Lab Manual
Lab Manual
S.No. Experiment
To conduct the open circuit & short circuit tests of Transformer & to calculate efficiency
4
without loading the Transformer
Apparatus:
• Single Phase Transformer
• Single phase AC Power Supply
• AC Voltmeters
• Connecting Leads
• Data Acquisition interface Software
a.Turns Ratio Test Of A Transformer
Discussion:
Voltage ratio test of a transformer is performed to find the turn ratio of the transformer. Turns ratio of a
transformer tells us that whether the transformer is step-up or step-down.
Polarity test of a transformer is performed to determine the polarity of the two windings of transformer so
that we can connect the two windings in series or in parallel and also two transformers in series or in
parallel. The correct polarity must be determined first in order to connect the transformers/windings in
proper arrangement either in series or in parallel.
Procedure:
Connections are made as shown in the diagram. The primary side is connected to single phase variable AC
voltage supply and voltmeter (Vp) in parallel. The secondary side is also connected to voltmeter (Vs) in
parallel. Note down the readings in table 2.1 as indicated by the voltmeters Vp and Vs.
Circuit Diagram:
Supply is switched on with the minimum 0 position. Vary the supply voltage and note down the readings in
the table.
Sr. E1 E2 N2/N1
No (V) (V)
Procedure:
Connect the H.V winding to an AC source. The rated voltage is applied to the primary and primary terminals
are marked as A1 and A2. The secondary winding terminals are marked as B1 and B2. A wire is connected
across A2 and B2 and a voltmeter connected across A1 and B1.
Circuit Diagram:
(a) (b)
If it measures the difference of V1 and V2 it mean A1 and B1 have same polarity as in figure 2.2 (a). The dots
are on same side. If voltmeter measure the addition of V1 and V2 it means A1 and B1 are of opposite
polarity as in figure 2.2 (b) the dots are on opposite side. Place 3 voltmeters; one at primary side and other at
secondary side and the third as connected in figure 2.2
Take the first reading and write down the value indicated by the voltmeters in table 2.2(a).
Sr. No EP ES E3
_____________________________________________________________________________________
_____________________________________________________________________________________
Repeat the process by connecting the circuit as shown in figure 2.2 (b) and record your results in table 2.2
_____________________________________________________________________________________
_____________________________________________________________________________________
_____________________________________________________________________________________
A T/F having primary voltage of 50V and primary current of 2A, if the secondary current is 4A what will be
its secondary voltage?
_______________________________________________________________________________________
_______________________________________________________________________________________
_______________________________________________________________________________________
Experiment No 3
Objective:
To determine the voltage regulation and efficiency of a single phase transformer
on a) Resistive Load
b) Inductive Load
c) Capacitive Load
Apparatus:
• Single Phase Transformer
• Single phase AC Power Supply
• AC Voltmeter
• AC Ammeter
• AC Wattmeter
• Resistive Load
• Inductive Load
• Capacitive Load
• Connecting Leads
• Labvolt data interface Software
Discussion:
The voltage regulation of the transformer is the percentage change in the output voltage from no-load to
fullload. And since power factor is a determining factor in the secondary voltage, power factor influences
voltage regulation, is defined by equation.
Procedure:
• set up the transformer loading circuit shown in Figure 3.1. Make sure that all switches on
the Resistive, Capacitive, and Inductive Load modules are open, and connect meter inputs
E1, E2, I1, and I2 as shown in the figure. Different load values will be used to examine
how the secondary (load) voltage changes as transformer loading changes.
Figure 3.1 voltage regulation of Transformer circuit with resistive load
• Turn on the power supply and vary the voltage upto the rated value of transformer.
• Adjust the switches on the Resistive Load module to successively obtain the resistance values given
in Table 3.1. For each resistance value, record the measured values. When all values have been
recorded, turn the voltage control knob fully counterclockwise, and turn off the Power Supply.
Apparatus:
• Single phase Transformer
• Connecting leads
• Single phase AC Power Supply
• AC Voltmeter
• AC Ammeter
• AC Wattmeter
• Connecting leads
• Labvolt Data Acquisition interface software
Discussion:
In any electrical machine, 'loss' can be defined as the difference between input power and output power. An
electrical transformer is an static device, hence mechanical losses (like windage or friction losses) are absent in it.
