: This Site
Legend:: This Site
11200
CITY OF CARCAR
OFFICE OF THE BUILDING OFFICIAL
TRIUMPHANT CROSS
MEMORIAL PARK RECOMMENDING APPROVAL
HEAD DATE
POWER SOURCE
220V, 1Ø, 60HZ
THIS SITE
S1 S2 kHM JHONDORF
SUBDIVISION
S2
S2
2-8.0mm² THHN
MUNICIPAL
CEMETERY
BUILDING OFFICIAL DATE
PB
S2 MANCAO
VILLAGE
C1
S1
60AT 2P
SIERVAS
S2
MOTHER MARY'S
10000
D
A
C7 C8
O
R
GAISANO
N
30 AT 2P SPARE
IO
LEGEND:
S
R
E
IV
C9
D
SPARE CCC
LP PANEL BOARD
S2 S3 C2 2-5.5mm² THW
POB. I C# CIRCUIT HOME RUN
BRGY HALL
CITY HALL CIRCUIT LINE
GROUND
CARCAR TOWN PLAZA CARCAR CENTRAL
S2 ACADEMY SWITCH LINE
SCHOOL
03 ONE LINE DIAGRAM CWD
CITY PUBLIC MARKET
LO LINE
NOT TO SCALE BRATO
06-07
CO LINE
CARCAR ROTUNDA
C3 12W DOWN LIGHT
8W CP LIGHT
01 LIGHTING LAY-OUT 04 LOCATION PLAN
SCALE 1:75MTRS NOT TO SCALE
06-07 06-07 REFRIGERATOR CONVENIENCE OUTLET
REF
S1 1 GANG SWITCH
S2 2 GANG SWITCH
S3 3 GANG SWITCH
PB
±0.80M ELEV ON FILL
PROTECTION
REF CKT.NO LOAD DESCRIPTIONS VA PHASE VOLT AMP SIZE OF WIRE SIZE OF
C6 AT P AF CONDUIT
C4 7 - 180W DUPLEX CONV. OUTLET 1260 1Ø 220 5.73 20 2 50 2-5.5mm² THHN 15mmØ
GENERAL SPECIFICATION:
10000
C5 7 - 180W DUPLEX CONV. OUTLET 1260 1Ø 220 5.73 20 2 50 2-5.5mm² THHN 15mmØ
ALL WIRING INSTALLATION SHALL CONFORM TO THE LATEST REVISED EDITION OF THE
C6 1 - 32W REF OUTLET 32 1Ø 220 0.15 20 2 50 2-5.5mm² THHN 15mmØ NATIONAL ELECTRICAL CODE OF THE PHILIPPINES AND IN CONFORMITY WITH THE
LOCAL REQUIREMENTS OF THE MUNICIPAL ENGINEERING SAFETY SECTION.
C7 AIR CON. UNIT (2H) 1492 1Ø 220 6.78 30 2 50 2-5.5mm² THHN 15mmØ
C7 ALL WIRES PASSING THRU CONCRETE OR CHB.WALL SHALL BE ENCLOSED WITH PVC
C8 SPARE - - - - - - CONDUIT PIPE
C9 SPARE - - - - - -
ALL WIRES PASSING THRU WOODEN STRUCTURES SHALL BE OPEN THRU THE USE OF
INCOMING 220V TOTAL LOAD CURRENTS 4252 19.33 PORCELAIN SPLIT KNOBS.
MAIN SIZE OF WIRE COMPUTATION MAIN PROTECTION SIZE COMPUTATION LOCATION OF LIGHT SWITCHES SHALL BE 1.50 m. HIGH FROM F.F.L AND CONVENIENCE
IP = [ (IT ) (250%) ] OUTLET SHALL BE 0.30 HIGH FROM F.F.L.
IC = [ (IT ) + (IH )(125%) ]
= (19.33) + (6.78)(1.25) = (19.33) (2.5) ALL MATERIALS TO BE USED HEREIN SHALL BE BRAND NEW AND OF APPROVED
= 28 Amps = 48 Amps STANDARD TYPE.
USE : 2-22mm² THHN, STRANDED COPPER WIRE AND USE: 60AT 2P, 100AF, 1-Ø, 10kaic
1-5.5mm² THW, GROUNDING WIRE IN 25MMØ uPVC PIPE BOLT-ON TYPE CIRCUIT BREAKER ALL ELECTRICAL INSTALLATIONS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF
A DULY LICENSED PROFESSIONAL ELECTRICAL ENGINEER.
02 POWER LAY-OUT INDICATED ELECTRICAL DISTRIBUTION LINE ARE FOR ESTIMATE PURPOSE ONLY. FINAAL
DISTRIBUTION INSTALLATION WILL BE DONE BY THE LOCAL UTILITY CONCERNED AND
SCALE 1:75MTRS
06-07 WILL DEPEND ON ACTUAL LOAD REQUIREMENTS.
SIGNED & SEALED BY : SEAL REP. ACT 9266 SEC.33 PROJECT TITLE : PROJECT OWNER : SHEET CONTENT: SHEET NO.