EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
EDMS 08-400-01
SPECIFICATION
FOR
(Indoor-Outdoor)
Issue: May.-2023 / Rev- 1
This revision contains option items that must be selected by …EDC before bidding.
EDMS 25-401 for Mineral Insulating Oil shall be attached.
EDMS 11-400 for Outdoor Surge Arrester shall be attached if applicable.
EDMS 26-200 for Neutral Grounding shall be attached.
EDMS 25-400 for SELF INDICATING ORANGE SILICA GEL CRYSTALS shall be attached.
Page 1 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
CONTENTS
Clause Description Page
1 SCOPE 3
2 APPLICABLE STANDARDS 3
3 SERVICE CONDITIONS 4
4 DESIGN CRITERIA 4
5 TRANSFORMER LOSSES 14
6 MARKING 16
7 TESTING and INSPECTION 16
8 SUBMITTALS 19
9 GUARANTEE 20
10 TECHNICAL DATA SCHEDULE 21
11 االشتراطات 21
Page 2 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
1. SCOPE
This specification covers the general requirements of design, manufacture,
testing, supply and delivery of (22/11 KV or 11/22 KV), three-phase, two-
windings oil immersed (Step-up or Step-down) power transformers with on load
tap changer and local / remote tap change control panels rated up to 30 MVA at
(ONAN/ONAF) Cooling. The transformers shall be suitable for indoor /outdoor
installations of the power networks of Egyptian Electricity Distribution
Companies (…EDCs).
2. APPLICABLE STANDARDS
The equipment/material covered in this specification shall comply with the latest
edition/amendment of the standards given in Table (1). Where any provision of
this specification differs from those of the standards listed below, the provisions
of this specification shall apply. Any deviations from the listed standards or the
provisions of this specification shall be clearly set out in the offer.
Table (1)
Standard
Description
No.
Part 1 General.
Part2 Temperature rise for liquid immersed transformers.
IEC 60076 Part3 Insulation levels and dielectric tests and external clearance in air.
power
transformer Part 5 Ability to withstand short circuit.
Part7 Loading guide for oil-immersed power transformers.
Part 10 Determination of sound levels.
Page 3 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
3. SERVICE CONDITIONS
The electrical and mechanical properties of the required transformers should be
guaranteed under the environmental conditions given in Table (2).
Table (2)
Minimum
-5 °C
ambient temperature
Maximum relative 95 %
humidity
Altitude Up to 1000 m above sea-level
4. DESIGN CRITERIA
4.1. Rated Power
The transformer should be able to deliver for an unlimited period of time at the
main tapping of the tap changer, without exceeding the allowable temperature
rise limit, if the applied voltage is equal to the rated voltage and maintained at
its rated frequency.
The maximum continuous power rating is selectable from the following set of
standard rates:
(2.5MVA-5MVA- 10MVA -15MVA -20MVA-25MVA-30MVA)
4.2. Voltage Ratio
The ratio of the transformers should be (11KV /22KV) OR (22KV/11KV)
according to….. EDC requirement.
The deviation of the transformation ratio measured at no-load and 50 Hz should
not exceed 0.5% from its nominal value.
Page 4 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
Tap No 1 2 3 4 5 6 7 8 9
Voltage
+5 +2.5 0 -2.5 -5 -7.5 -10 -12.5 -15
Regulation%
4.5. Overload Capacity
Permissible overload capacity starting from full load 10 % for 2 hr and 20% for
30 min. (without exceeding the permissible heating).
Page 5 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
4.8. Cooling
Cooling type shall be one of the following options (according to…EDC
requirements)
1. ONAN for 100% rated power.
2. ONAN for 100% rated power and ONAF for 120% rated power
3. ONAN for 80% rated power and ONAF for 100% rated power
4.9. Insulation Level
The following test voltages shall be applicable to the transformer: -
5MVA 7%
10 MVA 8%
15 MVA 8%
20MVA 8%
25MVA 8%
30MVA 10%
Page 6 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
4.11. Bushings
1. The transformer bushings shall be made of porcelain. Generally, it shall comply
with the requirements of IEC 60137.
2. The creepage distance should not be less than 2 cm/kV for indoor transformers
and 4 cm/kV (4.5 cm/KV optional according to ...EDC requirements) for
outdoor transformers.
3. To avoid overvoltage damage each high voltage bushing should be fitted with
a duplex arcing horn electrodes made of steel. The vertical distance of arcing
horn should be set at (155 mm for 22 K.V/86 mm for 11 K.V) according to
VDE0111/261.
4. Neutral bushings should be mounted on the tank cover in a manner such that the
minimum phase to phase clearance and phase to earth clearance should not be
less than those stated in IEC 60076.
5. The porcelain should not engage directly with the hard metal and gasket should
be interposed between them and the surface in contact with the gasket should
be unglazed.
6. The neutral bushings and stems should be identical to those provided for phase
terminations.
7. Bushing palms should be made of brass and be suitable for the bolting of
conductor compression lugs.
4.12. Core
1. The core should be made of low loss steel lamination which are made of cold
rolled grain oriented, annealed, high permeability, non-ageing, silicon steel
type.
2. The lamination should be insulated with suitable varnish or paint, solid
insulation is not acceptable.
3. The core, framework, clamping arrangement & general structure should be
mechanically robust to withstand any shocks to which they may be subjected
during transport, installation, service & faults.