A transformer only consists of electrical losses (iron losses and copper losses). Transformer losses are similar to
losses in a DC machine, except that transformers do not have mechanical losses.
These two transformer tests are performed to find the parameters of equivalent circuit of transformer and losses of
the transformer. Open circuit test and short circuit test on transformer are very economical and convenient because
they are performed without actually loading of the transformer. Open circuit test or no load test on a transformer is
performed to determine 'no load loss (core loss)' and 'no load current I0'. The circuit diagram for open circuit test
is shown in the figure below.
Usually high voltage (HV) winding is kept open and the low voltage (LV) winding is connected to its normal
supply. A wattmeter (W), ammeter (A) and voltmeter (V) are connected to the LV winding as shown in the figure.
Now, applied voltage is slowly increased from zero to normal rated value of the LV side with the help of a variac.
When the applied voltage reaches to the rated value of the LV winding, readings from all the three instruments are
taken. The ammeter reading gives the no load current Io. As Io itself is very small, the voltage drops due to this
current can be neglected. The input power is indicated by the wattmeter (W). But, as the other side of transformer
is open circuited, there is no output power. Hence, this input power only consists of core losses and copper losses.
But as described above, short circuit current is so small that these copper losses can be neglected. Hence, now the
input power is almost equal to the core losses. Thus, the wattmeter reading gives the core losses of the transformer.
The two components of no load current can be given as,
ATTENTION!!!!!!!
NOTE: Do not load the transformer above its rated current, the windings will be burnt
Circuit Diagram:
Introduction:
Many three-phase transformer configurations are possible when connecting the primary and secondary
windings of a three-phase transformer bank. Each configuration presents different characteristics.
When connecting a three-phase transformer bank in a circuit, it is therefore important to determine
which characteristics are advantageous to the circuit, and to choose the appropriate three-phase
transformer configuration accordingly. The four most common three-phase transformer configurations
are wye-wye, delta-delta, wye-delta, and delta-wye configurations.
Voltage, current, and phase relationships of the four common three-phase transformer configurations
The most determining characteristics of each three-phase transformer configuration mentioned in the
previous section (i.e., the wye-wye, delta-delta, wye-delta, and delta-wye configurations) are their
respective voltage, current, and phase relationships between the primary windings and the secondary
windings. The following three sections discuss these relationships for each threephase transformer
configuration. Note that, as wye-wye and delta-delta configurations have similar voltage, current, and
phase relationships, both configurations are covered in the same section. Also note that, in the
following sections, the turns ratio of each transformer in the three-phase transformer bank is assumed
to be equal to 1:1. This allows observation of the effects each configuration has on the voltage, current,
and phase relationships of the three phase transformer bank, independently of the turns ratio.
Wye-delta configuration
When a three-phase transformer bank is connected in a wye-delta configuration, the values and phases
of the line voltages and currents at the secondary are different from those at the primary. Thus, in a
wyedelta configuration, the value of the line voltages at the secondary is equal to that of the line
voltages at the primary divided by . Conversely, the value of the line currents at the secondary is
equal to that of the line currents at the primary multiplied by . Furthermore, the line voltage sine
waves at the secondary lag behind those at the primary by 30°. The same is true for the line current
sine waves at the secondary with respect to the line current sine waves at the primary.
Delta-wye configuration
When a three-phase transformer bank is connected in a delta-wye configuration, the values and phases
of the line voltages and currents at the secondary are different from those at the primary. Thus, in a
delta-wye configuration, the value of the line voltages at the secondary is equal to that of the line
voltages at the primary multiplied by . Conversely, the value of the line currents at the secondary is
equal to that of the line currents at the primary divided by . Furthermore, the line voltage sine waves
at the secondary lead those at the primary by 30°. The same is true for the line current sine waves at
the secondary with respect to the line current sine waves at the primary.
