Data Sheet 6ES7636-2EB00-0AE3: Operator Control and Monitoring
Data Sheet 6ES7636-2EB00-0AE3: Operator Control and Monitoring
Data Sheet 6ES7636-2EB00-0AE3: Operator Control and Monitoring
Display
Design of display CSTN, CCFL backlit; 10.4" color (256 colors)
Resolution (pixels)
● Horizontal image resolution 640 Pixel
● Vertical image resolution 480 Pixel
Backlighting
● MTBF backlighting (at 25 °C) 60 000 h
Control elements
Touch operation
● Design as touch screen Yes
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Digital inputs
— Rated value (DC) 24 V
— Reverse polarity protection Yes
Digital outputs
— Rated value (DC) 24 V
— Reverse polarity protection Yes
Analog outputs
— Rated value (DC) 24 V
— Reverse polarity protection Yes
Input current
Current consumption, typ. 650 mA; idling
Current consumption, max. 1.5 A
Inrush current, max. 3 A; 3 A for 10 ms, then 2 A for 70 ms
Digital inputs
● from load voltage L+ (without load), max. 70 mA
Digital outputs
● from load voltage L+, max. 20 mA; per group
Power loss
Memory
Micro Memory Card Yes
Work memory
● integrated 128 kbyte
● expandable No
Load memory
● Plug-in (MMC) Yes
● Plug-in (MMC), max. 8 Mbyte
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
● with battery Yes; Option for the panel
● without battery Yes; Program and data of the CPU
Battery
Backup battery
● Backup battery (optional) Yes
CPU-blocks
DB
● Number, max. 1 023; DB 0 reserved
● Size, max. 16 kbyte
FB
● Number, max. 2 048; see instruction list
● Size, max. 16 kbyte
FC
● Number, max. 2 048; see instruction list
● Size, max. 16 kbyte
OB
● Number, max. see instruction list
● Size, max. 16 kbyte
Nesting depth
● per priority class 8
● additional within an error OB 4
Address area
I/O address area
● Inputs 2 kbyte
● Outputs 2 kbyte
of which distributed
Hardware configuration
Number of modules per system, max. 23
Number of DP masters
● integrated 1
● via CP 1
Number of operable FMs and CPs (recommended)
● FM 8
● CP, PtP 8
● CP, LAN 10
Expansion modules
● Number of expansion modules, max. 4; max. 2 flat arrangement, max. 4 deep arrangement, max. 23 via
IM
Rack
● Racks, max. 4
● Modules per rack, max. 8; Modules in subrack 0: 4 max.; modules in subracks 1 and 2: 8
max.; modules in subrack 3: 7 max.
● Number of lines, max. 4
Time of day
Clock
● Hardware clock (real-time) Yes
● retentive and synchronizable Yes
Digital inputs
Number of digital inputs 24
● of which inputs usable for technological 16
functions
Input characteristic curve in accordance with IEC Yes
61131, type 1
Number of simultaneously controllable inputs
horizontal installation
— up to 40 °C, max. 12
vertical installation
— up to 40 °C, max. 18
Input voltage
● Rated value (DC) 24 V
● for signal "0" -3 to +5V
● for signal "1" +15 to +30V
Input current
● for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.1 / 0.3 / 3 / 15 ms
— Rated value 3 ms
for technological functions
— at "0" to "1", max. 8 µs
Cable length
● shielded, max. 1 000 m; 100 m for technological functions
● unshielded, max. 600 m
for technological functions
— shielded, max. 50 m; at maximum count frequency
— unshielded, max. not allowed
Analog inputs
Number of analog inputs 4
● For voltage/current measurement 4
● For resistance/resistance thermometer 1
measurement
integrated channels (AI) 4; + 1 AI
permissible input voltage for current input 2.5 V; max. 2.5 V permanent; max. 24 V for short time
(destruction limit), max.
permissible input voltage for voltage input 30 V; Permanent
(destruction limit), max.
permissible input current for voltage input 0.5 mA; Permanent
(destruction limit), max.
permissible input current for current input (destruction 50 mA; Permanent
limit), max.
No-load voltage for resistance-type transmitter, typ. 2.5 V
Constant measurement current for resistance-type 1.8 to 3.3 mA
transmitter, typ.
Technical unit for temperature measurement Yes; Degrees Celsius / degrees Fahrenheit / Kelvin
adjustable
Input ranges
● Voltage Yes
● Current Yes
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● -10 V to +10 V Yes
● Input resistance (-10 V to +10 V) 100 kΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 50 Ω
● -20 mA to +20 mA Yes
● Input resistance (-20 mA to +20 mA) 50 Ω
● 4 mA to 20 mA Yes
● Input resistance (4 mA to 20 mA) 50 Ω
Input ranges (rated values), resistance thermometer
● Pt 100 Yes
● Input resistance (Pt 100) 10 MΩ
Input ranges (rated values), resistors
● 0 to 600 ohms Yes
● Input resistance (0 to 600 ohms) 10 MΩ
Thermocouple (TC)
Analog outputs
Number of analog outputs 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 55 mA
Current output, no-load voltage, max. 17 V
Output ranges, voltage
● 0 to 10 V Yes
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Connection of actuators
● for voltage output two-wire connection Yes; Without compensation of the line resistances
● for voltage output four-wire connection No
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 0.1 µF
● with current outputs, max. 300 Ω
● with current outputs, inductive load, max. 0.1 mH
Destruction limits against externally applied voltages and currents
● Voltages at the outputs towards MANA 16 V; Permanent
● Current, max. 50 mA; Permanent
Cable length
● shielded, max. 200 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire 1.5 mA
sensor), max.