4. The core construction should ensure the efficient cooling of its internal parts,
the elimination of core vibration when loaded and the minimization of
harmonic voltage especially the third harmonics.
Page 7 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
Page 8 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
7. The transformer tank should be made of best quality plate steel with bolted
cover.
8. Pockets should be provided for a stem type thermometer and for the bulbs of
temperature indicators where specified. These pockets should be located in
the position of maximum oil temperature and it must be possible to remove
any bulb without lowering the oil level in the tank.
9. Captive screwed caps should be provided to prevent the ingress of water to
the thermometer pockets when they are not in use.
4.15. Oil expansion conservator
1. The transformer should be provided with overhead conservator tank,
connected to the main tank as well as the tap changer tank at the highest point
to prevent the trapping air or gas under the main tank cover.
2. The conservator should be made of sheet steel with an adequate capacity to
allow for the extreme expansion of oil level e.g. from ambient temperature to
at least 100oC.
3. Conservator should have a capacity between highest and lowest indicated oil
levels of not less than 7.5% of the total cold oil volume in the transformer and
its associated cooling equipment( For rated power >5 M.V.A).
4. The conservator is provided with the following:
a) Oil level indicator with two contacts for maximum and minimum levels
with sight glass(optional For rated power 2.5M.V.A).
b) silica-gel shall meet the requirements of EDMS 25-400.
c) Oil filling and drain plugs and a connection pipe for connecting the oil
to the transformer.
4.16. Transformer Oil
1. The oil should meet the requirements of the latest revision of EDMS 25-401.
4.17. Valves
1. The transformer should be fitted with necessary valves at the following
locations for filling, draining, filtering, conservator isolation etc.
Page 9 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
3. All valves should have visual indication of “Open” and “Shut” and should
be labeled as to their function.
4. All valves which are mounted near the base of the transformer should have
Page 10 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
Page 11 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
Page 12 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
4.24. Accessories:
The transformer shall be provided with the following accessories:
1. Buchholz relay with alarm and trip contacts for detection of any internal fault
inside the transformer tank.
2. The OLTC should be equipped with a separate tank protected by dependent
Page 13 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
Buchholz relay.
3. WTI and OTI for transformers (For rated power>10 M.V.A).
4. Dial type thermometer with two contacts (in case the transformer doesn’t
contain OTI)
5. Pressure relief device of trip contacts for rated power > 2.5 MVA (optional
according to …. EDC requirements)
6. Drain valve complete with control tap.
7. Welded lifting shackles.
8. Tank earthing, M 10 stud with nut shall be used.
9. Name plate.
10. Radiator
4.25. Wheels
1. The enclosure base should be fitted with four bi-directional wheels to
facilitate moving of the transformers during installation in two perpendicular
directions.
Where:
K= Present worth factor (L.E)
K = ((1+i)N-1 / i(i+1)N)).
I: latest interest rate from Central Bank of Egypt.
N: number of years (20 years).
Page 14 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
C= Cost of KWH (According to the max commercial cost of KWH and can
be adjusted as per EEHC latest update).
LS.F= Loss factor for the load = 0.4
Wi = Iron (no load) losses in KW at rated voltage and main tapping
Wcu = copper (Load) losses in KW at full load and (95ºC at main tapping)
P= Peak load (P.U.) = 0.8
The values of the required losses are given in Table (4)
Table (4)
6. MARKING
Transformer serial No. and rated power should be engraved on tank cover at LV
side.
Each transformer should be fitted with a name plate of weather proof materials
fitted in a visible position, showing the information listed below. Entries on the
plate should be indelibly marked by etching or engraving:
Page 15 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
The type tests should include and not limited to the following:
1. Full wave lightning impulse voltage withstand test. IEC 60076
2. Temperature rise test. IEC 60076
3. Chemical oil tests.
7.2. Routine Tests:
These tests shall be applied on each transformer in accordance with the
requirements of IEC standards for transformers, these shall include the following:
Page 16 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
Page 17 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
Where:
Page 18 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
Page 19 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
: االشتراطات.11
-:تلتزم الشركة الموردة بتنفيذ اآلتي بعد التوريد و قبل إطالق التيار الكهربائي علي المحوالت
إرسال أحد المختصيين لإلشراف علي كل من عملية التركيب ( أجزاء المحول – مغير الجهد و لوحة-أ
. و إختبارات التدشين و اإلختبارات الروتينية بالموقع، ) التحكم الخاص به
تدريب المهندسين و الفنيين علي عمليات التشغيل و الصيانة-ب
Page 20 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
1- Manufacturer
2- Type
3- Standard specification
5- Vector group
7- Method of cooling
8- Oil type
9- Material of insulation
ـ HV winding
ـ LV winding
14- Load losses at full load current / 95ºC winding temperature (Watts)
Page 21 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
17- Permissible symmetrical S.C current at L.V side terminals for 2sec
(KA)
18- Primary voltage at normal tapping (volts)
Page 22 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
ـNo. of steps
ـLength of leakage ( mm )
Page 23 of 24
Ministry of Electricity and Renewable Energy وزارة الكهرباء والطاقة المتجددة
Egyptian Electricity Holding Company الشركة القابضة لكهرباء مصر
EDMS 08-400-01
EEHC DISTRIBUTION MATERIALS SPECIFICATION
9-5-2023
I/we guarantee the correctness of above data for transformers we are offering to
Customer Company for Distributing Electricity.
Date: / /
Page 24 of 24