Three-phase transformer banks are used in three-phase ac power circuits for basically the same reasons
as single-phase power transformers in single-phase ac circuits, i.e., to step-up or step-down the voltages
in the circuit and to provide electrical isolation between the primary windings and the secondary
windings. However, the special properties of certain three-phase transformer configurations presented
in the previous sections allow three-phase transformer banks to be used in a few additional
applications. The primary uses of three-phase transformer banks in three-phase ac power circuits are
summarized below.
1. Three-phase transformer banks allow the voltages in the three-phase ac power circuit to be s
tepped-up (i.e., to be increased) or stepped down (i.e., to be decreased).
2. Three-phase transformer banks provide electrical isolation between the primary windings and
the secondary windings.
3. Three-phase transformer banks connected in a wye-delta or in a delta-wye configuration
allow the number of wires in the three-phase ac power circuit to be decreased from 4 to 3, or
increased from 3 to 4, respectively.
4. Three-phase transformer banks connected in a wye-delta or in a delta-wye configuration
allow the incoming line voltages and currents to be phase shifted -30° or 30°, respectively.
Circuit Diagram:
Procedure:
• Connect the transformer’s primary and secondary windings according to the circuit diagram.
Connect the voltmeters and connect the ac supply and set it to 50 volts.
• Open the phase analyzer in the Lab volt software and record the results.
Delta to Y Connections
Experiment No. 6
Objective:
• To study the external characteristics of DC Shunt Motor.
Apparatus:
• DC Motor/Generator Module
• Prime Mover/Dynamometer Module
• DC Variable Supply
• Lab Volt Data Acquisition Interfacing module
• Connecting Leads Discussion:
The shunt wound dc motor falls under the category of self excited dc motors, where the field windings are
shunted to, or are connected in parallel to the armature winding of the motor, as its name is suggestive of.
And for this reason both the armature winding and the field winding are exposed to the same supply voltage,
though there are separate branches for the flow of armature current and the field current.
Therefore the curve drawn between torque Vs armature current is a straight line transitory through the origin.
The shaft torque(Tsh) is a smaller amount than armature torque. From this curve it is proved that to start a
heavy load very large current is requisite. Hence the shunt DC motor should not be started at full load.
Speed Vs Armature Current Characteristic:
At normal condition the back E.M.F Eb and Flux Φ both are constant in a DC Shunt motor. Hence the
armature current differs and the speed of a DC Shunt motor will continue.Whenever the shunt motor load is
increased Eb=V-IaRa and flux reduces as a result drop in the armature resistance and armature reaction. On
the other hand, back e.m.f reduces marginally more than that the speed of the shunt motor decreases to some
extent with load.
Speed Vs Armature Torque:
This curve is drawn between the speed of the motor and armature current with various amps. From the curve
it is understood that the speed reduces when the load torque increases.
With the above three characteristic it is clearly understood that when the shunt motor runs from no load to full
load there is slight change in speed. Thus, it is essentially a constant speed motor. Since the armature torque
is directly proportional to the armature current, the starting torque is not high.
Procedure:
• Make connections as shown in circuit diagram.
Circuit Diagram:
• First of all set the prime mover/Dynamometer module mode on Dynamometer.
• Set the torque at 0 Nm. For this we have set the torque knob at 0 position (anticlockwise) on
Dynamometer.
• Set DC 220V at supply and adjust the field resistance rheostat at the position where motor’s rpm are
1500.
Observation:
Sr. T IA N
No
N.m (A) rpm
1 0
2 0.1 0.14 1520
3 0.2 0.15 1475
4 0.3 0.16 1465
5 0.4 0.16 1467
6 0.5 0.16 1449
7 0.6 0.17 1407
8 0.7 0.17 1411
9 0.8 0.17 1381
10 0.9 0.17 1387
11 1 0.17 1356
12 1.1 0.17 1312
Graphs:
Apparatus:
• DC Motor/Generator Module
• Dynamometer
• DC Variable Supply
• Labvolt Data Acquisition interface software
• Connecting Leads Introduction:
The series motor is a motor in which the field electromagnet is a series winding connected in series with the
armature as shown in Figure 7-1. The strength of the field electromagnet, therefore, varies as the armature
current varies. Figure 7-1 shows the speed versus torque characteristic of a series motor when the armature
voltage is fixed. This characteristic shows that the speed decreases none linearly as the torque increases, i.e.,
as the armature current increases.
