Rand Refinery

Generator
Installation
Quotation

Date: 9th August 2023


Company: Afritech
Author: Keith Christensen
Cable Selection
 All tables used are referenced from SANS 10142

(A)
1000A Generator

5M (x2) 240mm2 single core

(B) C/B 1 C/B 2 C/B 3


630A 250A 250A

30M (x3) 120mm2 SWA 4


Core
(C)

Take note
C/B 1 is adjustable between 250A to 630A.
C/B 2 and 3 is adjustable between 160A to 250A.
Cable Selection Between A - B
 The single core cable is to be installed on cable ladder
and will be placed flat and touching.

 Option 1
(x2) 240mm2 Single core cable connected in parallel.
According to table 6.2 (a) the current carrying capacity: 504A.
1000A/2 = 500A
According to table 6.2(b) the voltage drop: 0.27mV/A/m
Voltage Drop= mV/A/m x I x L
= 0.27x10-3 x 500 x 5
= 0.675 V
For both cables, 0.675 x 2 = 1.35V

Option 2
(x3) 150mm2 Single core cable connected in parallel.
According to table 6.2 (a) the current carrying capacity: 369A.
1000A/3 = 333.333
According to table 6.2 (b) the voltage drop: 0.34mV/A/m
Voltage Drop= mV/A/m x I x L
= 0.34 x 10-3 x 333.333 x 5
=0.567 V
For three cables, 0.567 x 3 = 1.7V
Cable Selection Between B – C
 The SWA cable will be installed in a cable duct in the
ground.

Option 1
(x2) 240mm2 SWA cable connected in parallel.
According to table 6.8 the current carrying capacity: 344A.
630A/2 = 315A
According to table 6.4(b) the voltage drop: 0.21mV/A/m.
Voltage Drop= mV/A/m x I x L
= 0.21x10-3 x 315 x 30
= 1.98V
For both cables, 1.98 x 2 = 3.97V

 Option 2
(x3) 120mm2 SWA cable connected in parallel.
According to table 6.8 the current carrying capacity: 234A.
630A/3 = 210A
According to table 6.4(b) the voltage drop: 0.35mV/A/m.
Voltage Drop= mV/A/m x I x L
= 0.35 x 10-3 x 210 x 30
= 2.205V
For three cables, 2.205V x 3 = 6.615V
Required Construction Materials List

Quantity/Length Material Cost

X1 Circuit breaker 630A R20 464.00

X2 Circuit breaker 250A R26 168.00

X1 Copper Busbar 300A R2 399.00

X1 Copper Busbar 1000A R8 152.00

X1 Enclosure

X20 Lugs 240mm2 R3 586.00

X40 Lugs 120mm2 R2 764.00

X10 Lugs 70mm2 R349.00

X18 240mm2 Glands R2 664.00

X6 120mm2 Glands R2 898.00

X4 70mm2 Glands R360.00

X2 2.5mm2 Glands R242.00

X6 120mm2 Shrouds R132.00

X2 2.5mm2 Shrouds R44.00

X1 Cable Tray Horizontal Bend R1 148.00

X1 Cable ladder R1 120.00

X1 Cable Clamps R888.00

X18 Straight Connector R320.00

55 Metres Singe Core 240mm2 XLPE Cable

90 Metres SWA 120mm2 4 core Cable R173 610.00

40 Metres Single Core 70mm2 XLPE Cable

30 Metres SWA 2.5mm2 7 core Cable R3 690.00

30 Metres Comms Cable R2 040.00

Labour

Total Amount: