F&G - Controller
F&G - Controller
F&G - Controller
1. Input Scan: Identifies the status of all input devices that are connected to the PLC.
2. Program Scan: Implements the user-created program logic.
3. Output Scan: Either energizes or de-energizes all connected output devices.
4. Housekeeping: This includes communications with programming terminals and internal
diagnostics.
What are input/output devices?
Input Device: An input device is a piece of computer hardware equipment used to provide
data, and control signals to an information processing system (IPS).
Some examples of input devices include:
Valves
Motor starters
Horns and alarms
Stack lights
Control relays
Pumps
Printers
Fans
What are the fundamentals of a PLC system?
CPU or processor: The Central Processing Unit, or main processor, is a microprocessor-
based system. It executes the control program after reading field input status, then sends
out commands to field outputs.
I/O section: I/O modules act as the Real Data Interface between field and CPU. A PLC
knows the real status of field devices and controls them with relevant I/O cards.
Programming device: CPU cards can be connected with programming devices through a
communication link via a programming port on the CPU.
Operating station: An operating station is used to provide an “operating window” to the PLC
process. It is generally a separate device, like a PC, that is loaded with Human Machine
Interface Software.
Operational Sequence
PLCs operate by continually scanning programs and repeat this process many times per
second. When a PLC starts, it runs checks on the hardware and software for faults, also
called a self-test. If there are no problems, then the PLC will start the scan cycle. The scan
cycle consists of three steps: input scan, executing program(s), and output scan.
Input Scan: A simple way of looking at this is the PLC takes a snapshot of the inputs and
solves the logic. The PLC looks at each input card to determine if it is ON or OFF and saves
this information in a data table for use in the next step. This makes the process faster and
avoids cases where an input changes from the start to the end of the program.
Execute Program (or Logic Execution): The PLC executes a program one instruction at a
time using only the memory copy of the inputs the ladder logic program. For example, the
program has the first input as ON. Since the PLC knows which inputs are ON/OFF from the
previous step, it will be able to decide whether the first output should be turned ON.
Output Scan: When the ladder scan completes, the outputs are updated using the
temporary values in memory. The PLC updates the status of the outputs based on which
inputs were ON during the first step and the results of executing a program during the
second step. The PLC now restarts the process by starting a self-check for faults.
Figure 1: PLC Scan Cycle
Logic Scan
Ladder logic programs are modeled after relay logic. In relay logic, each element in the
ladder will switch as quickly as possible. Program elements can only be examined one at a
time in a fixed sequence. The ladder logic scan begins at the top rung. At the end of the
rung, it interprets the top output first, and then the output branched below it. On the second
rung, it solves branches, before moving along the ladder logic rung.
PLC means Programmable Logic Controller. It is a class of industrially hardened devices that
provides hardware interface for input sensors and output control element. The field I/p include
element like limit switches, sensors, push button and the final control elements like actuator,
solenoid/control valves, drives, hooters etc.
PLC Senses the input through I/P modules, Processes the logic through CPU and memory and
gives output through output module.
Applications Of PLC?
PLC can be used in almost all industrial application solutions right from small machine to large
manufacturing plants. Even it caters applications of redundant systems at critical process plants.
PLC plays most important role in automation. All the monitoring as well as the control actions are
taken by PLCs. PLC Senses the input through I/P modules, Processes the logic through CPU and
memory and gives output through output module.
CPU consist of Arithmetic Logic Unit, Program memory, Process image memory, Internal timers and
counters, flags It receives information from I/P device, makes decisions depending upon the
information and logic written and sends information through the O/P devices.
Memory capacity
Instruction set supported
communication option
time required to execute the control program.
Power supply provides system power requirement to processor, I/O and communication modules.
Typically the power supply has input voltage 120 V – 230 V AC or 24 V DC and back plane output
current 2 A to 5 A at 5 V DC
A hardware assembly, which houses the processor, communication and I/O modules.
Power distribution
Containment of I/O modules
Communication path between I/O module and CPU
The chassis are available in different slots in various PLC systems. Additional chassis can be
connected using chassis interconnecting cable.