We know that torque is directly proportional to the product of armature current and field flux, Ta ɸ.Ia. In
DC series motors, field winding is connected in series with the armature, i.e. Ia = If. Therefore, before magnetic
saturation of the field, flux ɸ is directly proportional to Ia. Hence, before magnetic saturation Ta α Ia2.
Therefore, the Ta-Ia curve is parabola for smaller values of Ia. After magnetic saturation of the field poles,
flux ɸ is independent of armature current Ia. Therefore, the torque varies proportionally to Ia only, T Ia.
Therefore, after magnetic saturation, Ta-Ia curve becomes a straight line.
The shaft torque (Tsh) is less than armature torque (Ta) due to stray losses. Hence, the curve Tsh vs Ia lies
slightly lower.
In DC series motors, (prior to magnetic saturation) torque increases as the square of armature current, these
motors are used where high starting torque is required.
For small load current (and hence for small armature current) change in back emf Eb is small and it may be neglected.
Hence, for small currents speed is inversely proportional to ɸ. As we know, flux is directly proportional to Ia, speed
is inversely proportional to Ia. Therefore, when armature current is very small the speed becomes dangerously high.
That is why a series motor should never be started without some mechanical
load. But, at heavy loads, armature current Ia is large. And hence, speed is low which results in decreased
back emf Eb. Due to decreased Eb, more armature current is allowed.
3. Speed Vs Torque characteristic (N/Ta) when speed is high, torque is low and vice versa.
The series motor provides a strong starting torque and a wide range of operating speeds when it is
supplied by a fixed-voltage dc source. However, the speed, torque, and armature current depend on the
mechanical load applied to the motor. Also, the series motor has non-linear operating characteristics as
suggested by the speed versus torque relationship in Figure 7-1. As a result, it is difficult to operate a
series motor at a constant speed when the mechanical load fluctuates. Furthermore, the armature
current must be limited to prevent damage to the motor when it is starting (when power is applied to the
motor). Finally, a series motor must never run without mechanical load because the speed increases to
a veryhigh value which can damage the motor (motor runaway).
Today, series motors can operate with fixed-voltage power sources, for example, automobile starting
motors; or with variable-voltage power sources, for example, traction systems
Circuit Diagram
Procedure:
• Make connections as shown in figure 7-2.
• Rotate slightly the torque controlling knob of Dynamometer to clock wise.
• Turn on the Power supply and apply voltages to motor slowly upto its rated voltage
• Record your results by applying the torque on series motor with the help of dynamometer torque
control knob.
Observation:
Sr. T N.m IA (A) N rpm
No
Apparatus:
• DC Motor/ Generator module
• Prime Mover
• Resistive load
• Data Acquisition interface software
• Connecting leads
Introduction:
A dc generator is an electrical machine which converts mechanical energy into direct current electricity. This
energy conversion is based on the principle of production of dynamically induced emf. According to
Faraday’s laws of electromagnetic induction, whenever a conductor is placed in a varying magnetic field (OR
a conductor is moved in a magnetic field), an emf (electromotive force) gets induced in the conductor. The
magnitude of induced emf can be calculated from the emf equation of dc generator. If the conductor is provided
with the closed path, the induced current will circulate within the path. In a DC generator, field coils produce
an electromagnetic field and the armature conductors are rotated into the field. Thus, an electromagnetically
induced emf is generated in the armature conductors.
Although dc generators are rarely used today, it is important to know their operation because this helps
understanding how a separately-excited dc motor can be used as an electric brake in modern dc motor drives.
You saw earlier in this unit that a dc motor can be considered as a linear voltage-to-speed converter. This
linear conversion process is reversible, meaning that when a fixed speed is imposed on the motor by an external
driving force, the motor produces an output voltage E0, and thus, operates as a linear speed-to-voltage
converter, i.e., a dc generator. Figure 8-1 shows a DC Generator.
A shunt generator is a type of direct current electric generator in which field winding and armature winding
are connected in parallel, and in which the armature supplies both the load current and the field current.
