• Precision air conditioning unit for indoor installation for the air
conditioning of IT equipment, data centers, telecommunications
equipment and other operation-critical applications.
• Compact, ready-to-use circulating air conditioning unit (room air
conditioning unit) with integrated microprocessor control.
• Standard functions: cooling mode, dehumidification mode
• CyberAir 3PRO air conditioning units comply with the applicable technical
rules and standards and have CE certification.
• The unit is manufactured an ISO 9001 / ISO 14001 certified company
and thus includes the appropriate inspection, testing, and quality
assurance steps, during the production process, up to the delivery..
• Continuous protection of all ESD-sensitive components due to
manufacturing/production according to EN 61340-5-1 (protection of
electronic devices against electrostatic phenomena).
• Refrigerant: R407C
Principal features:
• CyberAir 3PRO air conditioning units are especially designed for
maximum cost effectiveness and energy efficiency with maximum
availability and reliability.
• high cooling capacity per footprint; Unit dimensions and integrated,
functional components optimised for small, medium and large rooms
• safe, energy-saving control functions and reliable monitoring of
proprietary STULZ microprocessor system
• practice-related, up-to-date design conditions, for refrigeration operation
without latent portion and based on the ASHRAE recommendations
• very low noise emission in operation without disturbing tonal noise
portions
• high flexibility in air flow and unit cooling capacities; wide variety of
options and adaptation to customer-specific requirements possible
• accessibility of all maintenance-related main components from the front
Air circuit:
• Air direction „Downflow"
• Air inlet (air intake/return air) into the A/C unit on a large surface from above
• Vertical, turbulence-free air flow through the unit from top to bottom
• Flow order: Air filter - Heat exchanger - EC fan
• internal arrangement of all flow-related components and sheet metal parts
optimised for low air-side pressure losses and full-surface incident flow of
the heat exchanger or filter surfaces for high performance and efficiency
values
• EC fans are positioned vertically in the lower third of the unit. Incident flow
area, impeller diameter and motor design perfectly matched to the internal
unit design for lowest power consumption and maximum air volumes.
• Air discharge (supply air) out of the unit to bottom into the raised floor
Panelwork:
• the unit is delivered with all sides closed, panels and doors can be removed
on all sides.
• back- and side panels are firmly screwed.
• all visible parts of sheet steel with a high-grade plastic powder coating
• the panelwork is executed with doors at the unit front, all doors open to the
same side for easy access to all maintenance relevant parts.
• the doors are assembled to the unit frame with lockable security fasteners
which prevent from unauthorized access to the units.
• panelwork and door insulation with insulation material of 25mm thickness
o fire classification is B-s1, d0 according to EN 13501-1, (hardly
inflammable, self-extinguishing)
o chemical-free and UV-proof
o no mould fungus according to DIN IEC 68
o resistent against house dust mites and vermins, non-provoking allergies
decay-proof
o sound absorbent features > 5 kNs/m4 according DIN52213
o toxicologically recognized as safe according to Öko-Tex standard 100
o detergent-proof
o thermal isolation characteristics until WLG 0,040 (040) DIN 52612
Unit colour:
• Panelwork and visible sheet steel parts in STULZ anthracite grey
• Controller front top in Stulz telegrey 4 (RAL 7047)
• the scroll compressor cooled by suction gas is installed in the unit with
anti-vibration mounts ensuring a low level of vibration and noise.
• High operational reliability due to integrated oil management system as well
as current- and temperature-dependent internal motor cut-out.
• The compressor is robust and maintenance-free, achieves a high efficiency
and therefore enables stable, energy-efficient operation of the refrigerant
circuit.
• Each compressor is protected by a high-pressure switch with manual reset
and a low-pressure switch with automatic reset, and features a low-pressure
management integrated in the A/C unit's control system to prevent excessive
condensation pressure or insufficient evaporation pressure.
Pipework:
• Internal unit pipework of copper, routed for optimum absorption and
dissipation of possible vibrations and optimised on low pressure loss.
• Suction gas line and injection line insulated diffusion resistant to prevent
the formation of condensate and loss of heat
• Piping grounded for potential equalisation
• Special pipe supports are used to absorb the load on the pipework, and for
thermal decoupling.
• Several Schrader valves are integrated at easily accessible points for
maintenance purposes.
Pipework connections:
• pipework (hotgas and liquid line) ends with soldering connections for
connection to customer's on-site pipework.
• connections can be locked separately.
• the pipework ends inside the unit pointing downwards in the front right area.
Tube insulation:
• insulation is CFC-free; UV-proof, non-ageing and water-proof
• classification according to EN 13501-1: building material class BL-s3,d0
(hardly inflammable)
• self-extinguishing, non-dropping, non-fire-conducting
• insulation will be glued full-surface on the valves and other critical points.
• resistant against most of the chemicals (with application in chemical
environment please indicate type of chemicals).