Electronic plug in units used for interfacing the i/p and o/p device in the machine or process to be
controlled.
I/P module receives data from i/p devices (Pushbutton, Switches, Transmitters) and send it to
processor. The O/P module receives data from processor and send it to output device (Relay,
Valves).
This module is inserted into processor system for maintaining a copy of project (PLC program). This
is helpful in case of memory corruption or Extended power loss.
In non modular PLCs the processor will have inbuilt power supply and I/Os in one unit.
The modular PLC, will have separate slots for components like Power supply, I/O modules. You can
select the I/Os or power supply as per the need.
Local – These are the I/Os placed in the PLC main rack containing CPU. These I/Os are connected
to CPU through backplane.
Distributed/Remote – These are the I/O placed at remote location from the main rack containing
the CPU.
These I/O’s are to be connected on communication bus like control net, device net or FIP I/O.
It is the minimum change in i/p parameter which can sensed by the i/p card. As far as Digital I/O is
concerned it takes only one bit for operation. In case of analog input the resolution determines how
much bits are used for input or output. For example a 12 bit resolution card means the input will
come as 0 to 4095 count (2^12). For 16 bit data the counts will be from 0 – 65536(2^16). More the
resolution the data will be more accurate
An I/O module that contains circuits that output an analog dc signal proportional to a digital value
transferred to the module from the processor. By implication, these analog outputs are usually direct
(i.e., a data table value directly controls the analog signal value).
Normally there are different cards for different signals. But in universal input card the same channels
can be configured for RTD, Thermocouple, Current or voltage input.
Sinking Source type modules gives out the current to the field digital devices while sink type
modules draw current when the device is in high state
Sinking – When active the output allows the current to flow to a common ground.
Sourcing – When active, current flows from a supply, through the output device and to ground.
Forcing the I/Os means making the desired status of I/O in PLCs irrespective of its status coming
from the field.
In certain cases when there is problem in receiving field input /output, we can force the i/Os so that
the logic takes desired state.
Scan time is the Time required to read the I/P, Process the logic and update the output in one cycle.
Typically it is less than 10 ms. It depends on the complexity of logic, PID algorithm etc.
This is a programming language, which expresses a program as a series of “coils” and “contacts”,
simulating the operation of electromechanical relays. The resultant program is the equivalent of an
equation, which is executed continuously in a combinatorial manner.
The advantage of this language is the familiarity many electricians have with the simple operation of
relays. Disadvantages include the complexity of large, cross-connected programs, and the difficulty
of expressing such non-binary functions as motion control and analog I/O.
What Is Redundancy ?
The capacity to switch from primary equipment to standby equipment automatically without affecting
the process under control. Redundancy means provision for standby module. In case of failure of
one module is running process, the standby module takes over. Hot redundancy means the
changeover of control from active processor to standby processor in less than 1 scan time.
In critical processes, it is important to run the plant without failure. In such case it is important to
have redundancy so that even if one system fails the redundant system can take care without
affecting plant.
CPU redundancy: In case of CPU failure the standby CPU takes care of the plant
Power Supply redundancy: In case the power supply fails the standby power supply takes control of
the situation.
I/O Redundancy : Multiple I/O channels are provided to take care of input or output failure.
Power Supply
Controller with built-in Modbus Plus and Modbus ports
Optional dual cable Modbus Plus
Optional fiber optic Modbus Plus
CHS Hot Standby module
Dual cable Remote I/O Head
Sinking Source type modules gives out the current to the field digital devices while sink type
modules draw current when the device is in high state
Sinking – When active the output allows the current to flow to a common ground.
Sourcing – When active, current flows from a supply, through the output device and to ground.
https://instrumentationtools.com/pid-controllers-multiple-choice-questions/
https://instrumentationtools.com/feedforward-control-questions-answers/
https://instrumentationtools.com/feedback-control-loop-questions-answers/
https://instrumentationtools.com/fire-and-gas-system-interview-questions-answers/
https://instrumentationtools.com/interview-questions-on-fire-detection-syste/