Open Circuit Characteristics of Shunt Generator:
This curve is drawn between shunt field current(Ish) and the no load voltage (E0). For a given excitation current
or field current, the e.m.f generated at no load E0 varies in proportionally with the rotational speed of the
armature. Here in the Graph 1 the magnetic characteristic curve for various speeds are drawn. Due to residual
magnetism the curves start from a point slightly up from the origin. The external load resistance of the machine
needs to be maintained greater than its critical value otherwise the machine will not excite or will stop running
if it is already in motion.
Graph 2 showing the external characteristics of shunt DC generator. It is showing the variation of terminal
voltage with the load current. Ohmic drop due to armature resistance gives lesser terminal voltage the
generated voltage. That is why the curve lies below the internal characteristic curve.
The terminal voltage can always be maintained constant by adjusting the of the load terminal. Now, when IL
increased, then terminal voltage decreased. After certain limit, due to heavy load current and increased Ohmic
drop, the terminal voltage is reduced drastically. This drastic reduction of terminal voltage across the load,
results the increase in the load current although at that time load is high or load resistance is low.
That is why the load resistance of the machine must be maintained properly. The point in which the machine
gives maximum current output is called breakdown point.
In a Dc shunt generator the shunt field current indicated by If should be increased in order to get the desired
output terminal voltages at the terminal of Generator at rated speed (1500 rpm). The field rehoestat should
be turned to anticlockwise position first and then it should be turned in clockwise position in order to
increase the terminal voltage and decreasing the field resistance. After obtaining the rated output voltage
which is 220V, then in 2nd part we will apply a resistive load on Generator to check its load current Vs
Terminal voltage characteristics.
Figure 8-2 E0 Vs If Characteristics of DC shunt Generator on no load at fixed speed
When the load is connected across the terminals of DC shunt Generator armature resistance causes the
output voltage E0 to decrease with increasing output current as shown in Figure 2-29. The output voltage E0
can be calculated using the following equation:
E0 = EMF – I0Ra
Where E0 is the DC generator output voltage EMF is the voltage induced across
the armature winding RA is the armature resistance I0 is the DC Generator output current
The separately-excited dc generator provides flexible use because its characteristics can be changed by
changing the field current. However, a separate dc power source is needed to excite the field electromagnet.
This was a disadvantage when the first dc generators were used because dc sources were not commonly
available at the time. Therefore, dc generators that operate without a dc power source were designed. These
are referred to as self-excited dc generators.
Procedure:
• Set up the separately-excited dc generator circuit shown in Figure 8-4. Notice that no electrical load
is connected to the generator output.
• Set the Four-Quadrant Dynamometer/Power Supply or the Prime Mover/Dynamometer to operate as
a clockwise prime mover
• Set the prime mover speed to 1500 rpm
• Now increase the field current with the help of field rheostat and record your results at different
intervals
Figure 8-4 DC shunt Generator circuit diagram on no load
• Now after completing this part connect a resistive load to DC shunt Generator output. Vary the
load current in steps of 0.05A from 0.05A to 0.35A.
Results:
• Without Loading:
E1 If N
(A) (rpm)
(V)
• With Loading:
E1 If N IL
(A) (rpm)
(V)
Graph:
Experiment No. 9
Objective:
To study External characteristics of DC Compound Generator.
Apparatus:
• DC Generator/Motor module
• Prime mover/Dynamometer module
• Rheostat
• DC Variable Supply
• Lab Volt Data Acquisition interfacing module
• Connecting Leads Discussion:
In a compound generator, both series and shunt winding occurs .The shunt winding can be connected either
across the armature only (short-shunt connection S) or across armature plus series field (long-shunt
connection G). The compound generator can be cumulatively compounded or differentially compounded
generator.
The series excitation aids the shunt excitation. The degree of compounding depends upon the increase in
series excitation with the increase in load current.
.
Figure Commulative compound Generator
Procedure:
Circuit Diagram:
• First of all Set the Prime mover Mode.
• Supply the power to prime mover and increase its voltage from 0 to 220V such that the rpm of
generator are 1500 and adjust the rheostat in such a way that the output voltages of generator are
220V approximately.
• Now Apply the Resistive load at the steps of 0.05A increment but keep rpm constant by increasing
the speed of prime mover.