• thermal conductivity at 0°C: 0,033 W / m x K
• water vapour transfer coefficient ; µ > 10.000
Air filter:
• located on suction side in the unit, position directly on heat exchanger
• large filter surface, small pressure loss, long service life and easy
replaceability from the front
• filter class according to ISO 16890: ISO ePM10 80% to ePM1 55%
• filter class according to EN 779: F7
• filter version with solid frame, fully combustible, metal-free
• classification according to EN 13501-1: E (normally flammable),
self-extinguishing
• filter material made of synthetic, completely recyclable micro spunbond with
tight, fixed fold spacing for maximum filter surface
• filter depth 47mm
• filter monitoring by differential pressure switch installed in the A/C unit's
electric box with optical and acoustic warning
• with "Filter-Control Management" software (integrated in the unit's control
system) for constant volume flow also in case of a soiled filter
Electric cabinet/Electrics:
• electric cabinet (electric box) integrated in the A/C unit for accommodation
of all high voltage and control components; design according to EN
60204-1; protection class: IP20
• located in upper front area of the unit; accessible for maintenance
exclusively from the front
• clear and space saving structure of all high voltage and control
components
• consistent separation of high voltage and control elements to avoid EMC
interferences. This improves the resistance against electro-magnetic
noise.
• all three-phase consumers protected against overload and short circuit by
circuit breakers according to IEC/EN 60947-1
• completed wiring of motor circuit breakers, contactors and control
components in wiring ducts
• top hat rail or busbar system for high voltage components
• installed main switch (3 poles) operable from the outside, design as load
disconnector
• main power supply provided by customer, cable pull relief provided
Feeding direction:
• feeding of the main power supply from bottom
• feeding of the external control lines from bottom
Microprocessor/Control:
• the A/C unit is equipped with a controller developed by STULZ and
optimized for use in A/C units on the hardware and software side.
• in the basic version, the A/C unit is supplied with an IO controller installed in
the electric cabinet and an EBUS expansion board (plus possibly
equipment-dependent number of additional expansion boards), which can
be used for A/C unit's control.
• power supply: 24V (+15%/-15%) VAC by transformer
• interfaces/IO controller connections:
o I/O board interface: EIA485 (RS485)
o service, download and printer interface: EIA232 (RS232)
o 4 analog inputs: signal current 0-20 mA or 4-20 mA or signal voltage
0-10 V
o 11 digital inputs: 24 VAC/DC (+24V = no alarm); status display via LED's
o 4 analog outputs: 0-10 VDC; maximum load 20 mA
o 7 digital outputs (relais with two way contact): 24 VAC, max. 6A, status
display via LED's
• EBUS expansion board:
o EIA485 (RS485) IO bus for internal communication between IO
controller and internal components (e.g. electronic expansion valve)
o EIA485 (RS485) BMS bus for communication with a building
management system per Modbus RTU (max. 250 data points) or for
connection to an optional protocol converter
• all unoccupied digital and analog inputs or outputs of the IO controller can
be freely assigned, e.g. for the connection of auxiliary alarms or external
signals and their designation with freely configurable texts.
• Basic features/functions:
o serial RS485 interface for connection to user interface (HMI)
o automatic or manual start after power loss
o unit start time delay and start delay for individual components adjustable
o adjustable alarm delays and alarm priorities; configurable alarm
relevance
o manual operation of individual components
o automatic start of standby units in case of failure and additional load;
runtime equalization
o sequencing of all IO controllers connected to the internal IO bus;
sequencing can be divided in up to 20 independent zones, adjustable
sequencing time
o event log, recording of alarms, warnings, failures the same as unit starts
and stops (200 events with time and date)
o temperature- and humidity recording up to 1440 data points, freely
scalable within 1 to 60000 minutes (ring buffer/data logger)
o day and night operation
o service warning according to pre-set time intervals
o capable for communication by Modbus RTU protocol
• Control and monitoring of the following functions and all operationally
relevant components (depending on the selected options):
o cooling, dehumidification, (re-)heating, humidification
o control and supervision of limit values for temperature and humidity of
return air and/or supply air including rule-based averaging when using
more than one similar sensor
o compressor(s), compressor speed (only for units with speed-controlled
compressor), expansion valve
o runtime equalization and sequencing between compressors in units with
2 refrigerant circuits
o winter start operation
o high and low pressure monitoring the same as condensation pressure
control
o energy-saving speed control of the EC fans depending on the
temperatures, humidity and/or pressure-dependent (differential pressure
control)
o standby management
o function and speed of EC fans
o control valve(s)
o directe or indirect free cooling
o filter monitor incl. filter control management
o reheat(s)
o humidifiers, water detector, conductivity measuring device
o phase monitoring, UPS operation
o dry coolers, pumps
A Schrader valve is located in the hotgas line for connecting a pressure gauge to
adjust the speed controller by maintenance personnel.