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.06 %
Temperature error (relative to input range), (+/-) 0.006 %/K
Crosstalk between the inputs, min. 50 dB; at Ucm = 0 V
Repeat accuracy in steady state at 25 °C (relative to 0.06 %
input range), (+/-)
Output ripple (relative to output range, bandwidth 0 to 0.1 %
50 kHz), (+/-)
Linearity error (relative to output range), (+/-) 0.15 %
Temperature error (relative to output range), (+/-) 0.01 %/K
Crosstalk between the outputs, min. 60 dB
Repeat accuracy in steady state at 25 °C (relative to 0.06 %
output range), (+/-)
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 1%
● Current, relative to input range, (+/-) 1%
● Resistance, relative to input range, (+/-) 5%
● Voltage, relative to output range, (+/-) 1%
● Current, relative to output range, (+/-) 1%
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.7 %
● Current, relative to input range, (+/-) 0.7 %
● Resistance, relative to input range, (+/-) 3%
Interfaces
Number of printer interfaces 1; serial, USB for panel
MPI
● Cable length, max. 50 m; without repeater
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated No
Power supply to interface (15 to 30 V DC), max. 200 mA
Protocols
● MPI Yes
● PROFIBUS DP master No
● PROFIBUS DP slave No
MPI
● Number of connections 16
● Transmission rate, max. 187.5 kbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client Yes; Via CP and loadable FB
— S7 communication, as server Yes
2. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Number of connection resources 16
Protocols
● MPI No
● PROFIBUS DP master Yes
Communication functions
Global data communication
● Number of GD packets, max. 8
S7 message functions
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 40
Interrupts/diagnostics/status information
Alarms Yes; No interrupts when used as standard I/O; when using the
technological functions, see the manual S7-300 Programmable
Controller, CPU31xC Technological Functions
Diagnostics function No; No interrupts when used as standard I/O; when using the
technological functions, see the manual S7-300 Programmable
Controller, CPU31xC Technological Functions
Integrated Functions
Number of counters 4; 4 channels in total
Counting frequency (counter) max. 60 kHz
Frequency measurement Yes
Number of frequency meters 4; 4 channels in total
controlled positioning Yes
integrated function blocks (closed-loop control) Yes
PID controller Yes
Number of pulse outputs 4; 4 channels in total
Limit frequency (pulse) 2.5 kHz
Potential separation
Potential separation digital inputs
● Potential separation digital inputs Yes
● between the channels No
● between the channels and backplane bus Yes
Potential separation digital outputs
● Potential separation digital outputs Yes
● between the channels Yes
● between the channels, in groups of 8
● between the channels and backplane bus Yes
Potential separation analog inputs
● Potential separation analog inputs Yes
● between the channels No
Isolation
Isolation tested with 500 V DC
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of Yes; ±6 kV contact discharge acc. to IEC 61000-4-2, ESD; ±8 kV
static electricity acc. to IEC 61000-4-2 air discharge acc. to IEC 61000-4-2, ESD
Interference immunity against high-frequency electromagnetic fields
● Interference immunity against high-frequency Yes; 10 V/m, with 80% amplitude modulation at 1 kHz, 80 MHz to
radiation acc. to IEC 61000-4-3 1 GHz (to IEC 61000-4-3); 10 V/m, pulse-modulated 50% duty
cycle at 900 MHz and 1.89 GHz (to IEC61000-4-3)
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to Yes; ±2 kV acc. to IEC 61000-4-4, burst; surge measurements
IEC 61000-4-4 with additional protective elements
● Interference immunity on signal cables acc. to Yes
IEC 61000-4-4
Interference immunity against voltage surge
● on the supply lines acc. to IEC 61000-4-5 Yes; ±1 kV acc. to IEC 61000-4-5, µs pulse/line to line; ±2 kV acc.
to IEC 61000-4-5, µs pulse/line to ground
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high-frequency Yes; 10 V/m, with 80% amplitude modulation at 1 kHz
radiation acc. to IEC 61000-4-6
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes
Ambient conditions
Operating systems
pre-installed operating system
● Windows CE Yes
Configuration
Configuration software
● STEP 7 Yes; V5.2 SP1 HSP or higher
● ProTool Yes; as of V6.0 SP3 with Setup C7-636
● ProTool/Lite Yes; as of version 6.0 SP3 and setup C7-636
● ProTool/Pro Yes; as of version 6.0 SP3 and setup C7-636
● WinCC flexible Compact Yes
● WinCC flexible Standard Yes
● WinCC flexible Advanced Yes
Programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
Languages
Online languages
● Number of online/runtime languages 5
Dimensions
Width 335 mm
Height 275 mm
Depth 100 mm
Mounting cutout, width 310 mm; Tolerance: +1 mm
Mounting cutout, height 248 mm; Tolerance: +1 mm
Weights
Weight, approx. 3 980 g