• After that record the load current and output voltages across Load.
Observations:
Eg IL N
Apparatus:
The stator of the motor consists of overlapping winding offset by an electrical angle of 120°. When the
primary winding or the stator is connected to a 3 phase AC source, it establishes a rotating magnetic field
which rotates at the synchronous speed.
Secrets behind the rotation:
According to Faraday’s law an emf induced in any circuit is due to the rate of change of magnetic flux
linkage through the circuit. As the rotor winding in an induction motor are either closed through an external
resistance or directly shorted by end ring, and cut the stator rotating magnetic field, an emf is induced in the
rotor copper bar and due to this emf a current flows through the rotor conductor.
Here the relative speed between the rotating flux and static rotor conductor is the cause of current
generation; hence as per Lenz's law the rotor will rotate in the same direction to reduce the cause i.e. the
relative velocity.
The difference between the synchronous speed of the magnetic field, and the shaft rotating speed is slip -
measured in RPM or frequency.
It is common to express the slip as the ratio between the shaft rotation speed and the synchronous magnetic
field speed.
S = (ns - nm) / ns X100%
where
S = slip
ns = synchronous speed of magnetic field (rev/min,
rpm) na = shaft rotating speed (rev/min, rpm)
When the rotor is not turning the slip is 100 %.And Slip at no load is approximately 0.
Slip and Voltage:
When a motor starts to rotate the slip is 100 % and the motor current is at maximum. Slip and motor current are
reduced when the rotor begin turning.
Slip Frequency:
Frequency decreases when slip decrease.
Procedure:
Circuit Diagram:
• First of all set the Dynamometer Mode.
• And set the torque at 0 Nm. For this we have set the torque knob at 0 position on Dynamometer.
• Set AC 3 phase power supply to maximum position.
• Now apply the torque at the steps of 0.1 increments and record the E1, E2, E3, I1, I2, I3, Active,
Reactive and Apparent Power, Power Factor, Slip and Speed.
Observations:
E1 E2 E3 I1 I2 I3 P Q S T N P.f Slip
Graphs:
I1 Vs P
Experiment No. 11
Objective:
• Synchronous Motor:
When a 3 phase electric conductors are placed in a certain geometrical positions (In certain angle from one
another) there is an electrical field generate. Now the rotating magnetic field rotates at a certain speed, that
speed is called synchronous speed. Now if an electromagnet is present in this rotating magnetic field, the
electromagnet is magnetically locked with this rotating magnetic field and rotates with same speed of
rotating field. Synchronous motor is called so because the speed of the rotor of this motor is same as the
rotating magnetic field. It is basically a fixed speed motor because it has only one speed, which is
synchronous speed, and therefore no intermediate speed is there or in other words it’s in synchronism with
the supply frequency.
Synchronous speed is given by
120 𝑓
𝑁𝑟𝑝𝑚 =
𝑃
Normally its construction is almost similar to that of a 3 phase induction motor, except the fact that
the rotor is given dc supply, the reason of which is explained later. Now, let us first go through the basic
construction of this type of motor from the above picture, it is clear that how this type of motors are
designed.
Main Features of Synchronous Motors
1. Synchronous motors are inherently not self starting. They require some external means to bring their
speed close to synchronous speed to before they are synchronized.
2. The speed of operation of is in synchronism with the supply frequency and hence for constant supply
frequency they behave as constant speed motor irrespective of load condition
3. This motor has the unique characteristics of operating under any electrical power factor. This makes it
being used in electrical power factor improvement.
Principle of Operation Synchronous Motor
Synchronous motor is a doubly excited machine i.e. two electrical inputs are provided to it. Its stator
winding which consists of a 3 phase winding is provided with 3 phase supply and rotor is provided with DC
supply. The 3 phase stator winding carrying 3 phase currents produces 3 phase rotating magnetic flux. The
rotor carrying DC supply also produces a constant flux. Considering the frequency to be 50 Hz, from the
above relation we can see that the 3 phase rotating flux rotates about 3000 revolution in 1 min or 50
revolutions in 1 sec. At a particular instant rotor and stator poles might be of same polarity (N-N or S-S)
causing repulsive force on rotor and the very next second it will be N-S causing attractive force. But due to
inertia of the rotor, it is unable to rotate in any direction due to attractive or repulsive force and remain in
standstill condition. Hence it is not self starting. To overcome this inertia, rotor is initially fed some
mechanical input which rotates it in same direction as magnetic field to a speed very close to synchronous
speed. After some time magnetic locking occurs and the synchronous motor rotates in synchronism with the
frequency.