Technical data:
• voltage supply: 400/3/50-60 V/Ph/Hz
• number of fans: 4
• max. operating pressure: 28 bar
Speed controller
• operation by display and 4 keys inside the housing
• adjustment of setpoint, proportional range, min/max speed, soft
start delay and speed jump to bypass a sound level maximum
• adjustment of condensation pressure setpoint (pressure at 100%
output voltage)
• switch for behaviour below the proportional range (cut off/minimum
speed)
• adjustment range: 0 to 30 bar
• proportional range: 1 to 30 bar
• alarm indication by display and LED:
- overheating of circuit board
- phase loss of the supply voltage
- input signal is below the lower limit (2mA)
- input signal is above the upper limit (24mA)
• ambient temperature: -45 to +60°C (50Hz) / +59°C (60Hz)
• protection: IP 55
Restrictions:
• admissible cable impedance: 100nF/km
• maximum cable length: 200m
Building Communication Module
provides the BACnet IP-protocol via an Ethernet interface. The BCM represents
an advantageous variant compared with the gateway realization by a collective
protocol converter in a separate box, when few A/C units or chillers are
concerned. With 3 units and more, the solution with a collective protocol
converter is more favourable in price. However, the redundancy in the usage of
BCMs is intrinsically higher.
consisting of:
• extension board with socket for protocol converter (instead of RS485 bus
extension board EBUS)
• protocol converter mounted on extension board
• default configuration
The interface board is the gateway between the building management system on
the customer side and the STULZ C7000 IO controller. It is plugged directly on
the main board of the IO controller.
Technical data:
• operating temperature: 5 to 40 °C
• energy consumption: 5VDC@208 mA (protocol converter)
C7000Advanced-Terminal
Additional user-interface for C7000-Control System: Graphic display and
BMS-Connectivity
Technical data of the terminal:
• Voltage supply: 24 VAC
• Power consumption: 14 VA
• Fuse 2 A slow
• Operating temperature: 5°C ... 40°C
Features:
• Large backlit LCD display
• LCD display located at a height of 1.55m
• Navigation via 5 keys
• Operation of up to 19 C7000 IO-Controllers via Windows technology
• Redundant user-interface by usage of up to 19 C7000AT
• Menu in 12 languages
• Visual and acustic signals of events
• Alarm transfer via SMS and E-mail (additional options required)
Interfaces:
- RS232 - Service Port (Sub-D 9) for configuration
- RS485 - for internal Stulz I/O-Bus
- RS232 or RS485 for connection to BMS
Note:
If the refrigerant circuit is equipped with Rotalock valves as a standard, these
valves are omitted with the installation of an adjustable high pressure switch.
However the Rotalock valves can be ordered by taking one of the options
"K99838 - K99844 Rotalock valves suction and discharge side for ASD/U ...".
The power for the condensate pump can either be supplied by the e-box
incorporated in the A/C unit or has to be provided by the customer on site.
Technical data: max. volume flow: 900 l/h
max. delivery head: 6,0 m
volume flow at 4,0 m: 450 l/h
Floor stand:
• Floor stand for A/C unit, adjustable height 495-545 mm.
• The floor stand serves for a vibration-decoupled positioning of the A/C unit,
the same as for adjusting the A/C unit position to the existing raised floor
height.
• The floor stand consists of the following components, which must be
assembled on site:
o a sufficient number of galvanized profile steel frames (70x40 mm), which
is adapted to the unit construction
o threaded supports with adjustable height incl. base plate (circular) and a
head plate (serrated disc)
o vibration reducing Mafund support strips (25 mm thickness)
o the associated fixing material, e.g. hammer head screws
• The number of threaded supports is adapted to the unit dimensions and
weight.
WinPlan
Unit
Unit type: ASD 792 A
Cooling capacity (total): 75.1 kW
Cooling capacity (sensible): 75.1 kW
Condensing temperature: 55 °C
EER: 2.78 kW/kW
AER: 0.30 W/(m³/h)
Sound power level: 84.2 dB(A)
LpA (2m freefield): 63.5 dB(A)
Airflow: 21,000 m³/h
Air velocity: 3.1 m/s
Return air temperature: 25 °C
Return air humidity: 48 rel.%
Supply air temperature: 14 °C
Altitude above sea level: 0 m
Height: 1,980 mm
Width: 2,200 mm
Depth: 890 mm
Weight: 714 kg
Refrigerant: R407C
Power supply: 400V/50Hz/3Ph/N/PE
Total power consumption: 27.0 kW
Condenser
Unit type: KSV090A41p
Ambient temperature: 48 °C
Sound pressure group: Standard
Required condenser capacity: 47.7 kW
Available condenser capacity: 50.1 kW
Difference: 5.0 %
Weight: 252 kg
Current consumption (per fan): 1.25 A
Power consumption (per fan): 0.86 kW
Height: 936 mm
Width: 4,880 mm
Depth: 920 mm
Airflow: 29,600 m³/h
LpA (5m freefield): 57.6 dB(A)
Number of fans: 4
Number of condensers: 2
The above mentioned data are determined and rated in accordance to EN 14511
and therefore are subject to measuring tolerances. Unless otherwise stated, all
data refer to a product in basic version.