Circuit Diagram:
• SynchronousGenerator:
The generator in which permanent magnet/electromagnet is used instead of coil to provide excitation
field is termed as synchronous generator.
In general, synchronous generator consists of two parts rotor and stator. The rotor part consists of
field poles and stator part consists of armature conductors. The rotation of field poles in the presence
of armature conductors induces an alternating voltage which results in electrical power generation.
Where, ‘f’ indicates alternating current frequency and ‘P’ indicates number of poles.
BB CC
N S
C B
C’ B’
A
Stator coils separated by 120o causes delay between phase EMFs by 120 degrees.
Phase difference depends upon the number of slots and number of coils per phase,
and position and orientation of coils.
Procedure:
Circuit Diagram:
Observation:
It is observed that as the Inductive load increase the terminal voltages decrease and as the capacitive load
increases the terminal voltages increases due to leading power factor of load. But there is no change in the
speed of generator.By increasing the field current the terminal voltages also increases.
Experiment No. 13
Objective:
To Synchronize the three phase alternator with Wapda/National grid.
Apparatus:
• Synchronous Motor/Generator Module
• Dynamometer/Prime mover Module
• Synchronizing Module
• DC Supply
• Connecting Leads
• Lab volt data acquisition and control interface Discussion:
To synchronize the alternator with national grid, before synchronizing there are 4 conditions which are must
be fulfiled
The synchroscope would be rotating rapidly counter clockwise. If the generator breaker were to be
accidentally closed, the generator would be out of step with the external electrical system. It would
behave like motor and the grid would try to bring it up to speed.In doing so, the rotor and stator would
be slipping poles and damage (possibly destroy) the generator as described previously. The same
problem would occur if the generator were faster than the grid.
The high points and zero crossings of the sinusoidal voltages occur at the same rate of speed. If the
generator breaker were to be closed at this time, the grid would pull the generator into
step.However, this again would cause a large current in-rush to the generator and high stresses on
the rotor/stator with subsequentdamage to the generator. If the generator were leading the grid, it
would try to immediately push power into the grid with the same destructive forces as mentioned.
Hence the generator must be brought to a point where the grid voltage waveform exactly matches
what it is producing.
Phase angle:
The phase angle between the voltage produced by the generator and the voltage produced by the
gridmust be zero.The phase angle (0 to 360°) can be readily observed by comparing the simultaneous
occurrence of the peaks or zero crossings of the sinusoidal waveforms.
If the generator breaker is closed when they match exactly, the connection will appear smooth and
seamless.
Procedure:
Setting:
• The flikring sequence should be same it means all bulbs on or off at the time.
• Flikring rate showld be zero it means they are all should be turn on or turn off (not
flashing).
• The intensty of glow should be minimum as much as possible.
Methods:
• Flickring sequence shows the phase angle sequence, to set the flickring sequence just
swap the any two phases of National Grid or Synchronous generator.
• Flickring rate shows the frequency difference, to set the frquency difference zero just
change the speed of Synchronous generator (increase or decrease is depend upon the
difference).
• The intensity of glow shows the Amplitude difference of both sinusoidal voltages, if
the glow intensity is high it means there is large difference between National grid
voltages and Synchronous generator voltages and vise versa.
• If All these condition fulfiled then turn on the synchronizing switch so that our
Synchronous generator will attached to the bus of national grid. Now its rpm depends
that either it is consuming or delivering the power to National Grid.
• After Synchronizing take reading of National grid and Synchronous generator
voltages and Synchronous generator current (of any one phase) and speed and torque
of Synchronous generator and active power of Synchronous generator.
• Increase the active power deliverd to National grid by Synchronous generator in
increments of 10 watts and record the measurments.
Circuit Diagram:
Results:
Resistive Load:
E1 I1 N